Identification: MD-AL-GI-00
Rev. 1.0 07.06.21 - Application: GID
Connext User Manual
Rev. 1.2 07/06/2021
1)
Remove a suitable length of the protective sleeve, as shown in the figure (A: 80~100 mm B:
6~8 mm).
Figure 17 – Preparing the RS485 cables
2)
Connect the 2-pole cable to the port of the photovoltaic inverter marked “RS485”. Follow the
polarity shown in the figure and the pinout in the table.
Figure 18 - Connections on photovoltaic inverter
PIN RS485
24-pin terminal block
RS485 + (Red)
9
RS485 – (Black)
10
Table 11 - RS485 connections to photovoltaic inverter
4.3.5.
Connecting to Azzurro three-phase photovoltaic inverters
To connect the RS485 port to Azzurro three-phase photovoltaic inverters, follow these instructions.
1)
Use a RJ45 connector to connect one of the two RS485 ports on the inverter-side.
SD
485s