   24 - EN

2.10.3Malfunctions (or problems) without alerts

An overview of the malfunctions (or problems) without notifications is given below.

Problem/Malfunction

Indication

Check / action

System switched off

Power supply on

The control circuit board is defective and must 
be replaced.

No power supply

Mains power is off.

High intake temperature 
in summer

Bypass remains closed

Reduce the comfort temperature.

ComfoAir is still in Winter mode: 
Bypass remains closed

Cheking the Mode of the ComfoAir is possible 
with special read-out software.

   Wait untill ComfoAir switches to  

Summer mode.

Low intake temperature 
in winter

Bypass stays open

Increase the comfort temperature.

Little or no 
air supply; 
shower remains damp

Filters blocked

Replace the filters.

Valves blocked

Clean the valves.

Exchanger clogged by dirt.

Clean the exchanger.

Exchanger frozen

Defrost the exchanger.

Fan dirty

Clean the fan.

Ventilation ducts blocked

Clean the ventilation ducts.

ComfoAir is in frost-protection
operation

Wait until the weather warms up.

Too noisy

Fan bearings defective

Replace the fan (bearings).

Fan settings to high

Change the fan (settings).

Slurping noise

  Siphon is empty

  Siphon does not seal properly

Reconnect the siphon.

Whistling noise

  An air gap somewhere

Seal the air gap.

Airflow noise

  Valves do not close onto duct.

  Valves not open far enough

Reinstall the valves.
Reset the valves.

Condensation leak

Condensation drain clogged

Unblock the condensation drain.

Condensation from exhaust duct does not run 
into leakage tray

Check whether the connections 
are correct.

Содержание ComfoAir 200 Luxe Series

Страница 1: ...Cooling Fresh Air Clean Air Heating ComfoAir 200 Luxe Installer manual...

Страница 2: ...l has been compiled with the most care The publisher cannot be held liable for any damage caused as a result of missing or incorrect information in this manual In case of disputes the Dutch version of...

Страница 3: ...g on the wall 8 2 6 3 Connection of the air ducts 8 2 6 4 Connection of the condensation drain 9 2 7 Commissioning the ComfoAir 9 2 7 2 P menus for the installer 11 2 8 Programming air specifications...

Страница 4: ...od of 24 months after fitting up to a maximum of 30 months after the date of manufacture Warranty claims may only be submitted for material faults and or construction faults arising during the warrant...

Страница 5: ...not allowed Always take ESD inhibiting measures when deal ing with electronics such as wearing an antistatic wristband The electronics can be damaged by static charges The ComfoAir is only suitable fo...

Страница 6: ...th high efficient fan HR High Efficient heat exchanger F Connector panel H2 with connections for external switches and controllers Control panel H1 with connections for the fans the bypass temperature...

Страница 7: ...n w c 125 Pa 1 10 A Electricity Power supply 240 50 60 V Hz Cos phi at Maximum 0 8 Connecting Power 1 49 kW Maximum Power Pre heater 1 35 kW Leakage current 1mA Supply fan noise level at 0 m Position...

Страница 8: ...Power 1 49 kW Maximum Power Pre heater 1 35 kW Leakage current 1mA Supply fan noise level at 0 m Position Ventilation capacity Sound power Absent Setting 11 77 CFM 20 m3 h at 0 01 in w c 3 Pa 37 db A...

Страница 9: ...6 EN 2 3 Dimension sketch...

Страница 10: ...is supplied in the following types Type ComfoAir 200 L Luxe ERV ComfoAir 200 R Luxe ERV Meaning of the suffixes L Left version R Right version ERV Contains a enthalpy exchanger by default Luxe Contain...

Страница 11: ...ile installing the air ducts Install the air exhaust duct so it drains in the direction of the ComfoAir Insulate the outside air supply and the air exhaust duct between the roof wall passage to render...

Страница 12: ...st be commissioned This can be done via the P menus on the digital operat ing device These P menus can be used to enter vari ous settings ventilation programmes in particular for the ComfoAir An overv...

Страница 13: ...e input 0 Min 15 Min 0 Min P22 Optional Note Only applies to systems fitted with a corded switch and a second switch in the bathroom Overrun timer for the bathroom switch to switch to normal position...

Страница 14: ...city in of the exhaust fan to HIGH POSITION 18 100 nL HL 70 90 P34 Setting the capacity in of the supply fan to ABSENT POSITION 0 or 15 97 nL HL 15 15 P35 Setting the capacity in of the supply fan in...

Страница 15: ...type Li Left hand version Re Right hand version Li Re Li With delivery the ComfoAir is correctly pre programmed at the factory After an general reset the pre programming is lost and the setting must b...

Страница 16: ...oAir will run at maximum Rotation Per Minute RPM The bypass valve will open and close P77 Resetting filter dirty counter 0 1 activate 0 Note This resets the counter that triggers a dirty filter alert...

Страница 17: ...ode the bypass valve is al ways closed After 30 minutes the ComfoAir au tomatically terminates the programming mode 2 Close all windows and outside doors 3 Close all inside doors 4 Check the presence...

Страница 18: ...ecessary cleaning the heat ex changer Inspecting and if necessary cleaning the fans A concise explanation of these maintenance activities is given in the paragraphs below Check the condensation drain...

Страница 19: ...um of 1 5 Nm This is roughly equal to setting 2 of an average battery powered drill 2 9 2 Inspecting and cleaning the fans Check the fans once every 2 years 1 Remove the heat exchanger as instructed i...

Страница 20: ...ription A0 n a A1 NTC sensor T1 is defective outside air temperature A2 NTC sensor T2 is defective supply air temperature A3 NTC sensor T3 is defective return air temperature A4 NTC sensor T4 is defec...

Страница 21: ...function Yes No Was the temperature 27 C or 127 C Reset the unit P74 on 1 Disconnect the power from the ComfoAir Disconnect the power from the ComfoAir Disconnect the power from the ComfoAir Release t...

Страница 22: ...control circuit board Activate the self test P76 on 1 Did the bypass motor run Yes Disconnect the power from the ComfoAir Replace the control circuit board Remove the motor Disconnect the power from t...

Страница 23: ...everse order Reconnect the power to the ComfoAir No Reconnect the power to the ComfoAir Is there 12VDC present on the Luxeconnection panel Yes Disconnect the power from the ComfoAir Replace the Luxe c...

Страница 24: ...onnect the power from the ComfoAir Replace the control circuit board Is a control signal 1 5 10 VDC present on the fan Yes No Disconnect the power from the ComfoAir Replace the control circuit board R...

Страница 25: ...he ComfoAir Install all parts in reverse order Reconnect the power to the ComfoAir Disconnect the power from the ComfoAir Replace the connection panel Are the connections at the ComfoAir correct Disco...

Страница 26: ...panel 2x to reset the FLTR warning Disconnect the power from the ComfoAir Remove the filter caps from the ComfoAir Remove the dirty filters from the ComfoAir Slide the clean new filters back into the...

Страница 27: ...o air supply shower remains damp Filters blocked Replace the filters Valves blocked Clean the valves Exchanger clogged by dirt Clean the exchanger Exchanger frozen Defrost the exchanger Fan dirty Clea...

Страница 28: ...umber Part Article number 1 Fan Right hand Green 400200034 2 Fan Left hand Red 400200035 3 Control panel 400300051 4 Connector panel 400300031 5 Temperature sensor T1 T3 400300049 6 Temperature sensor...

Страница 29: ...26 EN 2 12 Wiring diagram ComfoAir 200 RIGHT HAND version...

Страница 30: ...EN 27 2 13 Wiring diagram ComfoAir 200 LEFT HAND version...

Страница 31: ...uct ComfoAir 200 UL L R Luxe ERV UL file number E345822 2 15 Temperature conversion table C F C F 5 41 0 23 73 4 6 42 8 24 75 2 7 44 6 25 77 0 8 46 4 26 78 8 9 48 2 27 80 6 10 50 0 28 82 4 11 51 8 29...

Страница 32: ...Zehnder America Inc 6 Merrill Industrial Drive Suite 7 Hampton NH 03842 603 601 8544 info zehnderamerica com www zehnderamerica com ZGNL Manual_40011015 V0117 EN Subject to change...

Отзывы: