Fault Indicator System ENQ4 

L05 

 

E61-283-00 

Operating Instructions

 

English translation 

Errors and technical changes reserved 

 

At A1-A2 connect the supply voltage 

 

The internal alarm contact switches the voltage from A1 

to terminal 14.  

 

The voltage on the fault alarm inputs S1-S5 ist the same 

as the supply voltage. 

 

External  fusing  (6  A)  of  the  output  contact  14  must  be 

provided. 

 

A line cross section of  2.5 mm

2

 

must not be exceeded 

 

If the 24 V version is used, a safety transformer accord-

ing to EN 61558-2-6 or a power supply unit with electrical 

isolation from the mains must be connected. 

 
If the device does not function after commissioning, it must 

be  returned  to  the  manufacturer  unopened.  Opening  the 

device will void the warranty. 

Fig. 1: Electrical Connection

 

Electrical 

Connection

 

Maintenance 

The  device  must  be  checked  once  per  month  for  proper-

function and for signs of tampering. 

The device is otherwise maintenance free, provided that it 

was installed properly. 

Techn. Data 

Dimensions 

Variants 

A1: 

 

Power supply (+ 24 V at DC24 V version) 

A2:  

Power supply  (0V at DC 24 V version)

 

S1-S4 :

 

Fault alarm inputs  

 

S5: 

 

Test input

 

14

 :

 

Alarm contact 

 

8

1 0 0

4 5

5 5

4 8

55mm with additional front frame 

Order-No. 583000

 

ENQ4  AC230 V

 

Order-No. 583001

 

ENQ4  AC115 V

 

Order-No. 583002

 

ENQ4  DC24 V

 

Order-No. 583010

 

Plastic front frame 55

 

x

 

55 mm

 

Operating voltage  U

N

 

 

AC 230 V, 50-60 Hz, AC 115 V, 50-60 Hz, DC 24 V

 

Voltage tolerance

 

 

+ 10% / - 15%

 

Residual ripple (type DC)

 

 

5%

 

Power consumption

 

 

AC 1.5 VA; DC 2 W 

 

Inputs

 

 

4 fault alarm inputs, reporting on opening, 

 

 

1 additional test function 

Function

 

 

S1, S2, S3, S4 switching, reporting, storing 

 

 

S5 inverted switching without storage function  

Alarm input voltage

 

 

same as operating voltage 

Input current

 

 

< 10 mA

 

Signal delay 

 

approx. 200 ms for each reporting input  

 

 

and additional 200 ms for relay contact 

Acknowledgement/reset 

 

by interruption of power supply 

LED´s 

 

green: Normal Operation, Contact A1-14 closed 

 

 

 

red: Alarm on Input S1..S4, Contact A1-14 open 

 

Protection

 

 

front IP54

 

Switching capacity

 

 

1 NC, max. AC250 V, max. 8 A, max. 2000 VA

 

 

 

DC: 2 A at 24 VDC 

 

Contact life

 

 

mechanical 5x10

7

 operations

 

Contact fuses

 

 

6A  

 

Max. line cross section

 

 

2.5 mm

2

 

Max. cable length inputs

 

 

100 m

 

Test voltage

 

 

2.5 kV (control voltage/contacts)

 

Rated impulse withstand voltage

 

4 kV DIN VDE 0110

-

1

 

Rated insulation voltage

 

 

250 V

 

Temperature range

 

 

0

0

 - +50

0

 

Weight

 

 

approx. 180 g

 

Installation position 

 

any

 