Zeta ZetaBeam Protection System Plus Скачать руководство пользователя страница 1

The ZetaBeam

Protection System Plus

User Guide

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ZetaBeam Protection System Plus

Страница 1: ...The ZetaBeam Protection System Plus User Guide www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...head unit low level controller one reflector 3mm allen key and quick start installation guide this should be used for distances over 5m and up to 40m 40 to 80 metres the standard zetabeam mid range 4...

Страница 3: ...s and reflectors in environments that can be susceptible to condensation i e warehouses near to water that have areas open to the outside environment or that are exposed to quick extreme changes in te...

Страница 4: ...using colour coded terminals If this connection is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will r...

Страница 5: ...oller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manuf...

Страница 6: ...s 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Phase 2 Bayan Lepas Free Ind...

Страница 7: ...e current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is complete the ZetaBeam will automatically revert to normal low...

Страница 8: ...may be receiving a reflection from an object nearby and not the far wall By moving the beam looking at the far wall left x right x up y and down y you can move the beam path away from the obstacle By...

Страница 9: ...e higher the AQ the quicker it will auto align This is done by manually moving the x and y motors to obtain a received signal from the reflector In the example below we can see that the reflector is b...

Страница 10: ...signal is from the reflector Cover the entire reflector within one second If the beam is correctly targeted onto the reflector the AQ will drop to 0 max 10 and will fall into a fault condition after...

Страница 11: ...the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a self alignment normally becau...

Страница 12: ...d the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually be because you are receivi...

Страница 13: ...ory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right and left keys press enter t...

Страница 14: ...al This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and left keys press enter to...

Страница 15: ...n the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go into diagnostics IR power...

Страница 16: ...onds Alarm Indication Controller Status FIRE Controller Red Flashing LED Head Red Flashing LED Alarm Relay Change Over CO Contact Rating 2A 30 VDC Test Reset Features Beam test function by controller...

Отзывы: