Page 8 of 12  

87100NZ v1.12 09.22 WR FlushMaster

5. Set timing using switches

(alternatively, set the timing using fill time button as detailed in step 6)

Test Mode

When all switches are OFF, the sensor defaults to Test mode. 
The default test mode is set at approximately 35 seconds delay, 5 
seconds flush.
Test mode timings may be adjusted using the Fill Time button 
(see next section), otherwise you may reset the timing using the 
switches.

Delay time (valve closed)

The delay time is set with any combination of the four switches 
turned ON.
The minimum flush delay is 45 seconds (all switches OFF); maximum 
flush delay is 15 minutes (all switches ‘on’, 1+2+4+8 minutes).
Setting a short flush delay will reduce the life of the battery. 

Valve open time

The ‘valve open’ or ‘flush and fill’ time period can be set with six 
switches ranging from 15 seconds to 8 minutes. The total time 
ranges from 5 seconds (all switches OFF), to 15.75 minutes (all 
switches ON).

If the installation contains a cistern:

 set the ON period to permit 

the cistern to fill, activate the syphon and flush. The fill cycle should 
over-run the flush by a few seconds if possible to allow for pressure 
fluctuation.

If the installation has no cistern:

 a direct injection type air break 

must be used. Set the ‘valve open’ time to allow an adequate flush 
of the urinal whilst observing the flushing volume requirements of 
AS3500.1.

4. Connect power pack (optional) 

Locate battery holder and battery supplied with the system. 
If connected, remove the battery cable plug from the circuit board. 
Connect power pack to 220-240 volt 10 amp AC power point.
Carefully align the power pack outlet cable plug to circuit board 
inlet socket.
Firmly insert the cable plug from the power pack into the inlet 
socket.

Connect to 

circuit board

Fixing 

bracket 

(supplied)

Connect to 

power point

Delay time

Switch

Time

1

1 minute

2

2 minute

3

4 minute

4

8 minute

Valve open duration

Switch

Time

1

15 seconds

2

30 seconds

3

1 minute

4

2 minute

5

4 minute

6

8 minute

Installation

Surface Mounted Sensor

Drill a 12 mm hole in the side of the box, fit cable gland and thread 
cable through the cable gland into the sensor as shown.

Содержание FlushMaster 40090NZ

Страница 1: ...87100NZ v1 12 09 22 WR FlushMaster Page 1 of 12 Installation instructions user manual Zenith FlushMaster Surface mounted sensor Water saver urinal flushing system Product code 40090NZ...

Страница 2: ...ll timing using Fill Time Button 9 7 Complete installation 9 Maintenance 10 Cleaning 10 Battery Replacement 10 Valve Diaphragm Replacement 10 Troubleshooting 11 Read all instructions before attempting...

Страница 3: ...ass fittings with Restrictaflow Spares and accessories 99021NZ Zenith FlushMaster Cistern Autosyphon 1 00 inch BSP 25 mm 99022NZ Zenith FlushMaster Cistern Autosyphon 1 25 inch BSP 32 mm 99023NZ Zenit...

Страница 4: ...Capacity Single stall Twin stall Single trough Maximum trough length 600 mm Twin trough Maximum trough length 1200 mm Single trough 1 5 to 2 5 litre discharge capacity Single trough 3 0 to 5 0 litre...

Страница 5: ...o each cistern as equal in length as possible If this is not practical fit a flow restrictor of equal rating at the entry to each cistern Remove the existing filling mechanism from the cistern includi...

Страница 6: ...y of the cable connecting the sensor to the latching valve is visible shield it with conduit Warning Do not connect battery or power pack until all plumbing connections are completed The power must be...

Страница 7: ...t remove the valve output connector on the circuit board by lifting it directly upwards Hold the connector so that the fixing screws are facing you Secure the brown cable into the right hand screw ter...

Страница 8: ...stern set the ON period to permit the cistern to fill activate the syphon and flush The fill cycle should over run the flush by a few seconds if possible to allow for pressure fluctuation If the insta...

Страница 9: ...except while the valve is open To set the valve open flush fill time Press the Fill Time Button until the Fill LED lights up Press the Fill Time Button again to make the Fill LED pulse every second W...

Страница 10: ...nd remove existing battery Replace existing battery with lithium cell type CRP2 223A only Zenith product code 90098NZ Replace cover on battery holder and replace cover on sensor housing Valve Diaphrag...

Страница 11: ...ushes for only 35 seconds at a time Sensor timers set to test mode and latching valve cable wires crossed Reset sensor timer switches and uncross latching valve wire connection Cistern fills or direct...

Страница 12: ...ith and FlushMaster are registered trade marks Zenith products described in this publication are manufactured under one or more patents and further patent applications are pending As Zenith policy is...

Отзывы: