background image

5

Air Under Pressure Will Cause
Injury, Death Or Property Damage.

 

Do Not Exceed Pressure Rating.

 

Relieve Press. Before Servicing.

 

Do Not Modify/Repair/Rework
ASME Coded Pressure Vessels
As Insurance Rating Affected.

! READ INSTRUCTION MANUAL !

HIGH VOLTAGE Can Cause Severe
Injury Or Death.

 

Some circuits may be energized
when switch is off.

 

Disconnect and lockout ALL
power sources before servicing.

! READ INSTRUCTION MANUAL !

Air Under Pressure Will Cause
Injury, Death Or Property Damage

Relieve Press. Before Servicing.

Condensate Drain Discharges
Under Pressure.

Drain Requires Periodic
Cleaning (Service).

! READ INSTRUCTION

MANUAL !

L'air sous pression causera
des blessures graves, des
dégats matériels et peut
même entrainer la mort

Ne pas excéder le taux de
pression

Relâcher la pression avant
la mise en service de
l'appareil

Ne pas modifier/réparer ou
retravailler

Le taux de pression des
vaisseaux est conforme
aux recommendations de l'
ASME ( American Society
of Mechanical Engineers)
et peut être vérifié lors d'un
controle.

LIRE LE MANUEL
D'INSTRUCTIONS!

La haute tension peut
entrainer des blessures
graves ou même la mort

· Certains circuits peuvent
être chargés lorsque l'inter-
rupteur est en position
"fermé" (off)

· Déconnecter et vérouiller
TOUTES les sources d'élec-
tricité avant la mise en
service de l'appareil

LIRE LE MANUEL
D'INSTRUCTIONS!

L'air sous pression
causera des
blessures graves,
des dégats matériels
ou même la mort

Relâcher la pression
avant la mise en
service de l'appareil

Condenser les
tuyaux de décharges
sous pression

Les tuyaux doivent
être nettoyés
régulièrement
(service)

LIRE LE MANUEL
D'INSTRUCTIONS

Содержание CFX NC Series

Страница 1: ...16 8 SCHEDULED MAINTENANCE 19 9 TECHNICAIN MODE 22 10 TROUBLESHOOTING 25 11 WIRING DIAGRAMS 27 12 GENERAL ARRANGEMENT 31 13 PARTS IDENTIFICATION 32 14 ENGINEERING SPECIFICATIONS 35 ZEKS Compressed Ai...

Страница 2: ...e Warranty Registration Card may be completed online at www zeks com The total warranty period cannot exceed 18 months from the original date of shipment from the factory Equipment must be installed a...

Страница 3: ...of all other warranties There are no other warranties expressed or implied except as stated herein There are no implied warranties of merchantability or fitness for a particular purpose which are spe...

Страница 4: ...uld any person attempt to lift heavy objects without proper lifting equipment i e crane hoist slings or fork truck Lifting any unit without proper lifting equipment may cause serious injury To facilit...

Страница 5: ...erate the dryer at pressures in excess of its rating 8 Do not operate the dryer without guards shields and screen in place 9 Inspect unit daily to observe and correct any unsafe operating conditions T...

Страница 6: ...trainer la mort Ne pas exc der le taux de pression Rel cher la pression avant la mise en service de l appareil Ne pas modifier r parer ou retravailler Le taux de pression des vaisseaux est conforme au...

Страница 7: ...cation See Attached Terminal Connection Diagram Be Certain To Follow All NEC State Local and Other Applicable Codes During Installation Label Group 2 Page 1 of 2 File ZEKSLABELGROUP2 1 LA BO TE DE CON...

Страница 8: ...hot saturated air from the compressor enters the precooler reheater where the air temperature is reduced prior to entering the chiller by the cool air exiting the air moisture separator This precoolin...

Страница 9: ...uency is required A longer valve off time may be used during the winter months when moisture levels are lower 6 4 REFRIGERATION SYSTEM The Refrigeration System consists of all the components which han...

Страница 10: ...ted for 2A 120V max The DPC Controller features three levels of access The default level CUSTOMER MODE permits adjustment of dryer parameters to address seasonal variations for drain timing A protecte...

Страница 11: ...ose at 270 psig The DPC controller includes a digital readout for monitoring the discharge pressure of the refrigerant gas exiting the compressor This reading will vary depending upon condenser type a...

Страница 12: ...isplayed as the default display Allows user to increase set point values Set point values cycle through a fixed range Also allows entering negative numbers in FACTORY MODE TEST Allows user to manually...

Страница 13: ...tion pressure in psig of the refrig eration system DPC Plus Only Inlet Air Pressure and Temperature P AIR IN T AIR IN Displays the tempera ture in F and pressure in psig of the inlet compressed air DP...

Страница 14: ...DPC Controller has several user adjustable set points that are displayed at the end of the display parameter list These set points allow the user to configure the dryer to operate according to site co...

Страница 15: ...Note that this alarm will shut down the dryer after a response time delay This alarm will reset automatically once the alarm condition is rectified HIGH PRESSURE CUTOUT ALARM HI PRESS CO If the disch...

Страница 16: ...followed by the PRESS ON BUTTON display After the ASC delay has timed out the dryer will only start once the ON button is depressed In this configuration to restart the dryer the user must manually d...

Страница 17: ...ended Prefilters and afterfilters sized to your drying application can be provided by ZEKS and are available factory installed Call your local distributor to select the filter that best suits your fil...

Страница 18: ...and appropriate Wiring Diagrams A suitable fused disconnect switch or circuit breaker in accordance with national and local code requirements is recommended for all ZEKS equipment Refer to the Enginee...

Страница 19: ...Y using the SET button enables this mode of operation Note that the dryer s touch pad will still affect dryer operation Depressing the OFF button will de energize the refrigeration compressor and all...

Страница 20: ...equired Remote Automatic Mode Close the remote contact For NonCycle dryers after the initial delay has timed out the compressor is energized The suction pressure gauge will typically pull down between...

Страница 21: ...the valve is depressurized Carefully remove the Strainer End Cap and remove the Strainer Clean the Strainer and remove any debris that is evident in the valve Replace the Strainer and reinstall the S...

Страница 22: ...ilure to the seals will occur Be especially careful to clean the center brass orifice and the rubber gasket orifice on the orifice cup with a straight pin Reassemble all drain components after the dra...

Страница 23: ...hours AUTO RESTART ENABLE AUTO RESTART N or Y Parameter Display Set Point OPERATING MODE OP MODE HS or NC REFRIGERANT REFRIG 22 or 404 or 407 CONDENSER TYPE COND AC OR WC OPERATING TEMPERATURE DIFFER...

Страница 24: ...arameter for the Auto Restart feature AUTO RESTART N SELECT DISPLAY The DRAIN ENABLE parameter determines whether the DPC shall control an electronic solenoid drain valve A value of ON will permit the...

Страница 25: ...M LIST screen at the top of the ALARM LIST BEGIN ALARM LIST SELECT DISPLAY The Alarm List will repeat as long as the SELECT DISPLAY button is depressed To EXIT the ALARM LIST perform the following Dep...

Страница 26: ...DRAIN TEST contact distributor Check inlet and outlet pressures and system design capacity Correct cause of excessive flow Close by pass valve Check power supply and fuses circuit breakers Check and...

Страница 27: ...nd outlet filters blocked up Compressor relay contactor stuck DPC relay bad Probe not completely in thermal well Problem persists CORRECTIVE ACTION Check Chiller Temperature Check MAIN CONTROL fuse Co...

Страница 28: ...27 11 WIRING DIAGRAMS...

Страница 29: ...28...

Страница 30: ...29...

Страница 31: ...30...

Страница 32: ...31 12 GENERAL ARRANGEMENT...

Страница 33: ...NCE 700 NCE 800 NCE 1 Exchanger Assy 748065 748069 748056 748056 2 Solenoid Drain Valve 682657 682657 682657 682657 3 Drain Valve Repair Kit 683006 683006 683006 683006 4 Filter Stop 682438 682438 682...

Страница 34: ...33...

Страница 35: ...34...

Страница 36: ...35...

Отзывы: