Tecla 55
17
4 Bit
I
C - W T -
DPT_Control_Dimming
0x0 (Stop)
0x1 (Dec. by 100%)
...
0x7 (Dec. by 1%)
0x8 (Stop)
0xD (Inc. by 100%)
...
0xF (Inc. by 1%)
[Btn][Px] Light - Dimming
(Long Press) Lower = Brighter;
Upper = Darker
87, 93, 99
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] Two Objects - Long
Press
Left = 0; Right = 1
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] Two Objects - Long
Press
Left = 1; Right = 0
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Long Press) Left = Down; Right =
Up
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Start Pressing) Left = Down;
Right = Up
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Long Press) Left = Up; Right =
Down
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Start Pressing) Left = Up; Right
= Down
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Long Press) Lower = Down;
Upper = Up
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Long Press) Lower = Up; Upper =
Down
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Start Pressing) Lower = Down;
Upper = Up
1 Bit
C - - T -
DPT_UpDown
0/1
[Btn][Px] Shutter - Move
(Start Pressing) Lower = Up;
Upper = Down
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] Two Objects - Long
Press
Lower = 0; Upper = 1
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] Two Objects - Long
Press
Lower = 1; Upper = 0
88, 94, 100
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] LED On/Off
0 = On; 1 = Off
1 Bit
I
C - W T -
DPT_Switch
0/1
[Btn][Px] LED On/Off
0 = Off; 1 = On
89, 95, 101
1 Byte
I
C - W T -
DPT_Scaling
0% - 100%
[Btn][Px] Light - Dimming
(Status)
0 - 100 %
115
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
116
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 1
External Sensor Temperature
117
2 Bytes
I
C - W T U
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 2
External Sensor Temperature
118
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Effective Temperature
Effective Control Temperature
119
1 Byte
I
C - W - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode
1-Byte HVAC Mode