ZoningBOX 6 / ZoningBOX 4
Technical Support:
25
Cool Mode:
T
GSP
= T
RET
− Max (0, RInt (Max(T
REFi
− T
LSP
i
)))
Example 1
– Heating mode:
Return Temp. to the unit (T
RET
) = 19ºC
Zone 1
Reference Temp. (T
REF1
): 21ºC; Setpoint Temp. (T
LSP1
): 25ºC
Zone 2
Reference Temp. (T
REF2
): 20ºC; Setpoint Temp. (T
LSP2
): 26,5ºC
Global Setpoint Temperature calculate (T
GSP
):
𝑇
𝐺𝑆𝑃
= 𝑇
𝑅𝐸𝑇
+ 𝑀𝑎𝑥 (0, 𝑅𝐼𝑛𝑡(𝑀𝑎𝑥((𝑇
𝐿𝑆𝑃1
− 𝑇
𝑅𝐸𝐹1
), (𝑇
𝐿𝑆𝑃2
− 𝑇
𝑅𝐸𝐹2
))))
𝑇
𝐺𝑆𝑃
= 19 + 𝑀𝑎𝑥 (0, 𝑅𝐼𝑛𝑡 (𝑀𝑎𝑥((25 − 21), (26,5 − 20))))
𝑇
𝐺𝑆𝑃
= 19 + 𝑀𝑎𝑥(0, 𝑅𝐼𝑛𝑡(6,5)) = 19 + 𝑀𝑎𝑥(0,7)
𝑻
𝑮𝑺𝑷
= 𝟐𝟔º𝑪
Example 2
– Cool mode:
Return Temp. to the unit (T
RET
) = 26ºC
Zone 1
Reference Temp. (T
REF1
): 28ºC; Setpoint Temp. (T
LSP1
): 25ºC
Zone 2
Reference Temp. (T
REF2
): 29ºC; Setpoint Temp. (T
LSP2
): 23ºC
Global Setpoint Temperature calculate (T
GSP
):
𝑇
𝐺𝑆𝑃
= 𝑇
𝑅𝐸𝑇
− 𝑀𝑎𝑥 (0, 𝑅𝐼𝑛𝑡(𝑀𝑎𝑥((𝑇
𝑅𝐸𝐹1
− 𝑇
𝐿𝑆𝑃
1
), (𝑇
𝑅𝐸𝐹2
− 𝑇
𝐿𝑆𝑃2
))))
𝑇
𝐺𝑆𝑃
= 26 − 𝑀𝑎𝑥 (0, 𝑅𝐼𝑛𝑡 (𝑀𝑎𝑥((28 − 25), (29 − 23))))
𝑇
𝐺𝑆𝑃
= 26 − 𝑀𝑎𝑥(0, 𝑅𝐼𝑛𝑡(6)) = 26 − 𝑀𝑎𝑥(0,6)
𝑻
𝑮𝑺𝑷
= 𝟐𝟎º𝑪
Note
: Global temperature setpoint will be not calculated if Dry Air mode or Fan
mode are activated.