Installation

6

A 100mm nominal diameter spigot is provided for connection to ducting. Ductwork should be securely 
connected to the back of the fan. Failure to do this will cause unnecessary air leakage and may impair 
performance.

Reattach the front cover by
rotating clockwise, utilising
the guidance rail, until firmly
secured by the retaining clips

STEP 5

Retaining screw

Unlock position

Lock position

Turn power off and locate main body cover via the arrow & unlock
position, rotate clockwise to ‘lock position’  

Tighten retaining screw until main body cover cannot be opened.
Turn power on and follow respective commissioning on pages 7 & 8

STEP 4

Содержание Unity ZCV3si

Страница 1: ...ng extract fan designed to offer a simplistic approach to meet Building Regulations and provide an energy efficient domestic ventilation solution to improve indoor air quality in dwellings Please read instructions before commencing the installation Please make these instructions available for the user ...

Страница 2: ...ed where it would be subject to a direct heat source in excess of 40 C e g at least 600mm distance from cooker hob Observe appropriate safety precautions if working on steps or ladders Wear eye protection when breaking out wall or ceiling materials etc To disassemble the unit disconnect from mains supply and use a screwdriver to segregate the electronic components and motor from the plastic housin...

Страница 3: ...te anticlockwise to remove Main body Outer cover Cut the duct to depth of the plasterboard or tiled wall with slight fall to exterior Make provisions for cable Fill in any gaps with mortar or foam and make good internal and external walls Make sure that ducting retains its original shape Ø between 102mm 117mm to suit ducting dimensions Allow a clearance of 50mm from wall ceiling edges around the f...

Страница 4: ...he fan anticlockwise to unlock position and remove cover Connect ducting to the spigot on the back of the Unity ZCV3si Note If using flexible ducting ensure this is pulled taut to a min 90 stretch capacity between fan and termination Retaining screw STEP 1 STEP 2 Lock position Unlock position ...

Страница 5: ... terminal block as per wiring diagram tighten screws of the terminal block Note A facility to park the earth cable has been provided as the fan is double insulated no connection to earth is required Electrical Installation Preparation Installation or disconnection must be carried out by a qualified Electrician and all wiring must conform to local regulations Isolate electricity supply before start...

Страница 6: ...formance Reattach the front cover by rotating clockwise utilising the guidance rail until firmly secured by the retaining clips STEP 5 Retaining screw Unlock position Lock position Turn power off and locate main body cover via the arrow unlock position rotate clockwise to lock position Tighten retaining screw until main body cover cannot be opened Turn power on and follow respective commissioning ...

Страница 7: ...ee Step 5 on page 6 Default setting Off To activate press required button the light adjacent to your selection will go solid The Smart Humidity sensor automatically registers the speed at which the humidity in the room changes If there is a rapid change it reacts to a rise in room humidity caused by the user and switches on the ventilator The Smart Timer monitors the length of time that there is a...

Страница 8: ... will start to flash Note Do not press any buttons Open the Unity CV3 APP remove outer cover of your fan and when prompted match your Android device s NFC with the NFC symbol on the main body of the fan please refer to your Android device instructions for the NFC location Click on the Product Setup section and follow the APP on screen instructions Airflow 18 m3 h 29 m3 h 36 m3 h 47 m3 h 58 m3 h Se...

Страница 9: ...rrow unlock position rotate clockwise to lock position Tighten retaining screw until main body cover cannot be opened Turn the power to the fan ON recommission either via your fan or the APP refer to respective commissioning section for via the fan see page 7 or for via the APP see page 8 The Unity ZCV3si will start to go through its initialisation sequences for the flow rate commissioning See pag...

Страница 10: ...e build up of dirt The fan motor has sealed for life bearings which do not require lubrication Periodic cleaning of the fans front cover and casing can be carried out using a soft damp cloth Do not use solvents to clean this fan Cleaning and user maintenance shall not be made by children without supervision Please note that your stored fan settings will not be lost during any interruptions to your...

Страница 11: ...fan is running all the time My fan is running faster and noisier My fan still runs faster and noisier when I turn the light off Why can t I turn the fan off Answer The fan is very quiet when the room s light is off but it is still extracting and working to provide you with enhanced comfort If in doubt remove the front cover to expose the fan If the fan impellor is not rotating then contact your lo...

Страница 12: ...eved correct at time of going to press All dimensions referred to are in millimetres unless otherwise shown E OE All goods are sold according to Zehnder Group Sales International Standard Conditions of Sale which are available on request See website for warranty period details Zehnder Group Sales International reserves the right to change specifications and prices without prior notice Copyright Ze...

Отзывы: