background image

© Zennio Avance y Tecnología S.L. 

Edition 1 

Further information 

www.zennio.com

 

Page 1/4 

 

ALLinBOX 1612 v2 

Multifunction device with KNX power supply, KNX-IP Interface, 16 outputs, 12 inputs and logical module 

ZPR1612V2 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

640mA KNX power supply with 29VDC auxiliary output 

 

110-240VAC 50/60Hz power input 

 

Power generation for the KNX system (with LED indicator) 

 

Short-circuit and overvoltage protection 

 

Reset button and overload status LED 

 

KNXnet/IP tunneling protocol (up to 5 connections) 

 

Maximum APDU length of 254bytes 

 

Ethernet 10/100 BaseT IP with RJ45 socket 

 

4 different configurable blocks: shutter channels (up to 8), individual 
outputs (up to 16) and 2/4-pipe fan coil controls (up to 2) 

 

Outputs suitable for capacitive loads, maximum 140µF 

 

Manual output operation through remote control 

 

12 analog/digital inputs 

 

Climate control for up to 4 rooms 

 

Output timing 

 

20 logic functions 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU 

 

Dimensions 69 x 96 x 210mm (12 DIN units) 

 

DIN rail mounting (EN 50022), with fixing clamp 

 

Possibility of connecting different phases in adjacent channels 

 

Conformity with the CE directives (CE-mark on the right side)  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.  Main power supply 

2.  Overload status LED 

3. Power supply status 

LED 

4. Reset button 

5. Reset status LED 

6. IP factory reset button 

7. IP factory reset LED 

8. Ethernet LED 

9.  KNX bus LED 

10. Analog/digital inputs 

11. Auxiliary power output 

12. KNX connector 

13. Programming/Test 

button 

14. Programming/Test 

LED 

15. Fixing clamp 

16. Outputs 

17. IR input 

18. Ethernet connector 

19. Remote control (not included, ref. 9900024) 

PROGRAMMING/TEST BUTTON: short press to set programming mode. If this button is held while providing main power supply to the device, it enters 
the safe mode. If this button is held for more than 3 seconds, the device enters the test mode. 

PROGRAMMING/TEST LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual 
mode is indicated by the green color. During the start-up (reset or after providing main power supply) and if the device is not in safe mode, it starts a 
blue blinking sequence. 

POWER SUPPLY STATUS LED: it indicates the status of the power supply (green color: the device is working properly; off LED: power supply failure; 
green blinking: short-circuit on KNX bus and/or auxiliary power output). 

OVERLOAD STATUS LED: it indicates an overload on the KNX line or on the auxiliary power output (red blinking: cut-off due to overload/short circuit 
on the KNX bus and/or the auxiliary power output*; red color: overload on bus and/or auxiliary power output line *). 

*Reduce the load on the bus and/or the auxiliary power output lines until its total consumption does not exceed the maximum current specified. 

KNX BUS LED: it indicates that the device is powering up the KNX bus (green color). 

ETHERNET LED: it indicates that the device is connected to Ethernet and has an IP address assigned (green color). 

RESET INDICATOR LED: it indicates that a reset of the KNX system has been performed by using the corresponding reset button (red blinking). To 
reset the bus power supply, the Reset button should be pressed (it is recommended to hold it for at least 5 seconds to verify the reset of all the devices 
in the line). The reset LED will blink slightly in red while the Reset button is pressed. 

IP FACTORY RESET INDICATOR LED: it indicates that the device has just performed an IP factory reset (red color). To reset the KNX IP Interface, 
the IP Factory reset button must be pressed for at least 3 seconds. 

MANUAL CONTROL: In order to perform manual control of the device, an IR remote control is necessary (Ref. 9900024) not included with the ALLinBOX 
1612 v2. When the device is in Test On mode, the manual control can be done by pressing the corresponding buttons on the IR remote control (please, 
be sure that the remote IR emitter is pointing to the IR input of ALLinBOX 1612 v2). 

 

 

1

 

6

 

7

 

10 

16 

11 

12 

13  14 

15  16  17 18  19 

Figure 1: ALLinBOX 1612 v2 

  