EN - 25

3. 

Error messages

When  the  filters  must  be  cleaned  or 
replaced  the  text  says  FLTR,  INT  or 
FLTR, EXT*. Clean or replace the filters as 
described in the manual of the ventilation 
unit.

In event of a malfunction in the ventilation 
unit,  the  text  says  ERROR,  and  the 
corresponding malfunction code.
The meaning of the displayed malfunction 
code and how to solve the problem can be 
found in the manual of the ventilation unit.

The  following  malfunction  codes  only 
appear on the device:

Code

Description

FLTR, INT

Internal Filter is dirty.

FLTR, EXT

External Filter is dirty.

COMM, 
ERROR

No communication between 
the ventilation unit and the 
device.

Resetting FLTR, INT

1.  Press OK to enter the reset menu. 

2.  Press 

 or 

 to choose OK.

3.  Press OK to confirm. The text says 

DONE for 2 seconds. The menu is 
automatically closed.

Resetting FLTR EXT

After  cleaning  or  replacing  the  external 
filter  as  mentioned  in  the  external  filter 
manual  the  malfunction  code  will  reset 
itself automatically.

Resetting error messages

1. Press MENU.
2. Press OK.

4. 

Installation

  Disconnect the ventilation unit 

from the main power before 
installing the device. 

 

 Always 

follow 

local 

safety 

regulations.

  The letters mentioned in this 

chapter refer to the installation 
figures (fig. 1, 2 or 3 ) at the 
back of this document.

1. If ordered: Attach the wall-mounting 

casing I with the plugs H and screws 
G to the wall.

2. Fasten the wall frame A with the 

screws F** on the wall, wall-mounting 
casing I or mounting plate**.

3. Put the communication cable through 

the wanted design frame X and 
resize window D

4.  Connect the communication cable 

between the ventilation unit and the 
device as shown in fig. 4 at the back 
of this document. 

   The cable requirements are:

 

 

Q

  Minimum 4x0.25mm

2

 

(AWG 24)

 

 

Q

  Maximum 4x1.00mm

2

 

(AWG 17), 50m long

 

 

Q

  Advice 4x0.34mm

2

 (AWG 

22) 

5.  Screw the device B (with the design 

frame X and the resize window D) 
with the screws E to the frame A.

  When replacing use any of 

the following screws: 

Q

  PT10 bolcil. hardened and 

galvanized steel screw 2.2 
x12 PT10

 

 

Q

  M2.2x 12 cross recess 

plan plas-fix45°

Only available if the mentioned 
function is connected.

**  not supplied.

Содержание ComfoSense CH

Страница 1: ... ComfoSense Manual ComfoSense Betriebsanleitung ComfoSense Manuel ComfoSense Manuale ComfoSense Podręcznik ComfoSense Manual ComfoSense Heating Cooling Fresh Air Clean Air ComfoSense CH ComfoSense 55 ComfoSense 67 ...

Страница 2: ...he ComfoHood 20 2 5 Switching the ComfoHood Timer 20 2 6 Switching the PARTY TIMER 20 2 7 Ventilation program PROG 21 2 8 Setting the CLOCK 23 2 9 Setting the COMF Comfort temperature 23 2 10 Switching the FAN 23 2 11 Setting PARAM Parameters 24 2 12 CLOCK Back up 24 3 Error messages 25 4 Installation 26 5 Commissioning 26 5 1 Power up 26 5 2 Setting P menu s 26 I Figures 95 ...

Страница 3: ...r installation to a maximum of 30 months after production date of the device The warranty becomes invalid if Q The installation has not been carried out according to the applicable regulations Q The defects are due to incorrect connection inexpert use or contamination of the device Q Parts are used that have not been supplied by the manufacturer or repairs are made by unauthorized persons On site ...

Страница 4: ...nu Q Exit menu Display 1 Q Text Q Time 2 Value program parameter temperature 3 Q Degree Celsius Fahrenheit Q Percentage 4 ComfoHood 5 Q Supply fan off Q Exhaust fan off 6 Fan speed 7 Night cooling active 8 External sensor overrules the ventilation setting 9 Q Start time of a program Q End time of a program Only available if the mentioned function is connected Shown temperature in F will be changed...

Страница 5: ...efault setting can be programmed into the device see Setting the PROG The device is in Automatic operation mode when is pointing to AUTO Press AUTO MAN to switch to the Automatic operation mode 2 2 MAN operation In Manual operation mode the preprogrammed ventilation settings of the device will be overruled temporarily Overrule temporarily Directly press or to increase or decrease the fan speed The...

Страница 6: ...rm The text says OFF for 2 seconds 2 5 Switching the ComfoHood Timer This function is only visible if a ComfoHood cooker hood with sensor is connected and a delay time is programmed in PARAM P20 Turning on the ComfoHood Timer 1 Press MENU The text says HOOD 2 Press to choose HOOD TIMER 3 Press OK to confirm The text says ON for 2 seconds The text TIMER is visible in the main screen Turning off the...

Страница 7: ...ram with the shortest time is the leading program In the example above Prog 3 overrules Prog 2 When both overlapping programs have an equally long period the program with the smallest program number will be the leading program In the example above Prog 3 overrules Prog 5 Every day in the program starts at 3 00 and ends at 2 59 Setting a program 1 Press MENU 2 Press or to choose PROG 3 Press OK to ...

Страница 8: ... for 2 seconds After this SET is blinking The next program number is visible 18 Press MENU to return to the main menu Or go back to step 4 to set another program Deleting a program 1 Press MENU 2 Press or to choose PROG 3 Press OK to confirm SET is blinking The program number is visible 4 Press or to choose the program to delete PROG is blinking The program number is visible 5 Press OK seven times...

Страница 9: ... IN or exhaust OUT fan of the ventilation unit can be turned off manually This may be desired to keep out unpleasant odors from outside Bear in mind that switching off a fan will temporarily immobilize your dwelling s balanced ventilation system so do not forget to turn the fans on again When can the FAN not be switched To prevent air being sucked back from the chimney of a fireplace the ventilati...

Страница 10: ... 4 Press OK to confirm The parameter number P1 is blinking 5 Press or to choose the main parameter menu number 6 Press OK to confirm A second number next to the chosen number is blinking 7 Press or to choose the sub parameter menu number 8 Press OK to confirm The parameter value appears 9 When the appeared value is blinking press or to change the parameter value Only a parameter value that is blin...

Страница 11: ...elf automatically Resetting error messages 1 Press MENU 2 Press OK 4 Installation Disconnect the ventilation unit from the main power before installing the device Always follow local safety regulations The letters mentioned in this chapter refer to the installation figures fig 1 2 or 3 at the back of this document 1 If ordered Attach the wall mounting casing I with the plugs H and screws G to the ...

Страница 12: ... result will be 1 Press OK The text says SHIFT for 2 seconds 2 Press MENU before the text SHIFT disappears The text says COMF 3 Press or to choose PARAM 4 Press OK to confirm The parameter number is blinking 5 Press twice to choose PASSW 6 Press OK to confirm The password number 0 appears 7 Press to choose 14 8 Press OK to confirm P3 is blinking 9 Press or to choose the main parameter menu number ...

Страница 13: ... in Default Screen 1 Q Clock not visible Default Screen 0 895 0 1 0 Q Night cooling symbol visible in Default Screen 1 Q Night cooling symbol not visible in Default Screen 0 896 0 1 0 Q Degrees in Fahrenheit 1 Q Degrees in Celsius 0 897 0 255 Software version read only value 898 1 5 Quality RF reach Q 1 bad Q 5 good 899 0 1 0 Reset ventilation program PROG Only available if the mentioned function ...

Отзывы: