background image

ZENN

iO

 AVANCE Y TECNOLOGÍA 

 

vwww.zennio.com 

 

31 

31 

 

Example 3: disabled channel  

While measuring the electric consumption of a certain device that remains  always turned on 

and  that  consumes  200 W  constantly,  we  leave enabled  the  corresponding  channel  of KES 

between 0:00h am and 11:00h am on Monday. Exactly when 

it’s 11:00h am, we deactivate the 

channel through the object “[Cx] Disable”. When it turns midnight, KES will consider that the 

total  consumption during the day  has been  2.2  kWh  (that  is, 200  watts  constantly during  11 

hours, since there was no measuring between 11:00h am and midnight) and that the average 

daily consumption has been 200 watts per hour (2.2 kWh / 11 hours).  

Exactly  after  midnight,  the  channel  is  enabled  again  and  remains  this  way  indefinitely, 

measuring  a  200 Wh  consumption  every  hour.  When  the  week  is  over  (after  midnight  from 

Sunday  to  Monday)  the  earlier  Monday  will  be  considered  as  a  regular  day  in  order  to 

calculate the average weekly consumption per day. In other words:  

-

 

Weekly consumption

 = 2.2 kWh + (6 days x (0.2 kW x 24 hour)) = 31 kWh. 

 

-

 

Average weekly consumption

 = 31 kWh / 7 days = 4.43 kWh per day. 

Let  the  device  whose  consumption  we  are  measuring  be  now  turned  on  only  on  Tuesday, 

Thursday and Saturday and let the channel be always enabled. In that case, there will be a 

consumption of  0  kWh on  Monday, Wednesday,  Friday  and  Sunday.  The total  consumption 

for  Tuesday,  Thursday  and  Saturday  will  be  (3  days  x  (0.2  kW  x  24  hours))  =  14.4  kWh. 

However, once the week is over, the average weekly consumption will be 14.4 kWh / 7 days = 

2.06 kWh. The division is by 7 because the cannel stayed enabled during seven day forward 

changes, even the days in which there was a consumption of exactly zero. 

 

Example 4: disabled channel 

Suppose  the  energy  consumption  of  an  office  is  going  to  be  measured.  Most  of  everyday 

consumption takes place during the 8 working hours, and although there is not a  consumption 

of exactly 0 kWh during the rest of the day, it is not going to be measured. To achieve this, a 

case similar to #2 in Example 2 must be considered. Enabling the channel only during 8 hours 

a day will cause that any consumption made during the other 16 hours is discarded, and that 

the  average  daily  consumption  is  obtained  dividing  by  8  (not  24).  Regarding  weekly  and 

monthly values, only those days in which not only there was a null total consumption but also 

the channel was detected disabled at the end of the day (midnight) will not be considered. 

 

Содержание KES Series

Страница 1: ...KES KNX Energy Saver ZN1IO KES Programme version 1 0 Manual edition a PRODUCT MANUAL...

Страница 2: ...on 6 2 1 Active Power 6 2 2 Active Energy 7 2 3 Power Limits 7 3 ETS Parameterization 9 3 1 Default configuration 9 3 2 General window 10 3 3 Channels 14 3 3 1 Active Energy 15 3 3 2 Active Power 18 3...

Страница 3: ...n with the possibility of setting up 1 to 4 different tariffs as well as the volume of the CO2 emissions required to generate such energy Monitoring power limits Hourly daily weekly and monthly report...

Страница 4: ...ssociated LED 2 light in red If this button is held while plugging the device into the KNX bus KES goes into secure mode The LED blinks red Input connection 4 the terminal block with screws must be pl...

Страница 5: ...either in the inverse order 1 2 1 MEASURING PROBE The set up process of the ZN1AC CST60 measuring probe Figure 1 4 is described next Figure 1 4 Zennio ZN1AC CST60 measuring probe These are the require...

Страница 6: ...onsumed by the device whose phase line passes through the ZN1AC CST60 probe connected to one of the KES channels This active power is obtained from the effective intensity measured by the probe accord...

Страница 7: ...onsumption are set to be expressed in terms of cost KES allows specifying up to four different tariff values in cents of the local currency per kWh 2 3 POWER LIMITS KES can also monitor the level of t...

Страница 8: ...e 2 1 Power limit monitoring These concepts are explained in detail in Section 3 3 Power limit monitoring P t Deadband Lower limit Deadband Overconsumpt Alarm ON Overconsumpt Alarm OFF Low consumpt In...

Страница 9: ...defined yet the device and its objects will show as in Figure 3 1 Figure 3 1 KES 3xSingle Phase Default topology Objects Time and Date can be seen in the list They are intended to set the time and da...

Страница 10: ...al Request the value 1 through this object will make KES send the value of every communication object related to consumption instant values accumulate values average values peak values etc that has be...

Страница 11: ...c supplier Tariff x Initial value initial value for tariff x up to four different tariffs that will be considered when calculating the cost estimated actual or average of energy consumptions This cost...

Страница 12: ...urs the re sending of the last daily values will not work unless at least one channel A B C is active and unless at least one daily value has been enabled under the Active Energy screen Security sendi...

Страница 13: ...t day week and month Note Regardless of the selected period 0 1 2 3 4 6 or 12 hours the sending of the peak power values will not work unless at least one channel A B C is active and unless at least o...

Страница 14: ...it will report the accumulate values since the last reset for the energy consumption its cost and the carbon dioxide emissions related to channel x These values are reported through the communication...

Страница 15: ...creen captures shown here may refer to the configuration of Channel B In that case similar parameterization and behaviours can be assumed for channels A and C 3 3 1 ACTIVE ENERGY This screen allows th...

Страница 16: ...the latter will prevail resulting in sendings taking place only every y seconds If 0 is parameterized for Cycle time no periodic sending of the associated communication object will take place Send on...

Страница 17: ...ly CO2 Emissions Objects referring to Average Daily values energy consumption cost or CO2 emissions represent the total consumption in kWh local currency or kgCO2 of the day divided by the number of h...

Страница 18: ...Energy Consumption Cx Monthly Cost Cx Monthly CO2 Emissions Cx Average Monthly Energy Consumption Cx Average Monthly Cost and Cx Average Monthly CO2 Emissions Objects referring to Average Monthly val...

Страница 19: ...a certain value so that whenever a change in the instantaneous power greater than that value is detected a new sending of the corresponding communication object Instant Power will happen If there is...

Страница 20: ...screen it is possible to configure several parameters related to the monitoring of power consumption in relation to upper and lower limits section 2 3 Two different sections can be found one for conf...

Страница 21: ...user aware of the end of the over consumption situation Send on value change this parameter can be used to avoid consecutive over consumption alarms every time the instant power after having exceeded...

Страница 22: ...is set to 1 once the instant power is back again over the lower limit or over the lower limit plus the deadband or margin configured through the parameter explained below making the user aware of the...

Страница 23: ...to 5 different logical functions can be enabled independent of each other which can carry out up to 4 operations each To use any of them it is necessary to enable them in the following ETS window whic...

Страница 24: ...ng both objects up to three more times with a five second delay from one to another If no response is obtained after these four attempts KES will assume that the current time and date are those that t...

Страница 25: ...This way the next security re sending will happen at the end of next Thursday that is four day changes after the values were calculated Considering that the number of days in a week 7 is not a multip...

Страница 26: ...from 9h to 10h the second one from 10h to 1h and the third one from 1h to 5h Note that if no more fictitious time changes are forced after setting the clock to 5 06h the device will execute the second...

Страница 27: ...ion Example 1 total consumption The simplest usage of KES Energy Saver consists in destining it to calculate total consumptions so that they can be contrasted with those from the electric bill For tha...

Страница 28: ...way after every month KES will automatically report in what grade the bulb contributed to the consumption and the cost of the electric bill Alternatively if desired periodic security sendings can be e...

Страница 29: ...04 kWh Cx Average Weekly Energy Consumption 504 7 72 kWh per day CASE 2 Similar case but one of the days the channel is left disabled during 12 hours no matter which ones In such case that day Cx Dail...

Страница 30: ...Energy Consumption 432 7 62 kWh per day CASE 5 A particular case is that of having during one day a total consumption of zero note that such situation is quite improbable and the cannel disabled for...

Страница 31: ...vice whose consumption we are measuring be now turned on only on Tuesday Thursday and Saturday and let the channel be always enabled In that case there will be a consumption of 0 kWh on Monday Wednesd...

Страница 32: ...of applying only the new tariff 5 At 2 33h a 1 is sent through object Switch to tariff 3 6 When it s 3 00h Last hour cost is 2 kW 1h 0 m u 0 m u As seen setting the initial value of a tariff as zero d...

Страница 33: ...s of a watt Lower limit Initial value 100 tens of a watt When under limit send 1 Send object when over limit Yes Send on value change 20 tens of a watt In such case the following can be tested 1 As so...

Страница 34: ...few minutes how KES would work while time passes several hours several days and several weeks At the end of the example a small graph has been included to show the hour day and week changes that are b...

Страница 35: ...ect back the 2000 W load and set the internal clock to 10 00h am After the time change the object Last hour energy consumption will be sent containing a value of 1 kWh According to the device the last...

Страница 36: ...ay by the number of hours of that day two Average daily CO2 emissions 0 75 This value is the result of 50 kg 0 01 3 kWh 2 hours Average daily cost 75 monetary units This object indicates the cost per...

Страница 37: ...ounding to the nearest integer value the result of dividing the 5 kWh consumed during the previous week by the number of days of the week Average weekly CO2 emissions 1 25 This value comes from operat...

Страница 38: ...other words 50 kg 0 01 9 kWh Monthly Peak Power 3 kWh This value is a consequence of the few seconds the 3000 W load was connected Average monthly energy consumption 2 kWh per day 2 is the nearest int...

Страница 39: ...ulation scheme Month 1 WEEK 1 2 kW 0 kW 2 kW Monday Monday consumption 1 kWh 2 kWh 3 kWh 5 5 5 2 kW Tuesday Tuesday consumption 2 kWh WEEK 2 2 kW Monday Monday consumption 2 kWh WEEK 3 2 kW Monday Mon...

Страница 40: ...0 65535 Depends on initial paramet Previous Tariff x x 1 4 Tariff value 17 20 1 bit I W 0 1 0 0 Switch to tariff x x 1 4 0 No action 1 Switch Tariff CHANNELS GENERAL OBJECTS 4 6 1 bit I W 0 1 0 0 Cx...

Страница 41: ...aily cost Average daily cost 48 50 2 bytes O RT 0 670760 0 Previous Cx Average daily CO2 emissions Average daily CO2 emissions 51 53 4 bytes O RT 0 2 32 0 Previous Cx Weekly energy consumption Weekly...

Страница 42: ...0 Previous Cx Total CO2 emissions Total CO2 emissions CHANNELS ACTIVE POWER OBJECTS 96 98 2 bytes O RT 0 670760 0 Previous Cx Instantaneous Power Instantaneous power 99 101 2 bytes O RT 0 670760 0 Pr...

Страница 43: ...Entry 2bytes 1 FL Data Entry 2bytes 8 2 bytes Data entry 0 FFFF 2 bytes Data entry 0 FFFF 155 159 1 bit O RT 0 1 0 Previous FL Result of Function 1 1bit FL Result of Function 5 1bit Result of FUNCTIO...

Страница 44: ...44 ZENNIO TECHNICAL DOCUMENTATION BECOME USER http zennio zendesk com TECHNICAL SUPPORT...

Отзывы: