DATASHEET / OPERATING INSTRUCTONS

 

 

 

 
TEMPERATURE COMPENSATION MODELS, type number example ZAT1600/27,4/60/T

 

 

 
 

The temp.comp cable enables the charger to adjust the 
output voltage in accordance with battery voltage and 
temperature fluctuations 

 

 
 
 
 

 

 
 

Temp.comp. / sense 
Modular connector 

See instructions for changing and adjusting the output 
voltage 

 

 

OPTIONAL MASTER SLAVE CONNECTION

 

 

Using master power supply together with Slave unit. 

 

Master unit can be trimmer adjustable standard model ADC7520/24, analog controllable model ZAT1600/24/60/AI 
or temp.comp. model ZAT1600/27,4/60/T (24V as an example). 

 

Note ! 
Unit with relay alarm, type example ZAT1600/24/60/H can’t be used as a master unit. 

 

Slave unit is separate unit without any adjustment possibility, type ADC7520/24S or ADC7520/24SH slave with relay 
alarm (24V as an example). 

 

If more current is needed adjustable Master power supply can be parallel or series connected via digital bus to Slave 
power supply which equals Master but is without adjustment possibility. Then output current or voltage is doubled and 
the both supplies can still be adjusted thought multi turn potentiometers. Max one slave unit can be used in master-slave 
connection as a standard. (Please contact your local distributor if more slave units are needed to chain, needs special 
terminals/wires). Supply’s output terminals and communication bus terminals are isolated so that output's series 
connection is allowed for more voltage. 

 

Bus cable connection:

 

 

 
 
 

Master unit

 

 

 
 
 
 
 

Slave unit

 

 

Bus cables can be connected from 
previous units (J5) to the next (J5) 
with the same way. The first unit 
must be the master unit (with 
adjusting knobs). Wrong connection 
does not damage the units but in that 
case slaves does not follow the 
master's commands. Quantity of the 
slave units is limited to max 1 pcs 
due to digital bus terminals. In J5 
Pins 1 and 3 are serial output pins 
and pins 2 and 4 are serial input pins. 
Pin 1 is connected to pin 4 of  J5 in 
the next unit and pin 3 to pin 2 of  J5 
in the next unit. 

Содержание ZAT1600 SERIES

Страница 1: ...600W Power Supplies and Battery Chargers ZAT1600 SERIES TASHEET OPERATING INSTRUCTIONS Wide output adjustment range 0 72VDC Analog control by external 0 5VDC voltage Temp comp charging sense as on option Power fail relay alarm Master Slave connection Analog control modular connector Microprocessor controlled charging curves for all kind of batteries Master Slave connection ...

Страница 2: ... see table Output current see table Max power Installation dimensions Width x Height x Depth mm ZAT1600 27 4 60 T 55 264VAC 78 340VDC 27 4 VDC 5 36VDC 60 A 1600W Wall Bench 267x135x85 ZAT1600 41 1 45 T 55 264VAC 78 340VDC 41 1 VDC 12 54VDC 40 A 1600W Wall Bench 267x135x85 ZAT1600 54 8 30 T 55 264VAC 78 340VDC 54 8 VDC 24 72VDC 30 A 1600W Wall Bench 267x135x85 Cable sets with modular connectors are...

Страница 3: ...sions l x w x h 267 x 135 x 85 mm with rubber ends Weight 1 9kg without output cables Mounting Wall bench Cooling Temperature controlled fan Operating temperature range Full power typically 25ºC 40ºC Reduced power 40 70ºC see curve below Humidity 0 95 non condensing DATASHEET OPERATING INSTRUCTIONS TECHNICAL DATA Input voltage 50 260 VAC 50 200VAC reduced power see curve below 50 340 VDC 50 200VDC...

Страница 4: ...nstant orange light To avoid sparking turn the power off before disconnecting the cables CONNECTION WITH DC INPUT Wires in PSU s power cable to be connected as follows L DC input positive or negative N DC input negative or positive PE Ground OUTPUT VOLTAGE AND CURRENT LIMIT ADJUSTMENT Trimmer or analog control adjustable modules type example ZAT1600 24 60 or ZAT1600 24 60 AI The output voltage and...

Страница 5: ... code Switch N N PIN CONFIGURATION MODULAR CONNECTORS Front panel Rear panel J1 Analog input 0 5VDC J3 Temperature compensation Sense option J5 RS 232 bus in and out master slave Alternatively power fail relay alarm OPTIONAL ALARM RELAY If the unit is ordered with alarm relay for example ZAT1600 24 60 H the potential free alarm output indicates if the charger s output is healthy The alarm signal i...

Страница 6: ...output terminals That allows serial and parallel connection to separate power supply s so that equal steering voltages are used Number or connected devices are not limited Only be sure that 500V insulation voltage is not exceeded Connection example using internal 5VDC power source and external potentiometers 5V output can be used to feed logic voltages for external circuits Connection in an exampl...

Страница 7: ...le If more current is needed adjustable Master power supply can be parallel or series connected via digital bus to Slave power supply which equals Master but is without adjustment possibility Then output current or voltage is doubled and the both supplies can still be adjusted thought multi turn potentiometers Max one slave unit can be used in master slave connection as a standard Please contact y...

Страница 8: ...rrent 5 5 0 12 VDC 11 4 VDC 12 6 VDC 45 A 1 12 VDC 13 7 VDC 13 VDC 14 39 VDC 45 A 2 15 VDC 14 3 VDC 15 75 VDC 45 A 3 20 VDC 19 VDC 21 VDC 45 A 4 24 VDC 22 8 VDC 25 2 VDC 45 A 5 24 VDC 27 4 VDC 26 VDC 28 77 VDC 45 A 6 30 VDC 28 5 VDC 31 5 VDC 45 A 7 33 VDC 31 4 VDC 34 65 VDC 45 A 8 36 VDC 34 2 VDC 37 8 VDC 45 A 9 38 VDC 36 1 VDC 39 9 VDC 45 A A 36 VDC 41 1 VDC 39 VDC 43 16 VDC see curve B 36 VDC 41...

Страница 9: ...ut cables of the charger output short circuit Connect the charger to the power line Follow the Status led color Switch ON the charger from the on off switch Count all the number of green blinks There must be as much number of blinks as the code switch position number is Note If the position of the code switch is O Status led blinks only once and returns to red The code switch positions A F respond...

Страница 10: ...e The output voltage can be tuned 5 from its nominal value Choose such programmed output voltage which can reach the desired voltage by 5 adjustment Read the instruction from Changing programmed voltage Connect the voltage meter to output wires Tune with a small screw driver the voltage calibration trimmer and check the result from volt meter Clockwise direction increases the voltage Look at the p...

Отзывы: