Zeta ZetaBeam Protection System Plus Скачать руководство пользователя страница 9

stage three, manual alignment

You will now see the manual alignment screen showing anything between 0 and 6%. This is the amount of 
received signal with no reflector that the beam is picking up from the environment.

10. 

NOW place or uncover

 the reflector on the blank wall directly opposite the beam head ensuring there 

is a clear path through any obstructions such as structural steels etc.

It is 

important

 that there is a clear line of sight between the reflector and beam head. The beam must 

see at least 

200mm

 of clear space around the reflector to enable the beam to see the edges of the 

reflector to allow successful auto alignment in the following stage.

Once the reflector is in place and visible there should be a big jump in the received signal (AQ). This 
means that the head is seeing and receiving a signal back from the reflector. In most cases this will result 
in a received signal of over 100%. 

As long as there is a received signal of over 40% you can move onto the next stage: Auto Alignment, 
No.11.

If the AQ reading is 

below 40%

 it means the head is not seeing the reflector and will abort Auto 

Alignment. The next stage is to manually move the beam to achieve an AQ reading of over 40%, ideally 
over 100%. The higher the AQ the quicker it will auto align. This is done by manually moving the x and y 
motors to obtain a received signal from the reflector.

In the example below we can see that the reflector is below the eye line of the beam head, so in this 
case you would need to lower the angle of the beam (-Y) until you receive an AQ of over 40%.

The beam can be moved on both X and Y axis to a maximum 5 degrees using the 

left (x-), right (x+), 

up (y+) and down (y-)

 keys. 

Looking at the reflector

 this will move the beam across 

the reflector like so...Holding the keys down will quickly scroll through to your desired 
position, on release of the button the screen will revert to the actual beam position and 
can be seen stepping toward the requested position.

To confirm the beam is seeing the 

reflector 

covering

 the reflector at any time should drop the AQ and prove the beam 

is on the reflector.

200mm of clear space from 
the edges of the reflector

Manual        AQ     136%

X+0.00

°        Y+0.00°  

Manual        AQ       13%

X+0.00

°        Y+0.00°  

Reflector is lower than the beam head... use -Y to bring the beam onto the reflector

Beam head

Reflector

In the example above moving the y axis 
down (y-) results in a greater AQ.

Try and achieve as high an AQ as possible, it must be over 
40% to auto align. The higher the AQ the quicker the auto 
align, above 100% is good.

Manual          

AQ   6%

X+0.00°

      

 Y+0.00°

down

Manual          

AQ   110%

X+0.00°

      

 Y-2.26°

down

y+

x+

x-

y-

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ZetaBeam Protection System Plus

Страница 1: ...The ZetaBeam Protection System Plus User Guide www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 40 to 80 metres the standard zetabeam mid range 4...

Страница 3: ...s and reflectors in environments that can be susceptible to condensation i e warehouses near to water that have areas open to the outside environment or that are exposed to quick extreme changes in te...

Страница 4: ...using colour coded terminals If this connection is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will r...

Страница 5: ...oller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manuf...

Страница 6: ...s 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Phase 2 Bayan Lepas Free Ind...

Страница 7: ...e current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is complete the ZetaBeam will automatically revert to normal low...

Страница 8: ...may be receiving a reflection from an object nearby and not the far wall By moving the beam looking at the far wall left x right x up y and down y you can move the beam path away from the obstacle By...

Страница 9: ...e higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is b...

Страница 10: ...signal is from the reflector Cover the entire reflector within one second If the beam is correctly targeted onto the reflector the AQ will drop to 0 max 10 and will fall into a fault condition after...

Страница 11: ...the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a self alignment normally becau...

Страница 12: ...d the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually be because you are receivi...

Страница 13: ...ory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys press enter t...

Страница 14: ...al This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and left keys press enter to...

Страница 15: ...n the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go into diagnostics IR power...

Страница 16: ...onds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO Contact Rating 2A 30 VDC Test Reset Features Beam test function by controller...

Отзывы: