POSITIONING OF CT SENSOR
:
✓
Positioned at the output of the import/export meter
so that all incoming and outgoing power flows can be
read, it must include all phase cables entering or exiting the meter.
✓
The
direction of the CT is independent of the installation
, and is recognised by the system during the first
start-up.
Connect negative and positive in the sensor respectively to inputs 19 and 18 of the COM connector
Use an 8-pin, category 6
STP
cable as an
EXTENSION CABLE
; use all the coloured pins
(blue-orange-green-brown) to extend the positive cable of the CT and all the white/coloured pins
(white/blue-white/orange-white/green/brown) to extend the negative cable of the CT.
The shield must be grounded on one of the two sides.
PIN
Definition
19
CT-
(black/yellow)
18
CT+ (red)
Use for distances of less
than 50 m between the
inverter and CT
CT
- measures the
current exchanged
with the grid
M1
Household loads
Magn. Diff. (
300mA
)
Inverter
Magn. Diff.
(
30mA
) General
Meter
Production
Meter
Exchange
M2
OK
M1
Household loads
Magn. Diff. (300mA)
Inverter
Magn. Diff. (30mA)
General
Meter
Production
Meter
Exchange
M2
NO
10.1 MEASURING EXCHANGE VIA CT SENSOR
14