7. DISABLEMENTS 

 
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM. 

 
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions.  For 
example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is 
possible for the user to disable that zone during the risk period and then enable it again afterwards.  During a disablement 
of a zone(s), no fire or fault signal will be processed for that zone(s).  Only zone(s) in a non-alarm state can be disabled, 
that is zones already in a fire condition cannot be disabled. 
 
External sounders can also be disabled as could be required in certain conditions. 
 

7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS. 

 

1. 

Insert and turn control key to enabled position; 

 

2. 

Press DISABLE button and the screen will show: 
ZONE DISABLEMENT ZONE 1. The panel is now in  
SELECT DISABLEMENT MODE. 

 

3. 

Press DISABLEMENT SELECT until the required zone or  
sounder circuit is DISPLAYED. Press DISABLEMENT  
CONFIRM button. The screen will now show that the zone is 
disabled, and the Zone or Sounder LED will  
come on steady, along with the GENERAL DISABLEMENT  
LED. This section is now disabled. 

(NOTE: Call points in this zone  

will still be active. Contact the engineer if call points need to be disabled) 

 

4. 

If more than one zone (or sounder) needs to be disabled, then press DISABLEMENT SELECT again 
until the required zone (or sounder) is selected. 

 

5. 

If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on another 
part of the system), Either press DISABLEMENT button, or turn the keyswitch off, then back on again. 

 

6. 

Once all the maintenance work has been done the zones need to be enabled again. If the panel is still 
in SELECT DISABLEMENT MODE, jump to paragraph 7, otherwise, turn the keyswitch to controls 
enabled, press DISABLE button. The panel is now in SELECT DISABLEMENT MODE 

 

7. 

Press the DISABLEMENT SELECT button until the disabled zone is displayed on the screen. Press 
DISABLEMENT CONFIRM button to de-select disablement. Scroll to any other disabled zone and 
enable in the same way. When all zones are enabled again, the GENERAL DISABLEMENT LED will 
turn off. Turn the keyswitch to off position to return the system to normal. 

 

 

7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS. 
 

1. 

Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED 
with stay lit (steady); 

 

2. 

Press DISABLE button and the screen will show: ZONE DISABLEMENT ZONE 1. The panel is now in 
SELECT DISABLEMENT MODE.

 

 
2. 

Press SELECT until the disabled Zone or sounder is shown. 

  
3. 

Press CONFIRM to enable the selected item. The screen will now show enabled, and its disablement LED will turn 
off. The General Disablement LED will also turn off after all sections are taken out of disablement. 

 
4. 

Turn control Key to “Off” position and this will return the panel to normal operation. 

  Zone Disablement 
      Zone  3

        

 

Disabled 

Single Devices:  0 

  Zone Disablement 
      Zone  1

        

 

Enabled 

Single Devices:  0 

Содержание SP-64

Страница 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK Simplicity Plus 64 OR 126 DEVICE CAPACITY SINGLE LOOP ANALOGUE ADDRESABLE FIRE ALARM CONTROL PANEL...

Страница 2: ...A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES O...

Страница 3: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Страница 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Страница 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Страница 6: ...ly as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in...

Страница 7: ...ssages for each device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the...

Страница 8: ...tion momentarily pressing the Start Stop will cause the Alarm sounders to sound Pressing the Start Stop button again will Silence the Alarm Sounders Note If the Alarm Sounders have been disabled press...

Страница 9: ...s there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that these batteries are no longer working If the mains sup...

Страница 10: ...curs the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Ta...

Страница 11: ...der needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELECT DISABLEMENT MODE eg to silence a fault on ano...

Страница 12: ...A OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs to know a...

Страница 13: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Страница 14: ...ing work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Страница 15: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 108 PAGE 14 Issue 2 00 Authorised GH Date 04 06 2007 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Страница 16: ...t No GLT MAN 108 PAGE 15 Issue 2 00 Authorised GH Date 04 06 2007 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Страница 17: ...roved Document No GLT MAN 108 PAGE 16 Issue 2 00 Authorised GH Date 04 06 2007 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Страница 18: ...all points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complia...

Страница 19: ...mmendations of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on...

Страница 20: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...

Страница 21: ...in this certificate Name in block letters Position Signature Date For and on behalf of Address Postcode The extent of liability of the signatory is limited to the system described below Extent of the...

Страница 22: ...e Simplicity Plus Fire Alarm System installed at Address Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accor...

Страница 23: ...arm System installed at Address The following work is required before the system can be accepted All installation work appears to be satisfactory The system is capable of giving a fire alarm signal Th...

Отзывы: