MKII-xx Installation Guide 

 

32-0067-r03                                                             

  2 / 2 

17/10/2017

 

Zeta Alarms Limited, 72/78 Morfa Road, Swansea, SA1 2EN

 

 

SPECIFICATION 

 

EN54-5/7 approval 
Supply Voltage: 10.5~33V 
Alarm Current: 35-45mA at 24 volts 
Quiescent Current: 70uA Maximum 
Smoke Sensitivity: 0.08 dB/m - 0.12 dB/m 
Temperature class:    A2R (for MKII-HR); A2S (for MKII-HF) , CS (for MKII-HF/CS90) 
Humidity Range: 0% to 95% Relative Humidity, non condensing 
 

Maintenance Information 

 

Fyreye Mk II detectors are generally installed as part of a fire alarm system. 
Servicing of the system should be carried out in accordance with the requirements of the local code of practice for 
fire alarm installations, eg. BS 5839 Part 1, Fire Detection and Alarm Systems for Buildings: Code of Practice for 
System Design, Installation and Servicing. 
The frequency of inspection testing will be based on a risk assessment of the installation, but should be no more 
than 6 months between visits. 
Over a 12 month period every detector should be functionally tested, using suitable equipment to generate smoke 
or heat (EG the Solo range from No Climb Products) 
All Fyreye Mk II conventional smoke detectors have an IR transmitter that periodically transmits chamber data. 
This allows the detectors sensor status to be checked with a Sensitivity Test Wand. 

 

Cleaning 

 

Cleaning a smoke detector can prolong its working life. The detector can be cleaned with:- 
 

A hand held vacuum cleaner 

 

A clean air line or a “duster” aerosol 

 

A lint free cloth. 

The effectiveness of cleaning will depend on the operating environment of the detector. Depending on timescales 
& financial considerations, detector cleaning may not be a practical option. 

 
When to replace a detector 

 

A detector should be considered as needing to be replaced if:- 

 

The detector does not respond to a functional test 
If the detector has had an unexplained activation* 
If the detector has been in service for more than 10 years** 

 

* In some cases it may be sensible to leave a detector until a second unexplained activation, but consider the extra 
service costs and perceived system integrity if this is done. 

 

** Many detectors will continue to function adequately way beyond 10 years service. Balance the frequency of 
unwanted alarms, with the cost of replacing detectors when making this decision. 
 

 

 

0832 

 

Zeta Alarms Limited, 72-78 Morfa Road, Swansea SA1 2EN 

 

17 

 

0832-CPR-F0067/F0069/F0071/F0073/

F1922

 

EN54-5:2000+A1:2002   

Heat detectors — Point detectors 

 

EN54-7:2000+A1:2002 + A2: 2006 

Smoke detectors — Point detectors using scattered light, 

transmitted light or ionization 

 

MKII Conventional detectors 

MKII-OP, MKII-OH, MKII-HR, MKII-HF, MKII-HF/CS90 

 

Other Technical Data: See Doc: “MKII-xx LPCB, MKII-xx/CS LPCB” 

held by the manufacturer 

      