SIMPLICITY USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-108 

 

 

PAGE 4

 

Issue: 2.00

     

Authorised: GH         Date: 04/06/2007 

 
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, 
INCLUDING THE FACP & ITS INTEGRAL PSE 

 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings 
(BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person 
to oversee the effective operation of the Fire Alarm System (Clause 47.1). 

 

Below is a summary of the main functions the “Responsible Person” is expected to carry out.  This summary is 
not intended to replace Section seven (User responsibilities) of BS5839: Pt 1: 2002 (available from BSI, or your 
local library). It is meant to give a brief outline of user responsibilities for the safe upkeep of the Fire Alarm 
System.  The number in brackets shows the relevant BS5839: Pt 1: 2002 clauses. 

 

The responsible person must:- 

 

1.  Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 
2.  Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 
3.  Ensure there are arrangements for testing and maintaining the system (47.2.c) 
4.  Ensure the log book is up to date, and available for inspection (47.2.d) 
5.  Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence 

alarms, silence faults and system reset (47.2.e) 

6.  Take appropriate action to limit the rate of false alarms (47.2.f) 
7.  Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 
8.  Liase with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere 

with the functioning and reliability of the fire alarm system (47.2.h). 

9.  Ensure any changes to the system are recorded with updated drawings, operating instructions etc (47.2.i) 
10.  Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 
11.  In the event of a prealarm, determine the cause & take appropriate action (predetermined fire routine if the 

cause is the start of a fire, arrange maintenance if the cause is a contaminated detector head) (47.3) 

 
With the Simplicity Fire Alarm Panel, we recommend the following tests are carried out: - 

 

Daily Inspection

 

 

Check that the green Power LED is lit. 

 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated 
site maintenance engineer. 

 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do not test the same device each week. Test a different zone each week using a different call point or 
detector so that eventually, all the devices will be tested. 

 

Reset the System by pressing 1,2,3 (Stop sounders, Silence fault tone, Reset). 

 

Turn key to controls enabled. Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

 

Check that no call points or fire detectors are obstructed in any way. (eg New furniture or decorations) 

 

Quarterly Test (to be carried out by authorised service personnel only)

 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

 

Annual Test (to be carried out by authorised service personnel only)

 

 

Check every detector, call point, sounder and all auxiliary equipment for correct operation. 

 

Check Transformer output Voltage (32 VAC), Charger Voltage (28.4V off load, adjusted with VR1) & 
Battery Voltage (25-27V) 

 

Every Five Years (to be carried out by authorised service personnel only)

 

 

Carry out a complete wiring check in accordance with the testing and inspection requirements of the 
relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be 
replaced because SLA batteries have a working life of 5 years.

 

Содержание SP-64

Страница 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK Simplicity Plus 64 OR 126 DEVICE CAPACITY SINGLE LOOP ANALOGUE ADDRESABLE FIRE ALARM CONTROL PANEL...

Страница 2: ...A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES O...

Страница 3: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Страница 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Страница 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Страница 6: ...ly as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in...

Страница 7: ...ssages for each device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the...

Страница 8: ...tion momentarily pressing the Start Stop will cause the Alarm sounders to sound Pressing the Start Stop button again will Silence the Alarm Sounders Note If the Alarm Sounders have been disabled press...

Страница 9: ...s there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that these batteries are no longer working If the mains sup...

Страница 10: ...curs the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Ta...

Страница 11: ...der needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELECT DISABLEMENT MODE eg to silence a fault on ano...

Страница 12: ...A OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs to know a...

Страница 13: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Страница 14: ...ing work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Страница 15: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 108 PAGE 14 Issue 2 00 Authorised GH Date 04 06 2007 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Страница 16: ...t No GLT MAN 108 PAGE 15 Issue 2 00 Authorised GH Date 04 06 2007 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Страница 17: ...roved Document No GLT MAN 108 PAGE 16 Issue 2 00 Authorised GH Date 04 06 2007 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Страница 18: ...all points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complia...

Страница 19: ...mmendations of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on...

Страница 20: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...