4. FIRST FIX 

 

4.1 Mounting the Control Panel 

 

The control panel should be installed in accordance with the following recommendations:- 

 

The panel should be close to the main entrance of the building, so that it can be viewed 
by any fire-fighting personnel entering the building. 

 

It should be fitted to a sturdy wall that will not flex unnecessarily.  

 

It should be mounted at eye level, in order for it to be viewed without need of a ladder. 

 

It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight. 

 

It should be easily accessible, so that the responsible person can perform their regular 
fire alarm checks.  

 

4.2 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 

 

All wiring must be installed to meet BS5839: Pt1: 2002 and BS 7671 (Wiring Regs) standards.  
Other National standards of fire alarm system installation should be adhered to where 
applicable. 

 

Screened cables should be used throughout the installation to help shield the Panel from outside 
interference and ensure EMC compatibility. 

 

The two categories of cable according to BS5839: Pt1: 2002, Clause 26 “Fire Detection and Alarm 
Systems for Buildings (Code of Practice for System Design, Installation and Servicing)” are: 

 

Standard fire resisting cable – to PH30 classification of EN 50200 
Enhanced fire resisting cable – to PH120 classification of EN 50200 
(Note that all cables should be at least 1mm

2

 cross section 

 

On the Premier AD Panel the general recommendation would be to use standard fire resistant cable, 
such as GLT Exports Fire Defence Cable, Firetuff

 , FP200 or an equivalent. These cables are 

screened, and will provide good EMC shielding when properly grounded at the panel.  Certain system 
specifications may demand the use of a particular type of cable and due regard should be paid to this 
fact. 

 

Depending on the environment, the cables may need mechanical protection (such as a conduit). 

 

4.3 MAINS WIRING RECOMMENDATIONS 

 

The Mains supply to the FACP is fixed wiring, using 

Fire resisting

 3-core cable (Between 1 mm² and 

2.5mm²) or a suitable 3-conductor system, fed from an isolating double pole switch fused spur, fused 
at 3A.

  IT SHOULD NOT BE CONNECTED THROUGH AN RCD.

 This should be secure from 

unauthorised operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’.  The supply must be 
exclusive to the Fire Panel. 

MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE 

GROMMETS PROVIDED

 

 

For information on how to connect Mains to the Panel’s Power Supply PCB, see page 8. 
Also refer to rating information on the mains cover inside the FACP. 

 

Содержание Premier AD

Страница 1: ...INSTALLATION MANUAL...

Страница 2: ...OCIATED SOUNDER BASES 15 8 4 SUPPORTED SOUNDER TYPES THEIR APPLICATIONS 15 9 AUXILIARY INPUTS OUTPUTS 16 9 1 AUXILIARY INPUT WIRING EXAMPLES 16 9 2 AUXILIARY OUTPUT WIRING VOLTAGE FREE CHANGEOVER CONT...

Страница 3: ...ith our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 20...

Страница 4: ...The screen is simply there to identify loop device fault locations and to help in setting up the panel 2 2 ADVANTAGES OF AN ADDRESSABLE FIRE ALARM SYSTEM The table below lists the main advantages of a...

Страница 5: ...elow Old CPU 3 large ICs New CPU 2 small surface mount ICs If the control panel has the OLD CPU card then some of the options in this manual will not be applicable Contact your supplier to obtain Vers...

Страница 6: ...op sounders address 113 to 126 which allows 14 devices Each option has advantages disadvantages Check the Sounder option chart on page 15 for information 3 If zonal sounder operation is required loop...

Страница 7: ...ire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting...

Страница 8: ...oved by a push from inside the control panel box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c...

Страница 9: ...s connected the protective cover should be replaced BEFORE turning on the mains power This will minimise the chance of electric shock from the PCB MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE...

Страница 10: ...nder A maximum of 32 loop powered addressable sounders or sounder bases are permitted on the loop On the Premier AD Panel all Sounder Bases are always configured as common sounders Short circuit isola...

Страница 11: ...L2 L 1 I O U T L1IN R C RELAY OUTPUT Note that on the Fyreye Loop Isolator Base the loop wiring connects to the terminal block on the PCB and NOT to the Base Spring Screws The terminals are marked in...

Страница 12: ...Base 80 090 FE IB Fyreye Addressable Loop Isolator Base 80 100 FEA SB Fyreye Addressable Sounder Base 80 101 FEA ISB Fyreye Addressable Isolator Sounder Base 43 305 ZT CP2 AD Zeta Addressable EN54 Cal...

Страница 13: ...at during an alarm condition maximum current draw the voltage at all detectors must be at least 17 Volts with at least 5V of superimposed data signal The exact calculation equations are beyond the sco...

Страница 14: ...N 3 OFF 2 ON 1 OFF As an alternative to using this chart use the table on the following page SW 4 3 2 1 OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111 LOOP 1 LOOP 2 SW...

Страница 15: ...off off on on on 46 on off off off on off on 78 on off off off on on off 110 on off off off on off off 15 off off off off on on on 47 off off off off on off on 79 off off off off on on off 111 off of...

Страница 16: ...on any alarm Note that the Premier AD has a preset time out of 3 minutes after which ALL loop sounders will start even one from a different zone 8 3 ASSOCIATED SOUNDER BASES Associated sounder bases...

Страница 17: ...wiring options CLASS CHANGE 2nd Fire Alarm AUX FIRE RELAY CM NO CLASS CHANGE The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens sho...

Страница 18: ...wer supplies The panel supports up to 4 repeaters Connections Premier AD Termination PCB AD Repeater SERIAL REPEATER COM SERIAL REPEATER COM AUX SUP 28V AUX SUP 0V 11 2 SERIAL PRINTER CONNECTION The P...

Страница 19: ...o configure the loops The panel displays configuration in progress Please wait It will return to Configuration Menu 2 when completed 7 Press PREVIOUS button followed by button 1 to view the loop conte...

Страница 20: ...s shown below Note if every detector has a sounder base or if most of the detectors have a sounder base this speed up operation will have little or no effect 1 Press enter NEXT followed by 369 to ente...

Страница 21: ...rm Fault Description If the device is in a fault condition a description of the fault will appear here It will show one of the following messages FAULT MEANING Changed The device had been changed with...

Страница 22: ...vent number the date the time the type of event in this case a DEVICE ALARM and the Zone loop and address if appropriate Next Previous buttons will cycle through the list Faults Selecting this option...

Страница 23: ...ximum value of 524287 and will return to 0 after this 12 8 CHECKING SOFTWARE VERSION The Premier AD now has the ability to view the software version from the screen From Configuration menu 2 select co...

Страница 24: ...y along with the GENERAL DISABLEMENT LED This section is now disabled NOTE Call points in this zone will still be active To disable the call points as well disable them individually as points see 13 3...

Страница 25: ...re one or more disabled points in this zone the screen will show TIP a quick way to enable several disabled points is to disable the zone then re enable it To view from the Device Status screen press...

Страница 26: ...til all smoke spray has cleared from the detector 8 Once testing of that zone is completed press TEST FUNCTION SELECT button to move to another Zone or turn the control key switch to off position to e...

Страница 27: ...ssing device and check if it has its LED on Detector or check the dip switch setting 4 If this does not cure all double addresses go to the known location and temporarily remove the device The panel w...

Страница 28: ...hing is shorting to earth usually through the cable screen Disconnect the earth screens one at a time to determine the problem line Note connecting other equipment eg an oscilloscope to the panel can...

Страница 29: ...10 LOOP WIRING FAULTS A loop fault can be caused by a break or short circuit in the Loop wiring Open the panel and look for the 4 green LEDs on the termination PCB Under normal conditions these should...

Страница 30: ...Input Output Unit ZIOU 2 2 10 16 32 Zeta Sounder Control Module ZSCC 2 2 10 16 32 Zone Monitor Unit ZT ZM 6 8 30 22 10 20 Fyreye Addressable Beam Detector 5 50m ZTA FR50 t b c t b c t b c t b c t b c...

Страница 31: ...al Example A system comprises of 160 Addressable Optical detectors 64 Sounder bases and the required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required T...

Страница 32: ...t to loop 2 side B 8 SND 4 Connect to sounder circuit 4 sirens bells 9 FIRE RELAY NO CM NC Activates on fire including test mode 10 FAULT RELAY NO CM NC Normally powered ie NO is closed with no fault...

Страница 33: ...AL 18 32 V SYSTEM VOLTAGE RIPPLE 2V PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 24V DC NOMINAL 9 volt data SOUNDER ALARM OUTPUTS 4 x 250mA 24V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY...

Отзывы: