Zeta Alarm Systems
PC3K
User’s Manual
Revision 1.0
Part # 3000-0002
Page 40 of 46
to 5000 feet away with only a 4-wire connection. A total of up to 127 serial devices may be connected with a
twisted, shielded pair for communication and a standard pair for 24VDC power.
Additional modules provide an optically isolated printer port (ICP) secondary network port (SNP) and local
energy/reverse polarity city box connection (CBM).
19.3 Specifications
19.3.1 Listings
•
UL 864 listed for local, central station, remote station
•
CSFM and NY BSA/MEA pending
19.3.2 AC Power
•
120/240 VAC or 208/220 VAC 50/60Hz
•
Smart, Universal Power Supply
19.3.3 DC Power
•
Standard 5.75 Amps total available for all outputs combined
•
7.5 Amp supply optional
•
Intelligent multi-rate battery charger
•
All outputs are power limited and filtered
19.3.4 Initiating Circuits
•
2 Digital SLCs standard, expandable to 12 SLCs
•
Digital communication protocol
•
8,000 ft. wire run with 16AWG cable
•
Uses standard fire rated cable
•
126 Addressable devices per SLC
•
Style 4, 6, or 7 configuration
•
All circuits fully supervised
•
All circuits protected from surges
19.3.5 Notification/Auxiliary Power Circuits
•
4 Programmable, supervised (NAC), and power limited circuits plus dedicated network power
•
Each circuits programmable to be either a notification or auxiliary power output
•
Notification circuits can be Style Y or Z
•
Auxiliary power circuits can reset or be continuous
•
2 Amp limit on current draw per circuit subject to limitation of power supply
•
All circuits are power limited and filtered
•
All circuits fully supervised and protected from surges
•
Programmable signal patterns: March Time, ANSI Temporal Code, Steady
19.3.6 Panel Annunciation
•
80 Character backlit LCD
•
LEDs for Alarm, Trouble, Supervisory, Silenced, AC-Power, Off-line, and Test Mode
•
16 Button keypad
19.3.7 Relay Outputs
•
System alarm relay form C
•
System trouble relay form C
•
Up to 20 ZRM zone relays, form C, optional
•
All relays rated at 5 Amps