EXEMPLARy APPLICATIONS

EXEMPLARy APPLICATIONS

Room regulator with blending valve

  Press OK in the main menu to choose 

 option.

  In submenu 

 use cursors 

 to choose 

; press OK to confirm.

  In submenu 

 use cursors 

 to choose time of full valve opening from 

15 sec to 1200 sec; this time range should be given in a valve manual by 

the producer as it is unavoidable to operate properly. In case the time range 

is not given by the producer, it can be measured by means of a stopwatch: 

measuring starts with „opening” signal and finishes with full valve opening. 

In case relay time do not precisely correspond with valve opening time, then 

the nearest time once increased should be given; press OK to confirm; go to 

main menu.

  In  main  menu  use  cursors 

  to  choose 

;  option  and  press  OK  to 

confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to con

-

firm.

Room regulator switch on/off (electric heaters, gas/oil boilers, air-conditioners)

  Press OK in the main menu to choose 

 option.

  Use cursors 

 to choose 

; in submenu; press OK to confirm; 

go to main menu.

  In main menu use cursors 

 to choose 

 option and press OK 

to confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to 

confirm.

The regulator operates in the same way as the room regulator. The room 

expected temperature is chosen in temperature adjustment phase.

heater

L N

expected 

temperature

reference 

temperature

Coal-fired boiler pump control

The first sensor is mounted (reference temperature) where hot water escapes or 

at the top of a central heating boiler.

  Press OK in the main menu to choose 

 option.

  Use cursors 

 to choose 

; in submenu; press OK to confirm; go to 

main menu.

  In  main  menu  use  cursors 

  to  choose 

  option  and  press  OK  to 

confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to con

-

firm.

  In 

 option use cursors 

 to choose the curve value points till the last 

one, confirm every choice by OK command.

Exemplary points of heating curve:

Boiler’s

 

temperature

: 39

: 40

: 60

: 100

Central heating 

return 

 

temperature

: 0

: 28

: 48

: 100

CAUTION:

 In case the regulator operates as a central heating circulation pump 

relay, the comfort and economical temperatures should be adjusted to 20 °C, 

programmes  should  not  be  adjusted  or  economical  temperature  should  be 

switched on for all days and periods. When the temperature falls beneath 39 °C 

there is a complete switch off.

expected 

temperature

boiler

reference 

temperature

L

N

boiler’s

temperature

slow

 

-burning 

central 

heating 

boiler

central heating 

return

temperature

L

N

radiator

Weather regulator switch on/off (electric heaters, gas/oil boilers, air-conditioners)

  Press OK in the main menu to choose 

 option.

  In submenu use cursors 

 to choose 

; press OK to confirm; go 

to main menu.

  In main menu use cursors 

 to choose 

 option and press OK 

to confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to 

confirm to enter option adjustment.

  In submenu 

 use cursors 

 to choose curve’s type from the 

range from 0,2 to 1,8; press OK to confirm.

0,8  is  enough  for  well  insulated  homes,  however  the  typical  curve  for 

poor insulated homes is 1,0 to 1,2 and 1,6 for badly insulated homes. For 

homes with floor heating 0,2 or 0,6 is enough. Press OK to confirm.
It is recommended to adjust own heating curve points because of air-con

-

ditioning. The expected temperature sensor should be mounted in a way 

to measure the devices’ temperature (heater and air-conditioner) or room’s 

temperature with its individual heating curve adjustment.

Weather regulator with mixing valve

  Press OK in the main menu to choose 

 option.

  In submenu 

 use cursors 

 to choose 

; press OK to confirm.

  In submenu 

 use cursors 

 to choose time of full valve opening from 

15 sec to 1200 sec; this time range should be given in a valve manual by 

the producer as it is unavoidable to operate properly. In case the time range 

is not given by the producer, it can be measured by means of a stopwatch: 

measuring starts with „opening” signal and finishes with full valve opening. 

In case relay time do not precisely correspond with valve opening time, then 

the nearest time once increased should be given; press OK to confirm; go to 

main menu.

  In main menu use cursors 

 to choose 

; option and press OK to 

confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to con

-

firm to enter option adjustment.

  In submenu 

 use cursors 

 to choose curve’s type from the range 

from 0,2 to 1,8. 

0,8 is enough for well insulated homes, however the typical curve for poor insu

-

lated homes is 1,0 to 1,2 and 1,6 for badly insulated homes. For homes with floor 

heating 0,2 or 0,6 is enough. Press OK to confirm. It is possible to adjust own 

heating curve in 

 option.

Circulation pump relay

The reference temperature sensor should be mounted where hot water escapes 

or at the top of a container (boiler) so it has the best contact with the temperature 

of hot water for use. The expected temperature sensor should be mounted just 

behind the last point of water drawing so it has the best contact with hot water for 

use that returns to the container.

  Press OK in the main menu to choose 

 option.

  In submenu use cursors 

 to choose 

; press OK to confirm; go to 

main menu.

  In  main  menu  use  cursors 

  to  choose 

  option  and  press  OK  to 

confirm.

  In submenu 

 use cursors 

 to choose 

 and press OK to con

-

firm.

  In 

 option use cursors 

 to choose values for curve’s points accord

-

ing to the below presented example; press OK to confirm.

When the container reaches up to 40 ˚C the circulation pump should be switched 

on manually for about 2 to 5 minutes; temperature should be measured in the point 

where the expected temperature sensor is built - just behind the last water drawing 

(economically recommended) or in the point just before returning to the container.

The container’s temperature should be increased by 10 ˚C and the whole experi

-

ment should start from the beginning. All the points should be written down in a 

table. An exemplary table is presented below.

Container’s temp.

: 40

: 45

: 50

: 55

Circulation pipe 

temp.

: 35

: 37

: 40

: 43

CAUTION: 

If the regulator operates as a circulation pump relay for hot water, the 

comfort and economical temperature should be adjusted to 20 ˚C, and time pro

-

gramme must be adjusted without economical temperature, complete pump switch 

off is when there is an antifreeze temperature cycle in the programme. An anti

-

freeze temperature option can preserve the distant parts of pipes from freezing.

expected 

temperature

boiler

reference 

temperature

L

N

expected 

temperature

container

reference

temperature

L

N

L

N

electric

heater

air-conditioner

reference 

temperature

expected 

temperature