Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 36 of 44
14/12/06
•
SW 2/8 - Silent Zone Test:
Select sounder response in One Man [Detector] Test Mode:
o
OFF: Sounders operate once on each test.
o
ON: Sounders do not respond to a zone test.
•
SW 2/9 - Buzzer Disable:
Enable/disable panel fire/fault buzzer.
o
OFF: Buzzer is enabled.
o
ON: Buzzer is disabled. General Disablement LED illuminated.
o
Not EN54 compliant function. Provided for commissioning purposes.
•
SW 2/10 - Latched Faults:
When enabled, all fault conditions latch until the Reset switch is operated.
o
OFF: Non-latched faults.
o
ON: Latched faults.
15.7
Configurable Options via DIL switch selection on Repeater Interface
Board:
DIL switch SW1 on the C1631 Repeater Interface PCB is used to set the quantity
of repeaters and the repeater addresses as follows:
o
To set the repeater quantity, set SW1 on the C1631 fitted to the fire alarm
panel in line with Table 2 - C1631 setting for quantity of repeaters.
Table 2 - C1631 setting for quantity of repeaters
SW 1
Repeater Quantity
0 1 2 3 4 5
1-1 Off On Off On Off On
1-2 Off Off On On Off Off
1-3 Off Off Off Off On On
o
To set the addresses of the individual repeater panels, set SW1 on the C1631
fitted to each repeater panel in line with Table 3 - C1631 setting for repeater
addresses. Note that each repeater must have a different address.
Table 3 - C1631 setting for repeater addresses
SW 1
Repeater Address
0
* 1 2 3 4 5
1-1 Off
On Off On Off On
1-2 Off Off On On Off Off
1-3 Off Off Off Off On On
* Note: Address 0 = repeater disabled.
15.8
Configuring the Fire Routing, Fire Protection and Fault routing O/Ps
To configure the Fire Routing Output to volt-free relay contacts, remove links J10,
J11 and J12. [These links are combined in a single block].
To configure the Fire Protection Output to volt-free relay contacts, remove links J14,
J15 and J16. [These links are combined in a single block].