DEFROSTING
MEDIUM TEMP
GENERAL
Periodic defrosting to keep the coil free of frost is accomplished automatically by a time clock. Medium temperature cases generally
operate at temperatures that allow for off-cycle defrost. Medium temperature cases that operated at colder temperatures for fresh meat
products may use electric or hot gas defrost.
DEFROST SETTINGS AND CONTROLS
Off-Cycle Defrost
Frequency: Two off-cycle defrosts per day are recommended.
Duration: Generally defrost is terminated on time with the recommended setting of 30 minutes. If temperature termination is selected, the
termination temperature is set for 45°F for discharge air and coil temperature. Stocking or shopping activities during defrost may result in
premature defrost termination.
ELECTRIC AND HOT GAS DEFROST
Follow the setting recommendations found in the
DEFROST OPERATION
Off-Cycle
For off-cycle defrost, refrigeration to the unit is stopped either by stopping the compressor or closing the liquid line solenoid valve and
allowing the compressor to pump down. During an off-cycle defrost, the fans, lights, and anti-sweat heaters remain on.
Electric and Hot Gas
For a description of these defrost types see the
44 • Defrosting - Medium Temp
Содержание 3RMCC30WA
Страница 2: ......
Страница 4: ......
Страница 36: ...ELECTRICAL LOW TEMP Figure 26 Electric Defrost 30 24 Wiring 32 Electrical Low Temp...
Страница 37: ...ELECTRICAL LOW TEMP CONT Figure 27 Hot Gas Wiring Electrical Low Temp 33...
Страница 38: ...ELECTRICAL LOW TEMP CONT Figure 28 Single Point Wiring 34 Electrical Low Temp...
Страница 39: ...ELECTRICAL LOW TEMP CONT Figure 29 Master Satellite Wiring Electrical Low Temp 35...
Страница 40: ...ELECTRICAL MEDIUM TEMP Figure 30 RVCC30 and RMCC24 Wiring Diagram 36 Electrical Medium Temp...
Страница 41: ...ELECTRICAL MEDIUM TEMP CONT Figure 31 Single Point Wiring Electrical Medium Temp 37...
Страница 42: ...ELECTRICAL MEDIUM TEMP CONT Figure 32 Master Satellite Wiring 38 Electrical Medium Temp...