When the controller powers on, the unit will run self-qualify mode and automatically show below 

items on LCD before going into charging process

Self-test starts, digital meter segments test

Software version test

System battery voltage and current test

External battery temperature sensor test (if connected)

Absorption voltage test

Float voltage test

Self-test completed

CONTROLER OPERATION – LCD DISPLAY

SYSTEM BATTERY VOLTAGE SETTING 

 

Press and hold the 

SET UP

 button for 3 seconds to go into the system battery voltage setting 

mode, press 

PV / +

 or 

BATT / -

 button to select your desired system battery voltage 12V, 24V or 

AUTO, press the 

SET UP

 button again to confirm the battery voltage setting. 

 

THE DISPLAY IN SEQUENCE:

SYSTEM BATTERY TYPE SETTING 

 

Please check your battery manufacturer’s specifications to select correct battery type. The unit 

provides 9+1 custom battery types for selections: LI-95, LCO, LTO, LFP, Crystal (Lead crystal), Gel, 

AGM, WET (Conventional lead acid) and Calcium (Calcium contented) battery plus Custom setting. 

To set the battery type, press the 

SET UP

 button to go into your battery type setting mode, the 

battery type you select will be flashed on the LCD meter, the default setting is AGM Battery; the 

controller will automatically memorize your battery type setting.

CUSTOM SETTING 

 

This solar controller provides a CUSTOM mode to meet your special battery charging demand, the 

users can preset the Absorption voltage level and duration, Equalization voltage level, duration 

and periodical cycle, Float voltage level and Reset voltage level for your targeted battery charging 

parameters. 

Alternatively display Absorption Volage character 

AbS.U

 and voltage data when going into 

CUSTOM mode

The controller will automatically memorize your previous battery voltage setting, If AUTO mode 

selected, the controller will automatically detect 12V or 24V battery connected.

LFP battery shown in LCD indicates Lithium Iron Phosphate battery, LiFePO4 battery. LI-95 shown 

in LCD indicates the battery profile keeps your LiFePO4 battery charged at 95% LTO battery shown 

in LCD indicates Lithium titanate oxidized, Li4Ti5O12 battery.

Press 

PV / +

 or 

BATT / -

 button to navigate your desired battery type as below:

Press the 

SET UP

 button again, the selected battery type will be solid On and confirmed.

Absorption voltage setting range from 13.20V ~ 15.50V, press 

PV / +

 or 

BATT / -

 button for once +/- 

0.05V variation, press the 

SET UP

 button again to confirm the absorption voltage level you preset, 

then move to next Absorption duration setting.

Alternatively display Absorption Time character 

AbS.T

 and duration data; Absorption duration 

setting lasted from 5 – 500 minutes, press 

PV / +

 or 

BATT / -

 button for once +/- 5 minutes variation, 

press the 

SET UP

 button again to confirm the absorption duration setting, then move to next 

Equalization voltage setting.

Alternatively display Equalization voltage character 

EqL.U

 and voltage data; Equalization voltage 

setting range from 13.20V ~ 16.2V, press 

PV / +

 or 

BATT / -

 button for once +/- 0.05V variation, press 

the 

SET UP

 button again to confirm the Equalization voltage and then move to next Equalization 

duration setting.

Alternatively display Equalization Time character 

EqL.T

 and duration data; Equalization duration 

setting lasted from 5 – 500 minutes, press 

PV / +

 or 

BATT / -

 button for once +/- 5 minutes variation, 

press the 

SET UP

 button again to confirm the Equalization duration setting and then move to next 

Equalization periodical cycle setting.

Alternatively display Equalization periodical cycle character 

EqL.P

 and cycle day; Equalization 

periodical cycle day setting P.7/11 from 0 – 100 days, press 

PV / + 

or 

BATT / -

 button for once +/- 1 

day variation, 0 indicates no Equalization setting; press the 

SET UP

 button again to confirm the 

Equalization periodical cycle setting and move to next Float voltage setting.

Alternatively display Float voltage character 

FLT.U

 and voltage data; Float voltage setting range 

from 13.00V ~ 14.00V, press 

PV / +

 or 

BATT / -

 button for once +/- 0.05V variation, press the 

SET UP

 

button again to confirm the Float voltage and then move to next Reset/Rstart setting.

Press 

PV / +

 button in sequence, the LCD will display in turn with solar input voltage, current, 

power and kWh.

Press 

BATT / -

 button in sequence, the LCD will display in turn with battery voltage, charging 

current, charged capacity (Amp-hour) and battery temperature (if external temperature sensor 

connected)

The users also can read the battery temperature as degree centigrade or Fahrenheit degree by 

pressing 

SET UP

 button for converting.

Alternatively display voltage and FUL when battery is fully charged

Alternatively display Reset/ Restart voltage character 

rST.U

 and voltage data; Reset voltage setting 

range from 12.50V ~ 13.50V, press 

PV / +

 or 

BATT / -

 button for once +/- 0.05V variation, press the 

SET UP

 button again to confirm the Reset / Restart voltage and all settings will be automatically stored.

You also can visually monitor your battery charging condition for each battery; there is an LCD bar 

to show the percentage of charge, you can easily see the battery is charged to 25%, 50%, 75% or 

100%, and also roughly match each charging stage of Soft-start, Bulk, Absorption and Float.

The LCD also can be treated as an independent voltage meter or thermometer at night.

 

 

 

 

 

 

 

LCO BATTERY TYPE SETTING IS ONLY RECOMMENDED WORKING WITH 3-SERIES LITHIUM 

COBALT OXIDE LICOO2 BATTERY

CAUTION: INCORRECT BATTERY TYPE SETTING MAY DAMAGE YOUR BATTERY.

   

 

 

 

 

 

 

 

 

 

                                                                                                                                           

 

     

   

 

     

     

     

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SOLAR INPUT PARAMETER DISPLAY 

 

Once the settings are completed, the solar controller will automatically go into charging process, 

the LCD displays the parameters of solar input as below:

TECH SUPPORT

541-728-0924

[email protected]

Содержание DOMETIC SCC1012

Страница 1: ...LER USER MANUAL TECH SUPPORT 541 728 0924 support zampsolar com INPUT DC 100V MAXIMUM OUTPUT DC 12V 24V 30A THIS MANUAL CONTAINS IMPORTANT SAFETY AND OPERATING INSTRUCTIONS PLEASE READ AND FOLLOW INSTRUCTIONS TO ENSURE PROPER OPERATION ...

Страница 2: ...Designed according to UL1741 EN IEC 62109 1 EMI standard EN61000 61 EN61000 63 and FCC standard 47 CFR Part 15 Subpart B This charger is designed for indoor use only and should never be exposed to rain Do not disassemble the controller Contact Zamp Solar support if the unit requires attention Lead acid LCO LiFePO4 LTO LI 95 batteries can be dangerous Ensure no sparks or flames are present when work...

Страница 3: ... SUPPORT 541 728 0924 support zampsolar com The Solar Controller should be mounted using the mount points highlighted in red shown in the image below Mount the unit to a flat surface MOUNTING THE CONTROLLER ...

Страница 4: ...G Rated Current 30 Amp Solar Panel Controller Battery Solar Panel Controller Battery meter Rated Current Total cable length 10FT 10FT 10AWG 10 15FT 10 15FT 8AWG 20FT 20FT 6AWG Total cable length Total cable size AWG Rated Current 30 Amp Solar Panel Controller Battery Solar Panel Controller Battery meter 1 Take off the rubber mask plate at OPEN end on the top face you will see the four screws loose...

Страница 5: ...he SET UP button again to confirm the absorption duration setting then move to next Equalization voltage setting Alternatively display Equalization voltage character EqL U and voltage data Equalization voltage setting range from 13 20V 16 2V press PV or BATT button for once 0 05V variation press the SET UP button again to confirm the Equalization voltage and then move to next Equalization duration s...

Страница 6: ...city Equalization Only for WET or Calcium battery type when the battery is deeply drained below 10V or every 28 days cycle it will automatically run this stage to bring the internal cells as an equal state and fully complement the loss of capacity Lead crystal Gel AGM battery or Lithium batteries do not run Equalization charge Float Charge or Re Start charge Battery is fully charged and maintained...

Страница 7: ...BLUE FLASH ON ON OFF SOFT START BULK CHARGE FLOAT CHARGE ABSORBTION EQUALIZATION SOLAR PANEL ABNORMAL MODE BATTERY ABNORMAL MODE SOLAR PANEL WEAK 15V Solar panel is connected battery disconnected SOLAR PANEL REVERSE CONNECTION Battery reverse connection SOLAR PANEL OVER VOLTAGE 95V Battery over voltage than 17V Battery temperature over 65ºC The controller over temperature protection LCD DISPLAY LC...

Страница 8: ... Equalization Charging Voltage at 25ºC Input Output Terminal Controller Material Operating temperature Mounting Storage temperature IP grade Operating humidity range Net Weight Temperature compensation range Battery temperature compensation coefficient Voltage control accuracy LCO Battery LTO Battery LFP LI 95 battery for CUSTOM setting range Crystal GEL WET AGM and Calcium battery Restart Voltage ...

Отзывы: