INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624

   

 

Approved Document No: GLT2-211-7-2 

 

  

PAGE 21

 

Issue 1.00         Author: NRPJ      Date: 23/1/2013 

10. COMMISSIONING THE SYSTEM, INCLUDING POWER SUPPLY EQUIPMENT P.S.E. 

 

The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has an 
understanding of sections 2, 3, & 4 of BS5839 pt 1:2002 (i.e. Design considerations, Limitations of false alarms, Installation 
recommendations). 

 

The system layout drawing should be checked for accuracy & stored in a safe place, accessible to any fire officer. 

 

The system set-up data (section 8) should be checked for accuracy. 

 

The fire alarm log book contact details should be checked for completeness. 

 

The insulation of cables should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance. 

 

The Earthing should be checked in accordance with BS5839 Pt1: 2002 clause 38.2 for compliance. 

 

The PSE mains feed from a 3A spur should be checked. It should be protected by an over current device (MCB) NOT an 
earth leakage device (RCD). 

 

The PSE Charger voltage should be checked & adjusted if necessary (28.3 with batteries disconnected). 

 

The battery voltage should be checked (should be between 24 & 27V). 

 

All call points & detectors can signal an alarm condition and indicate the correct zone (and text message) on the fire alarm 
panel. 

 

The Sound pressure level throughout the building should be checked for compliance with the recommendations of 
BS5839 Pt1: 2002 clause 16.2. 

 

Any deviations from BS5839 Pt1 clause 7.2 should be listed in the Certificate of Installation & Commissioning. 

 

The Certificate of Installation & Commissioning should be completed, and the whole user manual passed to the relevant 
person on site. (They should be given a brief training on the basic operation of the FACP). 

10.1 DESIGN, INSTALLATION & COMMISSIONING CERTIFICATES 

The guidelines in BS 5839 Pt1: 2002 say that each stage of the system design and installation should have a separate certificate. 
Before this User Manual is handed over to the relevant person(s) on site, the following certificates (or the relevant company’s 
equivalent) should be completed by the system designer, the installation engineer and the commissioning engineer. The System 
Description sheet should also be completed on Pages 12-20 as should the relevant parts of the Log Book section. 

The user or responsible person should then complete the acceptance certificate to acknowledge that they have been instructed in 
the use of the fire alarm, have witnessed that it is operational, and have been given all the relevant paperwork (drawings, log book, 
user manual, etc.). 

Содержание ID2/2

Страница 1: ...IDE LOG BOOK Software Versions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 0 Issue 1 00 Author NRPJ Date 23 1 2013 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ID TECHNOLOGY...

Страница 2: ...CATION LEDS 6 4 6 WHAT THE LEDS MEAN 6 5 THE FIRE CONDITION 7 5 1 HOW THE SIMPLICITY INDICATES AN ALARM 7 5 2 TO TURN OFF THE ALARM SOUNDERS 7 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4...

Страница 3: ...d have activated it Steam cooking food exhaust smoke excessive dust etc can all activate a smoke detector If anything is found try to clear the room by opening a window If a fire is discovered call th...

Страница 4: ...evacuated and the fire extinguished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or...

Страница 5: ...that there are spare parts especially Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is...

Страница 6: ...roll between Messages menus The General Test button is used to control the one man test mode The General Disablement button is used to select disablements The numeric section is for entering access co...

Страница 7: ...ained by pressing the test button and entering the test code This is a factory preset code which cannot be changed Here the user can put any of the zones or sounder circuits into test mode Turn the ke...

Страница 8: ...ls internal buzzer can also be silenced by pressing the Silence Buzzer button 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE If another detection Zone is activated after the Alarm Sounders have b...

Страница 9: ...t 1 Mains Fault 2 Battery removed 3 Battery low 4 Battery High Impedance Earth Fault 1 Earth Fault Positive 2 Earth Fault Negative Sounder Fault 1 Sounder Open Circuit 2 Sounder Short Circuit 3 Faults...

Страница 10: ...Log Book at the back of this Manual Take appropriate action to correct the fault Usually by contacting the service engineer On the Infinity ID2 panel the fault indications except system fault are non...

Страница 11: ...SER MANUAL MAINTENANCE GUIDE LOG BOOK Software Versions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 10 Issue 1 00 Author NRPJ Date 23 1 2013 6 3 OTHER LED INDICATIONS DISABLEM...

Страница 12: ...een will then show ZONE DISABLEMENT ZONE 1 The panel is now in SELECT DISABLEMENT MODE 5 Press NEXT BUTTON until the required zone or sounder circuit is DISPLAYED Press ENTER to confirm the disablemen...

Страница 13: ...4 5 6 7 8 SOUNDER CIRCUIT INFORMATION SOUNDER CIRCUIT SOUNDER CIRCUIT DESCRIPTION A brief description of all the rooms and areas contained in each zone QTY SNDR QTY BELL QTY STROBE 1 2 OUTPUT ROUTING...

Страница 14: ...tem handover ID Type Description Verify Sndr Flsh ID Type Description Verify Sndr Flsh ID Type Description Verify Sndr Flsh Zone 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Zone 2 1 2 3 4 5 6 7 8 9 10 11 12...

Страница 15: ...th a note of any outstanding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS58...

Страница 16: ...OK Software Versions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 15 Issue 1 00 Author NRPJ Date 23 1 2013 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK...

Страница 17: ...ftware Versions PANEL 0 X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 16 Issue 1 00 Author NRPJ Date 23 1 2013 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR...

Страница 18: ...R624 Approved Document No GLT2 211 7 2 PAGE 17 Issue 1 00 Author NRPJ Date 23 1 2013 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE V...

Страница 19: ...Approved Document No GLT2 211 7 2 PAGE 18 Issue 1 00 Author NRPJ Date 23 1 2013 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENA...

Страница 20: ...X R8629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 19 Issue 1 00 Author NRPJ Date 23 1 2013 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAI...

Страница 21: ...629 LOOP 0 J R624 Approved Document No GLT2 211 7 2 PAGE 20 Issue 1 00 Author NRPJ Date 23 1 2013 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION...

Страница 22: ...d should be between 24 27V All call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the buildi...

Страница 23: ...hat the said design for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described b...

Страница 24: ...able for min Appropriate guidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended tha...

Страница 25: ...h the specifications described below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf...

Страница 26: ...use 39 of BS 5839 1 2002 see clause 7 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and t...

Страница 27: ...ent of the system covered by this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an...

Отзывы: