Parameterisation of boost ventilation and absent operating modes 

As described in “3.1.6 Description of the operating functions and signals”, the boost ventilation and absent operation modes 
can be adjusted according to user-specific needs. 

NOTE

 

Parameterisation must be carried out in the accessible status of the control board. 

  Configuration of the boost ventilation mode 

The temporarily active fan speed 4 operates as the boost ventilation function. To enable boost ventilation mode, DIP switch 
no. 3 in MODE SW1 must be set to the ON position. 

DIP switch no. 

Position of DIP switch  

3 ON 

The boost ventilation time can be parameterised between 5 and 120 minutes with the programming module. 

  Configuration of the Away mode 

The temporarily activated fan speed 1 operates as the Away function. The active operating time of fan speed 1 can be 
parameterised between 15 and 59 min/h with the programming module. 

 

Installing the exterior wall panel as a facade finish 

 

WARNING

 

Danger due to falling exterior wall panel  

The exterior wall panel is to be fixed using the supplied mounting accessories or with mounting material suitable for the 
facade construction. The professional and safe installation is to be checked and the responsibility of the technical crew 
performing the work. 

 

NOTE

 

The exterior wall panel should not be installed until the façade is completed, however, immediately following installation 
of the ventilation unit. Check the flatness between the wall mounting pipe, the EPP pipe housing, and the façade surface. 
The connection between the wall mounting pipe and the facade surface must be permanently sealed against moisture 
ingress. 

Proceed as follows for the installation of the exterior wall panel: 

1.  Take the top cover of the outside wall panel off the bottom cover of outer cover as set out in 3.3.1.1, item 2. 

NOTE

 

 

Using the raised contours for the airflow, put the bottom cover of the 
outside wall panel onto the EPP housing section pipe extension so 
that it fits exactly, and transfer the drill holes onto the façade 
centrally. 
Take the bottom cover of the outside wall panel off again and 
prepare a suitable fastening technique for the four fixing points as 
set out in the façade design. 

 

NOTE

 

for the square wall mounting pipe

 

 

Use a hammer to cautiously tap in the respective driven-in dowel 
into the four receiving holes in the EPP housing for the wall 
mounting pipe surface plan. 

 

Содержание ComfoSpot 50

Страница 1: ...Decorative Radiators Comfortable indoor ventilation Heating and cooling ceiling systems Clean air solutions User manual on operation and installation for operators and installers Zehnder ComfoSpot 50...

Страница 2: ...property of Zehnder Group Publication as a whole or in parts requires the written approval of Zehnder Group In house duplication designated for the evaluation of the product or for proper use is permi...

Страница 3: ...ements of the control panel 6 Description of the operating functions and signals 7 Options for ventilation operation 9 External control panel 9 Operation via networking 9 Automatic operation via senso...

Страница 4: ...iciently qualified for the respective work involved Qualification of target group 1 3 1 1 Users Users must be instructed by qualified personnel as follows Instruction in hazards when handling electric...

Страница 5: ...supply unless instructions to the contrary are listed in the manual Following installation all parts that could lead to personal injury are protected by the housing The unit cannot be opened without...

Страница 6: ...acade finish Intended use also includes observing all instructions in the user manual In the event of improper use the Zehnder Group accepts no liability for any damage that may occur and no warranty...

Страница 7: ...unit fully automatic demand controlled ventilation operation is possible An enthalpy exchanger which can transfer both humidity and heat owing to the physical characteristics is used in the ComfoSpot...

Страница 8: ...l has touch sensitive buttons and LED status indicators NOTE The ventilation unit can be operated at the same time with the internal and the external control panel Item Description A Facade finish ext...

Страница 9: ...up Fan speed 3 FS3 Increased ventilation The ventilation unit runs at a higher ventilation level 40 m h to reduce peak loads e g when several people are present LED1 4 light up Fan speed 4 FS4 Intensi...

Страница 10: ...e LED display is switched off If any key is touched the LED indicator will be activated again Touching the button brings about no change to the operating mode however Standby mode The unit can be swit...

Страница 11: ...s switched off Display of LED1 3 as example Frost protection mode From an outside air temperature of 4 C the frost protection function is automatically activated In frost protection operating mode the...

Страница 12: ...ting mode with humidity control 3 2 3 2 Functional principle of CO2 VOC sensor NOTE The CO2 sensor module and the VOC sensor module are each combined with a humidity temperature sensor The CO2 sensor...

Страница 13: ...unit is equipped with two air filters of filter class ISO Coarse 70 as standard Retrofitting with filters of filter class ISO ePM10 80 is possible preferably the higher quality ePM10 filter is inserte...

Страница 14: ...the bottom cover of the interior cover next to the filter compartment in each respective case Make sure that the filter is not pushed into the filter compartment with force 7 Insert the filter caps a...

Страница 15: ...onger be mechanically ventilated This may result in moisture and mould problems in the room that requires ventilation 4 Chapter for qualified personnel Installation requirements The following requirem...

Страница 16: ...rge when handling the control unit e g by wearing an anti static armband Installation preparations 4 2 2 1 Preparations for installing the wall mounting pipe Prior to installing the ventilation unit a...

Страница 17: ...unit either to the wall thickness or to the measure of length of the wall mounting pipe by shortening the EPP housing extension NOTE The cut must be performed all around perpendicular to the axis of t...

Страница 18: ...the openings for the electrical connections and fix the bottom cover of the interior cover in place using the screw from the installation set or the alternatively selected fixing material Relocating...

Страница 19: ...control panel carrier Restore the plug connection between the ribbon cable and control panel NOTE Watch out for the reverse polarity protection for the post connection when connecting 6 Install the ri...

Страница 20: ...Der The power supply is connected after the final positioning of the unit in the wall mounting pipe In doing so proceed as follows 1 Plug the WAGO lighting terminals 3 pieces included in the installa...

Страница 21: ...mounting material suitable for the facade construction The professional and safe installation is to be checked and the responsibility of the technical crew performing the work NOTE The exterior wall p...

Страница 22: ...ten the four screws from the supplied installation kit for the top cover of the outside wall panel on the bottom cover of the outside wall panel NOTE In general the top cover of the outside wall panel...

Страница 23: ...ing pipe until the PVC cover for the control board is freely accessible 5 Remove the PVC cover of the control board at the side of the ribbon cable entry out of the slot on the EPP housing and grippin...

Страница 24: ...EPP housing tight when doing so 10 Following the inspection install all parts whilst considering the restoration of all electrical connections in the reverse order 11 Restore the power supply and set...

Страница 25: ...ension set Mounting position Horizontally in the wall mounting pipe air passage openings laterally vertical on the interior cover and outside wall panel thumb wheel for shutter adjustment AT THE RIGHT...

Страница 26: ...370 330 Bottom cover for outer panel View from outside EHA ODA 330 360 Angular structural shell set View from outside Angular structural shell set View from inside 40 areas for cable entry 35 90 4x fa...

Страница 27: ...25 Terminal scheme...

Страница 28: ...ehnder Group Deutschland GmbH Almweg 34 77933 Lahr Deutschland T 49 7821 586 392 F 49 7821 586 406 sales international zehndergroup com www international zehnder systems com PDE Manual_CS50_V4 0_V0621...

Отзывы: