40 - EN
3. Briefly press the operating button to select the correct function:
■
Controller function:
The CO
2
LED turns
green
; the bottom two LEDs on the right turn
red.
■
Sensor function:
The CO
2
LED turns
red
; the bottom two LEDs on the right turn red.
4. Press the operator button for 5 seconds to confirm the selection:
■
All LEDs on the right blink green 3 times.
6.3 Control setting of the CO
2
0-10V Sensor
Ventilation unit
Advisory setting of the CO
2
Sensor
Ventilation with heat recovery and ComfoZone Box
Sensor
Ventilation with heat recovery
Controller, unless a value other than 1050ppm*
is desired.
Mechanical ventilation
Controller
* The CO
2
Sensor uses a fixed target value of 1050ppm (parts per million: number of units of
CO
2
per million units in the measured air).
Function
setting
Operation of the
CO
2
Sensor
ComfoAir Q settings
ComfoAir E settings
Sensor
The signal from the
device is the measured
value. (In this case,
2V corresponds to
400ppm and 10V to
2000ppm)
The controller to
ensure that the level of
CO
2
does not become
too high is located in
the ventilation unit.
■
Signal at 0%: 10V
(2000ppm)
■
Signal at 100%: 2V
(400ppm)
■
010V input function:
control
■
Setpoint: depending on the
desired CO
2
level; e.g. 4V
(800ppm)
■
Proportional ratio: 50%
(800ppm)
■
Integration time: 300
seconds
■
Activation: On
■
Method: Setpoint control
■
Setpoint: Depending on the
desired CO
2
level; e.g. 4V
(800ppm)
■
Min. setting: 2.0V
■
Max. setting: 10.0V
■
P value: 50%
■
I value: 300 seconds
■
Invert signal: Yes
Controller
A signal from the
device provides the
ventilation needed to
reach 1050ppm.
The ventilation unit can
be controlled via the
010V input.
■
Signal at 0%: 0V
(minimum ventilation)
■
Signal at 100%: 10V
(maximum ventilation)
■
010V input function: send
■
Activation: On
■
Method: Proportional flow
rate
■
Min. Setting: 0.0V
■
Max. Setting: 10.0V
■
Invert signal: No
Содержание RF55
Страница 2: ...2 NL Contents NL 3 EN 24 DE 45 FR 66 IT 87 PL 108 ES 129...
Страница 56: ...56 DE Anschluss RF 0 10V Abbildung 4 4 R ckseite CO2 Sensor Typ RF Abbildung 4 5 R ckseite CO2 Sensor Typ 0 10V...
Страница 119: ...119 PL Pod czenie RF 0 10V Rysunek 4 4 Tylna cz czujnika CO2 typu RF Rysunek 4 5 Tylna cz czujnika CO2 typu 0 10V...
Страница 150: ...150 ES...
Страница 151: ...151 ES...