Electrical 
connections

The unit serial tag lists the unit 
electrical characteristics such 
as the required supply voltage, 
motor amperage and required 
circuit ampacities. The unit 
wiring diagram shows all unit and 
field wiring. The installer must be 
familiar with the wiring diagram 
before beginning any wiring 
as the wiring can change from 
project to project.

Electrical shock can cause 
personal injury or death. When 
installing or servicing system, 
always turn off main power to 
system. There may be more 
than one disconnect switch. 
Thermostat “OFF” should not be 
used for disconnect purposes. 

All field wiring connecting to 
this type of unit must by 105 °F 
rated copper conductor and 
should be in accordance with the 
National Electrical Code and any 
applicable local codes. Branch 
circuit fusing and electrical 
disconnect means, if required, 
must be furnished and installed 
by others. All unit-mounted 
control components are factory 
wired to the junction control 
box located in the electrical 
end pocket of units. Remote-
mounted control components 
are shipped loose for field 
installation and wiring and are 
to be wired in strict accordance 
with the wiring diagram. Failure 
to do so could result in personal 
injury or damage to components 
and will void the manufacturer 
warranty.

All wiring connections should 
be checked prior to start-up to 
ensure connections have not 

come loose during shipment or 
installation, minimizing problems 
during start-up.

The fan motor(s) should never 
be controlled by any wiring or 
device other than the factory 
supplied switch or thermostat/
switch combination without 
factory authorization. 

Consult the factory wiring and 
valve package diagrams when 
installing an aquastat. The 
switch should always be installed 
upstream of the control valve on 
a pipe that will have constant 
flow regardless of the control 
valve position, allowing a true 
water temperature reading at all 
times. A bleed bypass may be 
required to guarantee proper 
aquastat operation.

The applicable wiring diagram 
ships with each unit and must 
be strictly followed. Field 
power supply wiring should be 
through end pocket openings 
or knockouts in the supplied 
junction boxes.

All field wiring should be done 
in accordance with governing 
codes and ordinances. Any 
modification of the unit wiring 
without factory authorization will 
void the warranty and nullify any 
agency listings.

Zehnder Rittling assumes no 
responsibility for any damages 
and/or injuries from improper 
field installation and/or wiring.

Electrical connections

Содержание RC-360

Страница 1: ...i Cooling Fresh Air Clean Air Heating Rittling Cabinet Unit Heater Installation Operation and Maintenance ...

Страница 2: ...ng 11 Safety considerations 12 Unpacking and preparation 13 Handling and installation 14 Hot water connections 15 Ductwork connections 16 Electrical connections 17 Wiring diagram 18 Start up 20 Air system balancing 21 Heating system 21 Water system balancing 22 Water treatment 22 Controls operation 23 Exposed unit touch up 23 Normal operation maintenance 24 Replacement parts 26 Equipment start up ...

Страница 3: ... 300 RW Wall RW 260 shown RW 270 and RW 280 available RWI Wall inverted flow RWI 290 shown RWI 300 and RWI 310 available RRW Wall partially recessed RRW 320 shown RRWI Wall partially recessed inverted flow RRWI 330 shown RFRW Wall fully recessed RFRW 340 shown RFRWI Wall fully recessed inverted flow RFRWI 350 shown Models and arrangements 1 ...

Страница 4: ...FI 240 RS 200 RSI 240 RF 220 RFI 250 RF Floor RF 200 shown RF 220 available RC Ceiling RC 360 shown RC 370 RC 380 RC 390 and RC 400 available RFI Floor inverted flow RFI 240 shown RFI 250 available RS Floor sloped RS 200 shown RRC Ceiling partially recessed RRC 440 shown RFRC Ceiling fully recessed RS 200 shown RSI Floor sloped inverted flow RSI 240 shown 2 ...

Страница 5: ...2 Cu Blower Quantity 1 1 2 2 1 2 4 4 Diameter 5 7 5 7 5 7 5 7 5 7 5 7 5 7 Width 7 5 10 4 7 5 10 4 7 5 10 4 7 5 10 4 Filter Number 1 1 1 1 1 1 1 Length in 22 28 34 46 52 60 70 Width in 9 75 9 75 9 75 9 75 9 75 9 75 9 75 Thickness in 1 1 1 1 1 1 1 Cabinet size Height in 26 5 26 5 26 5 26 5 26 5 26 5 26 5 Length in 38 2 44 2 50 2 62 2 68 2 76 2 86 2 Width in 10 10 10 10 10 10 10 Shipping weight lbs 8...

Страница 6: ...40 Power input Watts 100 110 130 180 325 368 368 Voltage Volts 120 120 120 120 120 120 120 Hz 60 60 60 60 60 60 60 Phase 1 1 1 1 1 1 1 Table B Electrical ratings Notes Maximum circuit ampacity MCA 1 25 x FLA motor 1 FLA motor 2 FLA electric heat Maximum overcurrent protection MOP 2 25 x FLA motor 1 FLA motor 2 FLA electric heat If the calculated MOP is within 10 of the next smaller available fuse ...

Страница 7: ... 2 3 1 2 5 1 4 4 1 2 8 1 8 RF 200 shown Dimensional data Unit size A B C D 02 38 3 16 22 3 16 24 20 03 44 3 16 28 3 16 30 26 04 50 3 16 34 3 16 36 32 06 62 3 16 46 3 16 48 44 08 68 3 16 52 3 16 54 50 10 76 3 16 60 3 16 62 58 12 86 3 16 70 3 16 72 68 Notes 1 and 2 row coil supply and return 1 2 nominal 5 8 OD all sizes Inlet grille optional Unit shown with left hand piping connections and right han...

Страница 8: ...S 200 shown Dimensions and data Models RS and RSI Dimensional data Unit size A B C D 02 38 3 16 22 3 16 24 20 03 44 3 16 28 3 16 30 26 04 50 3 16 34 3 16 36 32 06 62 3 16 46 3 16 48 44 08 68 3 16 52 3 16 54 50 10 76 3 16 60 3 16 62 58 12 86 3 16 70 3 16 72 68 Notes 1 and 2 row coil supply and return 1 2 nominal 5 8 OD all sizes Inlet grille optional Unit shown with left hand piping connections and...

Страница 9: ...urn and 1 row steam supply 1 row hot water suppy and 1 row steam return 2 row hot water return 2 row hot water supply 2 row hot water return 7 3 8 8 1 8 2 row hot water supply 7 1 4 4 1 2 24 24 18 1 4 16 1 2 15 3 4 13 1 2 1 row hot water supply and 1 row steam return Filter position 10 3 8 2 5 1 4 7 1 4 2 5 1 4 4 1 2 5 5 8 Dimensions and data Notes 1 and 2 row coil supply and return 1 2 nominal 5 ...

Страница 10: ...nd 2 row coil supply and return 1 2 nominal 5 8 OD all sizes Unit shown with left hand piping connections and right hand electrical connections as standard Right hand piping connections with left hand electrical connections available as an option Piping hand determined when facing the air outlet All listed dimensions are approximate and are subject to change without notice Modifications to the pro...

Страница 11: ...03 44 3 16 28 3 8 30 18 5 8 04 50 3 16 34 3 8 36 23 5 8 06 62 3 16 46 3 8 48 23 5 8 08 68 3 16 52 3 8 54 33 5 8 10 76 3 16 60 3 8 62 33 5 8 12 86 3 16 70 3 8 72 33 5 8 Notes Damper motor always on right side when viewing unit from front side All listed dimensions are approximate and are subject to change without notice Modifications to the product specifications must be accepted by Zehnder Rittlin...

Страница 12: ...louvered inlet grille with internal bug screen 3 1 2 A Front View Weep holes 2 5 8 4 to 8 1 2 2 13 16 Side View Dimensions and data Outside air wall box Dimensional data Model A Rough opening WB 0203 24 22 1 2 x 3 WB 0406 29 27 1 2 x 3 WB 081012 39 37 1 2 x 3 10 ...

Страница 13: ...d damage not discovered during unloading must be reported to the shipping company within 15 days of receipt of the shipment All units are shipped F O B factory Therefore Zehnder Rittling is not responsible for damage during transit It is the responsibility of the installing contractor to inspect and verify that the units shipped were in fact the correct model number voltage etc Any discrepancies s...

Страница 14: ...ays pressure test with an inert fluid such as water or dry nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing Always protect adjacent flammable material when welding or soldering Use a suitable heat shield material to contain sparks or drops of solder Have a fire extinguisher readily available Please follow standard safe practices regarding the h...

Страница 15: ...ive environments or in locations subject to temperature or humidity extremes e g attics garages rooftops etc Corrosive conditions and high temperature or humidity can significantly reduce system performance reliability and overall service life a clean dry area of the building or in a warehouse Do not remove any equipment from its shipping package until it is needed for installation The equipment i...

Страница 16: ...kets where hanging rod and rubber in shear or spring vibration isolators supplied by others can be used for proper suspension and vibration isolation The type of mounting device is a matter of choice however the mounting point should always be that provided in the chassis or cabinet Improper mounting could result in the unit falling from its position causing personal injury or even death After mou...

Страница 17: ...using a leak Secure the union nut hand tight and then tighten no more than an additional 1 4 turn The inlet supply connection is marked at the appropriate coil stub out with the other coil stub out being the outlet return connection After the connections are completed the system should be tested for leaks Since some components are not designed to hold pressure with a gas hydronic systems should be...

Страница 18: ...ovided with outside air should have some form of low temperature protection to prevent coil s from freezing This protection may be a low temperature thermostat to close the outside air damper a preheat coil to temper the outside air before it reaches the unit or any other protective method It should be noted that none of these methods will adequately protect a coil in the event of power failure Th...

Страница 19: ...agram Failure to do so could result in personal injury or damage to components and will void the manufacturer warranty All wiring connections should be checked prior to start up to ensure connections have not come loose during shipment or installation minimizing problems during start up The fan motor s should never be controlled by any wiring or device other than the factory supplied switch or the...

Страница 20: ...ELLOW WHITE YELLOW RED RED BLACK BLACK B R YEL WALL THERMOSTAT OPTIONAL RETURN AIR FAN CONTROL OPTIONAL AQUASTAT FAN CONTROL OPTIONAL R B WHITE BLACK GREEN WALL PLUG OPTIONAL DISCONNECT SWITCH OPTIONAL FREEZESTAT OPTIONAL M2 L2 YELLOW SEE CHART SEE CHART SEE CHART PSC MOTOR OPTION NOTE FOR HIGH STATIC MOTORS USE THE FOLLOWING 3 SPEED SWITCH WIRING CONFIGURATION RED LOW BLUE MED BLACK HIGH YELLOW W...

Страница 21: ...L M BLOWER MOTOR MOTOR QUICK CONNECT OPTIONAL HEATER L1 T1 L2 T2 MANUAL MOTOR STARTER OPTIONAL TRANSFORMER L2 M2 FREEZESTAT OPTIONAL BLACK BLACK BLACK WHITE SEE CHART SEE CHART SEE CHART PSC MOTOR OPTION NOTE FOR HIGH STATIC MOTORS USE THE FOLLOWING 3 SPEED SWITCH WIRING CONFIGURATION RED LOW BLUE MED BLACK HIGH YELLOW COMPLETE THE WIRING IN ACCORDANCE WITH NATIONAL AND LOCAL CODES WIRING DIAGRAM ...

Страница 22: ...lancing The initial step is to visually inspect all of the equipment plenums connecting ductwork and piping Ensure that all systems are properly installed and supported and that all construction debris or foreign objects have been removed from the equipment Each unit should be checked for Free blower wheel operation Loose wires Loose or missing access panels or doors Filter installed clean and of ...

Страница 23: ... some systems may require repeated venting over time to fully eliminate air in the system Prior to the water system start up and balancing the hot water system should be thoroughly flushed to clean out dirt and debris which may have accumulated in the piping during construction During this procedure all unit service valves must be in the closed position This will prevent any foreign material from ...

Страница 24: ...expert The system must be complete and all components must be in operating condition before beginning the water system balancing procedures Each hydronic system has different operating conditions depending on the devices and controls installed for the particular application The actual balancing technique may vary from one system to another After the proper system operation is established the appro...

Страница 25: ...op coats involving an exothermic chemical process between two components such as epoxies and urethanes should be avoided All standard colors including primer can be painted over If the installing contractor chooses not to paint over the primer color the factory cannot match primer color on future orders potentially causing color match issues in the field Factory touch up spray paint may require a ...

Страница 26: ...d increased power consumption Clean the coil at every inspection Units provided with the proper type of air filters replaced regularly will require less frequent coil cleaning Normal operation and periodic maintenance General Each unit on a project will have its own unique operating environment and conditions which dictate a maintenance schedule for that unit that may be different from other equip...

Страница 27: ...ed in the unit instead of being disposed of when dirty The cleanable filters may be washed in hot soapy water and then set aside to dry before recharging and reinstalling Before replacing the filter it should be recharged with some type of entrapment film such as Film Car Recharging Oil The filter should be sprayed on both sides or submerged in the film to assure complete coverage The filter shoul...

Страница 28: ... undamaged Unit received complete as ordered Unit arrangement and handing is correct Unit structural support is complete and correct Handling and installation Mounting grommets isolators are used Unit mounted level and square Proper access is provided for unit and accessories Proper overcurrent protection is provided Proper service switch disconnect is provided Proper hot water line sizes to unit ...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...der Rittling 100 Rittling Boulevard Buffalo NY USA 14220 T 716 827 6510 F 716 827 6523 sales zehnder rittling com www zehnder rittling com Zehnder Rittling May 2014 English subject to change without notice ...

Отзывы: