Zeta 200 CO Скачать руководство пользователя страница 2

- 2 -

 

(d)  In exhaust streams from gas engines, vents, flues or chimneys 
(e)  Do not place in close proximity to an automobile exhaust pipe; 

this will damage the detector 

INSTALLING YOUR DETECTOR 

The Carbon Monoxide Detector is easy to install to protect you and 
your family in your home, cottage, cabin and office.   

The product can be installed flush mounted set into a wall/partition. 
You will need the following tools to install the unit: 
 
Drill with a 6mm bit 
Phillips screwdrivers 
 
The product is designed with the cables emerging from the bottom 
of the unit. 
 
Flush mounting 
 
In order to flush mount the unit a suitable hole will needs to be cut 
in the wall. This will need to be 150mm wide by 90mm high and a 
minimum of 40mm deep. The power supply cabling and 
connections for the Remote LED and relay (if used) will need to 
come from behind or inside the wall. This will normally be via 
conduit in solid wall or from inside the outer skin of a partition wall. 
Once mounted in the hole in the wall, the unit can be secured to the 
wall using the two screws provided (and if needed the raw plugs) 
through the two holes either side of the base. 
 
  Figure 1 – Flush Mounting 
 
 

 

 

Before connecting power ensure you have selected the correct 
connection for either mains or DC installation, checking the label on 
the product. 
 
Feed the cables for the power (and, if used, the relay and Remote 
LED) up from the underside of the base. The cables are then 
secured using the cable clamps provide. The cable clamp can be 
reversed to accommodate larger cables as shown. 
 
 
 
 
 
 
 
 
Figure 2 Cable Clamps     
 

 

 
Mains Powered Connect 
 
CAUTION: ISOLATE THE MAINS BEFORE STARTING WORK 
 
The detector should be wired to the mains supply via an 
unswitched fused outlet to BS5733. The fuse should be rated at 3 
Amps. The brown or red wire should be connected to the live 
terminal shown L below and the blue or black wire should be 
connected to the neutral terminal shown N. The earth terminal is 
not required. 
 
Figure 3 AC Supply Wiring 

 

 
DC Powered Connect 
 
The detector should be wired to the 12V or 24V supply with a fuse 
rated at 3 Amps. The red wire should be connected to the terminal 
shown below with a + (plus) sign and the black wire to the negative 
terminal shown with a – (minus).    Reversing the connections may 
damage the product. 
 
In caravans and motorhomes the detector should be connected to 
the battery supply via the main switch. This will ensure operation 
when the caravan is occupied. Permanent connection for prolonged 
periods may cause a flat battery if the battery remains uncharged 
 
Figure 4 DC Supply Wiring 
 

 

 
HOW TO USE THE RELAY FACILITY 
 
The relay provides a means of signalling an alarm condition to an 
external warning device such as control panel or remote audible 
buzzer. It can also be used to shut off a gas valve in the event of a 
detected leak. The relay is a single pole changeover type that 
allows contacts to be either open or closed when gas is detected. 
Relay contacts can be wired in parallel to provide an alarm signal 
when any of the units connected detect gas. 
 
For the mains powered versions the relay contact is specified up to 
240V @ 6A ac and for DC powered versions its is specified at 24V 
@ 6A   
 

Отзывы: