RTM-20 TEMPERATURE REGULATOR
INSTRUCTION MANUAL
Zak
ł
ad Mechaniki i Elektroniki
ZAMEL
sp.j.
J.W. Dzida, K.
Ł
odzi
ń
ska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com
, e-mail: [email protected]
APPEARANCE
FEATURES
TECHNICAL DATA
DESCRIPTION
RTM-20
Power terminals : A1, A2
Rated voltage: 230 V~
Rated voltage tolerance: -15 ÷ +10 %
Rated frequency: 50 / 60 Hz
Rated power consumption: 2 W / 14 VA
NTC sensor terminals: NTC
Input terminals: IN, IN
Temperature adjustment range: 5 ÷ 60
o
C
Hysteresis: ± 1
o
C
Relay terminals: 12, 12, 11, 11, 14, 14
Load indicator: LCD
Colour of LCD panel lighting: amber
Parameters of transmitter contacts: 16A NO/NC 4000 VA AC1
Number of terminating clamps: 12
Intersection of terminating conductors: 0,2 ÷ 2,50 mm
2
Temperature of work: -20 ÷ 60
o
C
Temperatura pracy sondy: -20 ÷ 90
o
C
Position of work: any
Fixing of casing: TH 35 rail (EN 60715)
Level of protection of casing: IP20 (EN 60529)
Protectivity class: II
Overvoltage category: II
Level of pollution: 2
Measurements: two-module (35 mm) 90x35x66 mm
Weight: 130 g
Compatibility with norms: EN 60730-1; PN-EN 60730-2-7
EN 61000-4-2,3,4,5,6,11
●
Temperature control within the range
of 5°C ÷ 60°C,
●
External NTC-03 probe,
●
Led d keyboard,
●
Load control in dependence of am-
bient temperature,
●
Double-module casing with a protec-
tion flap,
●
Mounted on TH 35 rail,
●
Relay output, 16 A maximum load.
The RTM-20 temperature digital regulator
is designed for load control (e.g. heaters,
floor heating systems) in dependence of
ambient temperature near an external
NTC sensor. It is possible to control
temperature within the range of +5°C ÷
+60°C.
The external NTC-03 probe is needed
for a correct device operation. The is
not part of the set and it is necessary to
purchase it separately. The probe lead is
3 m in length. It is possible to extend it up
to 50 m with 0,2 ÷ 2,5 mm
2
lead. Do not
join the probes.
CAUTION:
Before installing
the device in the
switchboard
or starting the
system operation
in order to
programme it,
the battery security
separator should
be removed
against
discharging.
The device should be con-
nected to a single-phase
system according to current
standards. The device con-
nections will be described in
this manual. Only quali
fi
ed
electricians are allowed to
mount, connect and adjust the module. It is
necessary to read this manual before the de-
vice mounting. Do not disassembly the device
casing or you will lose any warranty rights and
expose yourself to the electric shock hazard.
Before mounting operation make sure of di-
sconnecting the connection wires from the
electric network. Use a cross-head screwdri-
ver of 3.5 mm diameter to mount the device.
The regulator should be carried, stored and
used in an appropriate way. Do not mount the
device in case of any regulator parts lack, da-
mage or deformation. In case of malfunction
please notify the manufacturer.
CAUTION
Display
Relay output terminals
(12, 12, 11, 11, 14, 14)
Control buttons
NTC terminals
(NTC)
Power terminals
(A1, A2)
Trigger terminals
(IN, IN)
VER. 004_31.03.2010
DESCRIPTION
MAIN MENU
DATE SETTING
- Current date setting; entry after pressing OK;
YEAR - choose adequate year with cursors
con
fi
rm with OK, range of
years: 2000÷2099;
MONTH - choose month with cursors
con
fi
rm with OK;
DAY - choose day with cursors
con
fi
rm with OK; the system has a protec-
tion against introducing incorrect parameter of a day for a given month ( it
takes into account leap years and it automatically calculates the day of the
week on the basis of an arranged date);
Con
fi
rmation causes movement to a date setting window and set-up of cur-
rent summer/ winter time - if the option
is arranged.
It is possible to exit every sub- menu window in any moment without
saving settings by pressing the button or .
Description of displayed
fi
elds and messages
From window no. it is possible to enter the info window (time and date) no. after
pressing the cursor or . The window will be closed after 15 seconds automatically.
Window
Window
,
- relay state
- days of week
- automatic mode
- relay state
- manual mode
- automatic mode
- output temperature
- manual mode
- non-freeze temperature
- winter time
- comfort temperature
- current date
- econo temperature
- current time
- temperature setting
- actual temperature
Other windows:
- day
- year
- automatic
- user’s
- ON/OFF
- NTC probe error (short circuit or break)
Button description
• the main window – entering the automatic op mode;
• ther windows – exit to a higher level without saving changes
entered;
• the main window – entering the manual op mode or the tem-
perature setting changing, if the manual mode set previously;
• other windows - exit to a higher level without saving
changes;
• the main window – entering the main menu;
• other windows – entering a submenu or the set value ac-
knowledgement;
• toggle between menu windows / options or the set value
increase / decrease
.
Enter the menu by pressing OK in the main window;
scroll the menu by means of the following cursors
.
Function Description
PROGRAM ASSIGNING
TEMPERATURE
SETTING
PROGRAM
SETTING
CURRENT
TIME
SETTING
CURRENT DATE SETTING
SUMMER / WINTER TIME SETTING
EXTERNAL OUTPUT SETTING
SENSOR
ADAPTATION
SETTING
RTM - 20
TIME SETTING
WINTER / SUMMER TIME SETTING
OPERATING MODE CHANGE (AUTOMATIC, MANUAL)
- setting the current clock time; entry after pressing
OK;
HOUR- choose adequate hour with cursor
which you can
set in 1-24 or 1-12 (AM) and 1-12 (PM)format; con
fi
rm
with OK;
MINUTES - choose adequate parameter of minutes with cur-
sors
con
fi
rm with OK;
Con
fi
rmation of the parameter of minutes causes simultane-
ous nulli
fi
cation of the parameter of seconds and movement to
the window of time setting.
It is possible to exit every sub- menu window in any moment
without saving settings by pressing the button or .
- choice of one of the two modes in which switching be-
tween winter and summer season time will occur.
- switching
will take place in an automatic way, on the last Sunday of March, at
2.00 (for summer time) and on the last Sunday of October, at 3.00
(for winter time),
- a user chooses between winter/ summer
time, entry after pressing OK;
setting the mode - choose mode
or
with cursors
, con
fi
rm with OK; after choosing the mode
, the clock au-
tomatically sets the time as winter or summer one, depending on
the arranged date; after choosing the mode
you go to another
window;
Choose time for winter/ summer one with cursors
where is
winter time and is summer time, if change of marker has hap-
pened the system will change the current time by adding or sub-
tracting 1 hour, con
fi
rm the operation with OK;
After choosing the system moves to winter/ summer time shift win-
dow.
It is possible to exit every sub- menu window in any moment
without saving settings by pressing the button or .
MANUAL OP MODE TOGGLE - if the main window is open
and the device is in the automatic op mode , pressing the
key will force the unit to toggle into the manual op
mode with active non-freeze temperature ; succes-
sive pressing the key will force the manual op mode
changeover as follows:
non-freeze temperature;
comfort temperature;
econo temperature;
output temperature.
If the unit is in one of the mentioned manual op modes
, pressing the key will force return to the automatic
mode .