APPEARANCE

CEChy

TEChNICAL DATA

DESCRIPTION

RTM-30

Power supply terminals: A1, A2

Input rated voltage: 85 ÷ 265 V AC

Nominal frequency: 50 / 60 Hz

Rated power consumption: < 1,5 W

Temperature sensor terminals: T1 (t reference), T2 (t expected)

Temperature sensor type: KTY 81-210

Temperature regulation adjustment range: 5 ÷ 95 

o

C

Hysteresis: +/- 0,5 

o

C

Relay output (supply) terminals: 11, 12, 14, 21, 22, 24

Receiver switch on indicator:

LCD

LCD display backlight: amber

Output relay parameters: 2NO/NC 16A / 250V AC1 4000VA

Number of terminal clamps: 12

Section of connecting cables: 0,2 ÷ 2,50 mm

2

Regulator ambient temperature range: -20 ÷ 60 

o

C

Sensor ambient temperature range: -20 ÷ 90 

o

C

Operating mode: freely

Mounting: rail TH35 (acc to PN-EN 60715)

Protection degree: IP20 (PN-EN 60529)

Protection level:

II

Overvoltage category:

II

Pollution degree: 2

Dimensions: double-modular (35 mm) 90x35x66 mm

Weight: 0,160 kg

Reference standards: PN-EN 60730-1; PN-EN 60730-2-7

PN-EN 61000-4-2,3,4,5,6,11

●  Temperature level regulation in the range 

of 5 ÷ 95 °C,

●  two external temperature sensors,

●  LCD display and keypad,

●  output receiver’s temperature regulation in 

accordance with the reference temperatu

-

re,

●  output receiver’s temperature regulation in 

accordance with temperature differences,

●  heating sources economical regulation 

gives enormous savings during heating 

period,

●  simultaneous regulation possibilities of 

cooling and heating sources,

●  temperature regulation possibility by 

means of blending valves,

●  replacing possibility of a reference tempe

-

rature regulator with a standard resistor,

●  double-modular casing with a shield,

●  TH-35 DIN rail installation,

●  two output relays of max 16A capacity.

The  temperature  regulator  operation  is 

based on heating/regulation curve which we  

obtain  by  means  of  choosing  points  inclu

-

ding both the expected temperature and the 

reference temperature, by choosing a ready 

made curve or by changing options for room 

regulation. The regulator preserves the tem

-

perature with the heating source suitable for 

the reference point (e.g outer or inner tem

-

perature),  chosen  during  configuration  pha

-

se. Regulation algorithm causes the heating 

costs lower and the same gives full comfort of 

room and weather regulation. The regulator 

uses two sensors for proper operation. There 

is also a possibility of extending its existing 

connection cable up to 50 m with a cable sec

-

tion of 0,2÷2,5 mm

2

. The reference tempera

-

ture sensor can be replaced with a standard 

resistor, which causes one sensor operation 

as in the standard temperature regulation. 

The regulator is a perfect solution in eve

-

ry situation we want to be sure there was a 

full factor ciculation e.g.: cooling systems or 

heating systems, but also in situations where 

suitable temperature difference is necessary 

for preserving best conditions with maximum 

low costs e.g.: hot water circulation. Repla

-

cing one temperature sensor with a standard 

resistor has the effect of constant regulation 

around one point in accordance with the ad

-

justed curve, close to the chosen points.

Replacing one temperature sensor with a 

potentiometer with similar functions has the 

effect of changing a universal regulator into a 

standard temperature regulator with differen

-

ce  regulation  possibility  by  means  of  curve 

and hysterisis. It allows to control, e.g., the 

heating source in such a way its temperature 

is higher than the adjusted one including dif

-

ference corresponding e.g. the ambient tem

-

perature loss through windows, etc.

VER. 002_20.05.2010

LCD displa

y

C

ont

r

o

l pus

h

 

b

u

tton

s

Temperature sensor clamps

(T1, T2)

Power supply
terminals (A1, A2)

Relay output (supply) terminals 

(12, 11, 14, 24, 21, 22)

The symbol stands for selective 

collection of electrical and 

electronical devices. It is 

forbidden to place the used 

devices with other waste.

CONNECTION

MOUNTING

APPLICATION

DIMENSIONS

FAMILy PRODUCT

RTM-30 temperature regulator belongs 

to RTM family product.

1.  Disconnect power supply by the pha

-

se  fuse,  the  circuit-breaker    or  the 

switch- disconnector combined to the 

proper circuit.

2.  Check if there is no voltage on con

-

nection cables by means of a special 

measure equipment.

3.  Install the RTM-30 on the TH-35 DIN 

rail in the switchboard.

4.  Connect    the  cables  with  the  termi

-

nals in accordance with the installing 

diagram.

5.  Switch on the power supply from the 

mains.

INNER DIAGRAM

Outer temperature sensor

RTM-30 regulator

Room temperature sensor

Floor heating

Air-conditioner

L

N

Heating

Cooling

Device type:

01 - basic

02 - LCD display

03 - weather with LCD 

display

Device symbol

RTM - xx

L N

μC

KLA
W

.

LCD

ZAS.

A/C

A/C

RTC

WARRANTy CARD

There is 24 months guarantee on the product

Salesman stamp and signature, date of sale

1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product.

2. The manufacturer’s guarantee does not cover any of the following actions:

a) mechanical damage during transport, loading / unloading or under other circumstances,

b) damage caused by incorrect product mounting or misuse,

c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices 

needed for the product functioning, 

d)  damage caused by Act of God or any other incidents independent of the manufacturer.

3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J.

4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation.

5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement  or money return. 

6. The manufacturer’s guarantee is valid in the Republic of Poland.

7. The PURCHASER’s  statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or 

otherwise are not affected by this warranty.

Отзывы: