REMOTE BLOWERS (EXTERNAL AND IN-LINE)

CAUTION: To reduce risk of fire and electric shock, install this range hood only with External
Blower Model CBE-1000, and In-Line Blower Model PBN-1000A. Other blowers cannot be
substituited.

INSTALLING THE DUCTWORK: REMOTE BLOWER

NOTE: To reduce the risk of fire, use only metal ductwork.

1. Choose the location where the External Blower or In-Line Blower will be mounted. See

illustrations below for mounting location suggestions and restrictions.

2. A straight, short duct run using a minimum 8” round duct will allow the hood to perform

most efficiently.

3. Long duct runs, elbows and transitions will reduce the performance of the hood. Use as

few of them as possible. Larger ducting may be required for best performance with long
duct runs.

4. After the External or In-Line Blower has been installed, connect round metal ductwork

and work back towards the hood location. Use duct tape to seal joints between ductwork
sections.

Roof Pitch w/
Flashing & Cap

in-line

blower

(blower

housing)

(blower

housing)

external blower

Attic or  crawl space

Содержание ADL-E42BSX

Страница 1: ...www zephyronline com RANGE HOOD Installation and use instructions ENGLISH 3 FRAN AIS 29 Layers Island ALL M90BBX ALL M90BWX ALL E42BBX ALL E42BWX Duo Island ADL M90BSX ADL E42BSX...

Страница 2: ...mum 6 round duct will allow the hood to perform most efficiently 3 Long duct runs elbows and transitions will reduce the performance of the hood Use as few of them as possible 4 Install a roof cap Con...

Страница 3: ...the flange may already be pre installed Fig 8 2 Remove the blower plate unscrewing the 4 3 9x9 5 mm screws Fig 9 3 Install internal blower into blower plate and secure using 4 screws Fig 10 4 Install...

Страница 4: ...x9 5 mm screws Fig 13A 2 Make connections B C D Fig 13 3 Remove the wiring box cover Remove a knockout from the wiring box Fig 14E 4 Secure the conduit to the wiring box through a conduit connector 5...

Страница 5: ...or mounting location suggestions and restrictions 2 A straight short duct run using a minimum 8 round duct will allow the hood to perform most efficiently 3 Long duct runs elbows and transitions will...

Страница 6: ...etails refer to manual included with the blower 1 Remove the blower plate unscrewing the 4 3 9x9 5 mm screws Fig 15 2 Install the external blower plate and secure using 4 3 9x6 mm screws Fig 16 3 Inst...

Страница 7: ...electrical connections remote blower box marked motor connection Connect white to white black to black blue to blue red to red green to ground Fig 18B 6 Replace the wiring box covers and screws Make s...

Страница 8: ...n the 8 screws in the height adjustment holes as necessary Insert 8 screws 3 9x6 mm located in the Hardware Package Fig 19 4 Secure the support frame to joists and cross framing with four 4 screws pro...

Страница 9: ...e air to the outside 3 Tape all duct joints with aluminum duct tape NON DUCTED INSTALLATION ONLY Note a Purchase Model ZRC 01LL Non ducted Recirculating Kit from your local dealer b Rooms with 10 to 1...

Страница 10: ...th 4 3 9 x 9 5 mm screws Fig 24 Vents may be exposed on 10 to 12 foot ceilings 2 Secure the two lower duct covers parts to the support frame by overlapping the lateral magnets Fig 25 FIG 24 FIG 25 UPP...

Страница 11: ...filter into place and release tab Make sure the filter is securely engaged after installation NON DUCTED HOODS ONLY 1 To remove the CHARCOAL filter grip and push filter tab toward rear of hood Pull th...

Страница 12: ...0031 Metal Mesh Filter ALL 50200033 OPTIONAL ACCESSORIES Recirculating Kit ADL ALL ZRC 01LL Replacement Charcoal Filters ADL ALL Z0F 01AC Extension Flue up to 12 ADL ALL Z1C 02LL To order parts visit...

Отзывы: