To enter the TECHNICIAN MODE, perform the following keystrokes:
Pressing the “2” and “3” buttons simultaneously enters
the TECHNICIAN MODE.
TECH SET MODE
SELECT
DISPLAY
Depressing SELECT DISPLAY scrolls through the
available parameters. The first three parameters viewed
are adjustable in TECHNICIAN MODE.
DRAIN ENABLE: ON
2
3
Depressing ENTER saves the selected set point.
Depressing the SELECT DISPLAY button advances to
the next adjustable parameter for the Crankcase Heater
Delay. This parameter must not be altered unless
instructed by ZEKS Service personnel.
DRAIN ENABLE: OFF
CCH DELAY: 4
SET
For parameters with “ON / “OFF” or “Y” / “N” choices, the
set point is changed using the SET button. Pressing the
SET button changes the Drain Enable from ON to OFF.
DRAIN ENABLE: OFF
ENTER
SELECT
DISPLAY
Depressing ENTER saves the selected set point.
AUTO RESTART: Y
SET
Depressing the SET button changes the AUTO RESTART
parameter from “N” to “Y”.
AUTO RESTART: Y
ENTER
Depressing the SELECT DISPLAY button advances to
the next adjustable parameter for the Auto Restart
feature.
AUTO RESTART: N
SELECT
DISPLAY
The DRAIN ENABLE parameter determines whether the DPC™ shall control an electronic
solenoid drain valve. A value of “ON” will permit the DPC™ to control the drain valve. A
value of “OFF” will disable this feature. This would be suitable for servicing the drain
valve or if an independent no air loss drain is to be used with the dryer. To change the
DRAIN ENABLE set point from the displayed set point, perform the following. Otherwise,
depress the SELECT DISPLAY button to advance to the next adjustable parameter:
The AUTO RESTART feature permits the dryer to operate once power is applied to the
dryer without requiring operator intervention. This would be desirable should the user
wish to have the dryer restart automatically after a power outage. To change the AUTO
RESTART set point from “N” (NO) to “Y” (YES), perform the following. Otherwise,
depress the SELECT DISPLAY button to advance to the next display:
The Crankcase Heater Delay set point must not be altered unless directed by ZEKS
Service Personnel. Improperly altering the set point may result in damage to the dryer.
Contact ZEKS Compressed Air Solutions before altering the default set point.
NOTICE