DALIBOX Interface 64/32
Technical Support:
14
If ECG Automatic Detection is not enabled, DALIBOX Interface 64/32 will only
be able to monitor ballast whose individual address have been detected before
for the device.
Collisions Detections
: this functionality analyses the responses of the ballasts
to detect those that have been assigned the same individual address.
Note
:
In case the collision detection is disabled and there are several ballasts
in the installation with the same assigned address, all of them will respond in
the same way to the control commands.
Important
:
when Collisions Detection is not enabled, some features as error
detection, ballast configuration, or emergency tests could not work properly.
Note
:
to ensure proper operation, enabling ECG Automatic Detection as long as
Collisions Detection is activated is recommended.
Standard Bit Timing
:
this function allows customising the time threshold after
which the arrival of a new bit through the DALI bus will be considered as
corrupt, for instance to prevent telegram collisions in case several ballasts have
been assigned the same address. Preserving the standard threshold is highly
encouraged, unless intending to connect very specific ballasts that may require
modifying it.
Manual Control Lock
: provides an optional procedure for locking the manual
control in runtime.
ETS PARAMETERISATION
After importing the corresponding ETS database and adding the device to the project
topology, the configuration process begins by entering the Parameters tab of the device.
The tab tree on the left shows the “General” tab in the first place. This entry itself
comprises the following parameters: