DESCRIPTION
MAIN MENU
TIME ADJUSTMENT
DATE ADJUSTMENT
SUMMER/WINTER TIME ADJUSTMENT
OPERATING MODE ChANGE (AUTOMATIC, MANUAL)
REGULATOR FUNCTION ADJUSTMENT
- current time adjustment; press OK to enter;
HOUR - use cursor
use cursor to choose the required hour, you can adjust in format 1-24 or 1-12 (AM) and 1-12 (PM), press OK to confirm;
MINUTES
- use cursor
to choose the required minutes value, press OK to confirm;
Confirming the minutes value causes seconds reset and time adjustment window entry.
There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments.
- current date adjustment; press OK to enter;
YEAR
- use cursor
to choose the required year, press OK to confirm, adjustment range from 2000 to 2099;
MONTH - use cursor
to choose the required month, press OK to confirm;
DAY - use cursor
to choose the required day of the month, press OK to confirm; the system is equipped with protection against wrong insertion of days for a
particular month ( it includes leap years), and it automatically counts the day of the week on the basis of the adjusted date;
Confirming the command allows to enter date adjustment window and current summer/winter time adjustment window if the option
is activated.
There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments.
Window
- days of the week
- automatic mode
- manual mode
- winter time
- current date
- current time
Window
- automatic mode, - manual mode
- reference temperature
- anti frozen temperature
- comfort temperature
- economical temperature
- calculated temperature
- expected temperature (T2)
Different windows:
- day,
- year
- automatic,
- user
- on/off
or
- T1 or T2 sensor error
Window
- adjusted temperature
- reference temperature (T1)
Displayed elements and messages description
Use cursor to change from main window to current time and date window
or use cursor to choose calculated and expected temperature window
.
After 15 sec there is an automatic return.
Choose OK to enter menu; use cursor
to choose
options.
Function Description
PROGRAMMES ASSIGNING
TEMPERATURE ADJUSTMENT
PROGRAMME ADJUSTMENT
CURRENT TIME ADJUSTMENT
CURRENT DATE ADJUSTMENT
SUMMER/WINTER TIME ADJUSTMENT
REGULATOR FUNCTION ADJUSTMENT
SENSOR ADAPTATION ADJUSTMENT
HEATING CURVE VALUE ADJUSTMENT
Push buttons description
• main window - automatic mode entry;
• different windows - one level higher entry without saving the inserted data;
• main window - manual mode entry;
• different windows - one level higher entry without saving the inserted data;
• main window - main menu entry;
• different windows - submenu entry or adjusted data saving;
• toggle between menu windows or increase/decrease options of the ad
-
justed value
.
Arrow up blinks: opening - enter signal to open the valve.
Arrow up is on: switch on the heater or open the central heating
circulation valve.
Arrow down blinks: closing - enter signal to close the valve.
Arrow down is on: switch on the cooling device or open the ice water
valve.
- choosing one out of two modes by means of which the summer/winter time switching follows:
- the switching follows automat
-
ically the last Sunday of March at 2:00 AM from winter time to summer time, and last Sunday of October at 3:00 AM from summer time to winter time,
- the user chooses between winter/summer time; press OK to enter;
MODE ADJUSTMENT - use cursor
to choose the required mode
or
and press OK to confirm; after choosing
mode, the clock automatically
adjusts to summer or winter time in reference to the adjusted date; choosing
mode allows to enter the next window;
Use cursors
o choose summer/winter time where stands for winter time and stands for summer time, if there was a cursor change the system changes
current time by adding or distracting 1 hour, press OK to confirm;
Confirming the choice the system enters summer/winter time change window.
There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments.
Regulator in
function:
Jf the regulator is in manual mode pressing (holding)
cursor causes the heating relay switches on (the relay
short circuits contacts 11-14) - symbols and
light
, when the cursor is released the relay is switched off and
and symbols fade . Another pressing (holding) cur
-
sor lights both and
, and switches on the relay - the
relay is switched on only when pressing the cursor
.
If the regulator is in manual mode pressing (holding)
cursor causes the cooling relay is switched on (the relay
short circuits contacts 11-12) - symbols light , when the
cursor is released the relay is switched off and and
symbols fade . Another pressing (holding) cursor lights
and , and switches on the relay - the relay is switched
on only when pressing the cursor
.
Regulator in
function:
If the regulator is in manual mode pressing (holding) cursor causes the opening valve
relay switches on (the relay short circuits contacts 11-14) - arrow lights; when the cursor
is released the relay is switched off and ights, it symbolizes the previous meter status
. Another pressing (holding) cursor lights the arrow and switches on the relay - when
the cursor is released, the arrow fades and the relay switches off - the relay is switched
on only when pressing the cursor
.
If the regulator is in manual mode pressing cursor causes the closing valve relay switch
-
es on (the relay short circuits contacts 21-24) - arrow lights; when the cursor
is released
the relay is switched off;
it symbolizes the previous meter status . Another pressing
(holding) cursor lights the arrow and switches on the relay - when the cursor is released,
the arrow fades and the relay switches off - the relay is switched on only when pressing
the cursor
.
If the system is in one of the two mentioned manual modes , press the cursor to return to automatic mode
.
MANUAL MODE CHANGE - if the system is in the main window and in automatic mode pressing the button causes the system switches into manual mode,
with a possibility of direct device switch on/switch off or valve control.
There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments.
- regulator function adjustment. Choose
to
control devices on the basis of on/off (heater, air conditoner,
boiler, temperature control by means of two-way valve), and
choose
to control temperature by means of three-way
or four-way blending valve, press OK to review and to edit;
Use cursors
to choose functions
or
, press
OK to confirm; choose
function to return to
menu; next choose
to adjust function parameters:
- regulator intensification (dynamics); press OK to enter;
use cursors
to adjust the value in the range of 1 to 10;
press OK to confirm.
- full valve opening time; press OK to enter; use cursors
to adjust the value in the range of 15 to 1200 seconds;
press OK to confirm.
- time between following measurements (so called inte
-
grator time); press OK to enter; use cursors
to adjust
the value in the range of 5 to 600 seconds;
it means
time equals 1/5 ; press OK to confirm.