SIMPLICITY USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-108
PAGE 10
Issue: 2.00
Authorised: GH Date: 04/06/2007
7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM.
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For
example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is
possible for the user to disable that zone during the risk period and then enable it again afterwards. During a disablement
of a zone(s), no fire or fault signal will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled,
that is zones already in a fire condition cannot be disabled.
External sounders can also be disabled as could be required in certain conditions.
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1.
Insert and turn control key to enabled position;
2.
Press DISABLE button and the screen will show:
ZONE DISABLEMENT ZONE 1. The panel is now in
SELECT DISABLEMENT MODE.
3.
Press DISABLEMENT SELECT until the required zone or
sounder circuit is DISPLAYED. Press DISABLEMENT
CONFIRM button. The screen will now show that the zone is
disabled, and the Zone or Sounder LED will
come on steady, along with the GENERAL DISABLEMENT
LED. This section is now disabled.
(NOTE: Call points in this zone
will still be active. Contact the engineer if call points need to be disabled)
4.
If more than one zone (or sounder) needs to be disabled, then press DISABLEMENT SELECT again
until the required zone (or sounder) is selected.
5.
If the panel needs to be taken out of SELECT DISABLEMENT MODE (eg to silence a fault on another
part of the system), Either press DISABLEMENT button, or turn the keyswitch off, then back on again.
6.
Once all the maintenance work has been done the zones need to be enabled again. If the panel is still
in SELECT DISABLEMENT MODE, jump to paragraph 7, otherwise, turn the keyswitch to controls
enabled, press DISABLE button. The panel is now in SELECT DISABLEMENT MODE
7.
Press the DISABLEMENT SELECT button until the disabled zone is displayed on the screen. Press
DISABLEMENT CONFIRM button to de-select disablement. Scroll to any other disabled zone and
enable in the same way. When all zones are enabled again, the GENERAL DISABLEMENT LED will
turn off. Turn the keyswitch to off position to return the system to normal.
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS.
1.
Turn key to “Controls enable” position (since a zone is already disabled at this time, the General Disablement LED
with stay lit (steady);
2.
Press DISABLE button and the screen will show: ZONE DISABLEMENT ZONE 1. The panel is now in
SELECT DISABLEMENT MODE.
2.
Press SELECT until the disabled Zone or sounder is shown.
3.
Press CONFIRM to enable the selected item. The screen will now show enabled, and its disablement LED will turn
off. The General Disablement LED will also turn off after all sections are taken out of disablement.
4.
Turn control Key to “Off” position and this will return the panel to normal operation.
Zone Disablement
Zone 3
Disabled
Single Devices: 0
Zone Disablement
Zone 1
Enabled
Single Devices: 0