To connect the mains to RigSwitch cabinets, bring in a suitable 3
phase supply at 100A per phase maximum, to the main isolator top left
of the cabinet, and a secure mains earth to the Earth busbar at the top
of the cabinet. RigSwitch will accept a maximum 35mm
2
input supply
cable.
Top Cable Entries
2x Flange:
14x ø11mm
8x ø15mm
2x ø28mm
Relief stamp:
2x M32/M40
Connecting channel outputs
Double stacked load output terminals for live and neutral per channel
are situated top right of the cabinet, and will accept a maximum 6mm
2
cable. Earths will share the main bus bar top left of the cabinet.
Each block of 12 channels is rated at a maximum of 192A load.
Top Cable Entries
2x Flange:
14x ø11mm
8x ø15mm
2x ø28mm
Relief stamp:
2x M32/M40