2.7        Ducting Guidelines 

   

2.7.1          Please refer to design drawings for proposed ducting layout.

2.7.2          Four spigots are provided for connection of the ducting;

     
                  •    ComfoAir 155 CM - 125mm nominal diameter 

                  Ductwork should be securely connected to spigots. Failure to do this will cause unnecessary air leakage and 
                  impair performance. Ducting must be connected to all four spigots according to right or left hand configuration 
                  

(See Section 2.3 for Configuration). 

It is recommended that a minimum distance of 200mm is maintained 

                  between the ComfoAir 155 CM and any ducting bends.

2.7.3          To prevent condensation, ensure that the intake and exhaust ductwork from the unit is insulated.

2.7.4          Where ducts are exposed in unheated areas, such as roof spaces, they must be insulated with at least 25mm of 

                  insulation.

2.7.5          If applicable, Fire Dampers 

MUST BE FITTED

in accordance with Part B of the Building Regulations.

2.7.6          

Rigid Ducting

                  •    Install using the fewest number of fittings to minimise resistance to air flow.
                  •    Where possible, final connection to grilles and unit should be made with a flexible connection.
                  •    Mechanically fix ducts using metal jubilee clips and appropriate non-hardening sealant for air tightness.
     
                  

WARNING: Do not use screws for connection and ensure jubilee clips 

            are not over tightened.

2.7.7           

Flexible Ducting

                  •    Ensure ducting lengths are kept to a minimum and ducting is pulled taut so that it is smooth and straight. 

                       A maximum of 300mm should be used on each spigot.

                  •    Mechanically fix ducts using metal jubilee clips and tape seal for air tightness.

     

         W ARNING: Should be in accordance with local Building Regulations.

 

 

Min 5º fall

Figure 6 - Close up view

of condensate

Figure 7 - Front View

Figure 8 - Side View

Содержание ComfoAir 155 CM

Страница 1: ...ComfoAir 155 CM Mechanical Ventilation with Heat Recovery Installation Instructions CA155CM GB...

Страница 2: ...2 0 Installation Instructions 4 General Preparation 4 Configuration 5 Mounting 6 Access for Maintenance 7 Condensate Drain 7 Ducting Guidelines 8 Electrical 9 Wiring the Unit 10 Connecting to the BMS...

Страница 3: ...ow and high option ZGRC1 Hardwired boost and system status controller switching between low and high option ZGS1 Hardwired switch providing switching between low AUX and high option 1 1 5 Packaging in...

Страница 4: ...ired for compliance with local Building Regulations 2 1 2 Installation of the unit should be in accordance with the current editions of Building Regulations NHBC Compliance Guide and BS7671 IEE Wiring...

Страница 5: ...on 2 5 Access for Maintenance 2 2 4 The unit can be configured for right and left hand installation at a touch of a button by following the steps within the Commissioning Wizard See Section 3 1 4 Comm...

Страница 6: ...e 1 and loosely fit four screws within each slot at the inner nearside point This will allow the bracket to be slotted inwards to secure the unit 2 4 3 The unit fixes to the ceiling bracket by slottin...

Страница 7: ...k of mechanical damage to the drainage pipe work IMPORTANT NOTE The condensate drain must incorporate a waterless trap or U bend to create an air block and avoid leakage of smells back into the unit I...

Страница 8: ...must be insulated with at least 25mm of insulation 2 7 5 If applicable Fire Dampers MUST BE FITTED in accordance with Part B of the Building Regulations 2 7 6 Rigid Ducting Install using the fewest nu...

Страница 9: ...ch having a minimum contact separation of 3 0mm must be used to provide isolation for the unit 2 8 5 The recommended switches for use with this product are the Zehnder ZGS2 Optional 2 position hardwir...

Страница 10: ...speed control via a light switch 2 9 2 Two speed control via ZGS2 switch 2 9 3 Three speed control via ZGS1 switch 2 9 4 Three speed control via a light switch for trickle boost speeds and an AUX spee...

Страница 11: ...a minimum separation distance of 35mm between the mains power and controller cables BMS Connector Pre wired supply cord connector DO NOT DISCONNECT ComfoAir 155 CM Figure 9 Top View Cable grommet for...

Страница 12: ...e normally closed contact 5 N O Volt Free normally open contact 6 Common Relay common Figure 11 ZGRC1 Controller Figure 12 BMS Wiring Diagram 1 2 3 4 5 6 1 2 6 5 4 3 N C N O COM ELECTRICAL CONNECTION...

Страница 13: ...le clamp down with screw fixings 2 9 9 Refit electrical cover taking care gasket seal underneath is seated correctly and cable is not trapped 13 1 2 3 4 5 Pre wired supply cord not shown Figure 13 Sec...

Страница 14: ...Bottom line flashing cursor indicating next action to be reviewed changed P O R T C O N F I G R H d w f c k a b Example 2 Re confirmation screen Top line function statement Bottom line three selectab...

Страница 15: ...steps of the wizard are as follows 15 P O R T C O N F I G R H E X T R A C T H I G H 6 6 S U P P L Y H I G H 6 6 E X T R A C T L O W 3 3 S U P P L Y L O W 3 3 Port Configuration Set up Rotate button t...

Страница 16: ...hoose either ON or OFF Default setting ON Smart Timer Rotate button to choose either ON or OFF Default setting ON Setup Complete Rotate button to EXIT and press button to select Installer Settings 3 1...

Страница 17: ...r indicators are NOT reset 3 1 8 Performance Graph Airflow Characteristics S E T U P M E N U p a s s w o r d e n t r y P A S S W O R D X X X X 3 1 9 To Re activate Commissioning Set up Wizard In the e...

Страница 18: ...ly Low Wizard airflow setting will be shown rotate button to required airflow Wizard airflow setting will be shown rotate button to required airflow Wizard airflow setting will be shown rotate button...

Страница 19: ...Setup Menu Press button to select Enter Password 1010 by rotating the button to the respective number and press to select this has to be completed for each number prior to continuing Rotate button to...

Страница 20: ...g to press E OE All goods are sold according to Zehnder s Standard Conditions of Sale which are available on request All dimensions referred to are in millimetres unless otherwise stated Zehnder Group...

Отзывы: