APPEARANCE

FEATURES

TECHNICAL DATA

DESCRIPTION

RTM-20

Power terminals : A1, A2

Rated voltage: 230 V~

Rated voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60 Hz

Rated power consumption: 2 W / 14 VA

NTC sensor terminals: NTC

Input terminals: IN, IN

Temperature adjustment range: 5 ÷ 60 

o

C

Hysteresis: ± 1 

o

C

Relay terminals: 12, 12, 11, 11, 14, 14

Load  indicator: LCD

Colour of LCD panel lighting: amber

Parameters of transmitter contacts: 16A NO/NC 4000 VA AC1

Number of terminating clamps: 12

Intersection of terminating conductors: 0,2 ÷ 2,50 mm

2

Temperature of work: -20 ÷ 60 

o

C

Temperatura pracy sondy: -20 ÷ 90 

o

C

Position of work: any

Fixing of casing: TH 35 rail (EN 60715)

Level of protection of casing: IP20 (EN 60529)

Protectivity class: II

Overvoltage category: II

Level of pollution: 2

Measurements: two-module (35 mm) 90x35x66 mm

Weight: 130 g

Compatibility with norms: EN 60730-1; PN-EN 60730-2-7

EN 61000-4-2,3,4,5,6,11

  Temperature control within the range 

of 5°C ÷ 60°C,

  External NTC-03 probe,

  Led d keyboard,

  Load control in dependence of am-

bient temperature,

  Double-module casing with a protec-

tion flap,

  Mounted on TH 35 rail,

  Relay output, 16 A maximum load.

The RTM-20 temperature digital regulator 
is designed for load control (e.g. heaters, 
floor heating systems) in dependence of 
ambient temperature near an external 
NTC sensor. It is possible to control 
temperature within the range of +5°C ÷ 
+60°C.
The external NTC-03 probe is needed 
for a correct device operation.  The is 
not part of  the set and it is necessary to 
purchase it separately.  The probe lead is 
3 m in length. It is possible to extend it up 
to 50 m with 0,2 ÷ 2,5 mm

2

 lead. Do not 

join the probes.

CAUTION: 
Before installing 
the device in the 
switchboard 
or starting the 
system operation 
in order to 
programme it, 
the battery security 
separator should 
be removed 
against 
discharging.

The  device  should  be  con-
nected to a single-phase 
system according to current 
standards. The device con-
nections will be described in 
this manual. Only quali

fi

 ed 

electricians are allowed to 

mount, connect and adjust the module. It is 
necessary to read this manual before the de-
vice mounting.  Do not disassembly the device 
casing or you will lose any warranty rights and 
expose yourself to the electric shock hazard. 
Before  mounting  operation  make  sure  of    di-
sconnecting the connection wires from the 
electric network.  Use a cross-head screwdri-
ver of 3.5 mm diameter to mount the device. 
The regulator should be carried, stored and 
used in an appropriate way. Do not mount the 
device in case of  any regulator parts lack, da-
mage or deformation.  In case of malfunction 
please notify the manufacturer.

CAUTION

Display

Relay output terminals 
(12, 12, 11, 11, 14, 14)

Control buttons

NTC terminals

(NTC)

Power terminals
(A1, A2)

Trigger terminals

(IN, IN)

VER. 004_31.03.2010

DESCRIPTION

MAIN MENU

DATE SETTING

 

 - Current date setting; entry after pressing OK;

 YEAR - choose adequate year with cursors 

 con

fi

 rm with OK, range of 

years: 2000÷2099;

 MONTH - choose month with cursors 

 con

fi

 rm with OK;

 DAY - choose day with cursors 

 con

fi

 rm with OK; the system has a protec-

tion against introducing incorrect parameter of a day for a given month ( it 
takes into account leap years and it automatically calculates the day of the 
week on the basis of an arranged date);

 Con

fi

 rmation causes movement to a date setting window and set-up of cur-

rent summer/ winter time - if the option 

 is arranged.

It is possible to exit every sub- menu window in any moment without 
saving settings by pressing the button   or  .

Description of displayed 

fi

 elds and messages

From  window no.   it is possible to enter the info window (time and date)  no.   after 
pressing the cursor    or  . The window will be closed after 15 seconds automatically.
Window    

 

 

Window 

 

 

 - relay state 

  

 

 

- days of week

 - automatic mode   

 

  

 - relay state

 - manual mode 

 

 

    - automatic mode 

 - output temperature 

 

    - manual mode 

 - non-freeze temperature 

 

    - winter time

 - comfort temperature 

 

  

 - current date

- econo temperature 

 

  

 - current time

 - temperature setting

 - actual temperature

Other windows:

 

- day 

 - year

 - automatic

 - user’s

 - ON/OFF

 - NTC probe error (short circuit or break)

Button description

   

• the main window – entering the automatic op mode;

  

• ther windows – exit to a higher level without saving changes 
entered;

   

• the main window – entering the manual op mode or the tem-
perature setting changing, if the manual mode set previously;

  

• other windows - exit to a higher level without saving 
changes;

    • the main window – entering the main menu;
  

• other windows – entering a submenu or the set value ac-
knowledgement;

 

  • toggle between menu windows / options or the set value 

increase / decrease

.

Enter the menu by pressing OK in the main window;

scroll the menu by means of the following cursors 

.

 Function Description

 

 

PROGRAM ASSIGNING

 

 TEMPERATURE 

SETTING

 

 PROGRAM 

SETTING

 

 CURRENT 

TIME 

SETTING

 

 

CURRENT DATE SETTING

 

 

SUMMER / WINTER TIME SETTING

 

 

EXTERNAL OUTPUT SETTING

 

 SENSOR 

ADAPTATION 

SETTING

RTM - 20

TIME SETTING

WINTER / SUMMER TIME SETTING

OPERATING MODE CHANGE (AUTOMATIC, MANUAL)

 

 - setting the current clock time; entry after pressing 

OK;

 HOUR- choose adequate hour with cursor 

 which you can 

set in 1-24   or 1-12   (AM) and 1-12   (PM)format; con

fi

 rm 

with OK;

 MINUTES - choose adequate parameter of minutes with cur-

sors 

 con

fi

 rm with OK;

 Con

fi

 rmation of the parameter of minutes causes simultane-

ous nulli

fi

 cation of the parameter of seconds and movement to 

the window of time setting.

It is possible to exit every sub- menu window in any moment 
without saving settings by pressing the button   or  .

 

 - choice of one of the two modes in which switching be-

tween winter and summer season time will occur. 

 - switching 

will take place in an automatic way, on the last Sunday of March, at 

2.00 (for summer time) and on the last Sunday of October, at 3.00 

(for winter time), 

 - a user chooses between winter/ summer 

time, entry after pressing OK;

   setting the mode - choose mode 

 or 

 with cursors 

, con

fi

 rm with OK; after choosing the mode 

, the clock au-

tomatically sets the time as winter or summer one, depending on 

the arranged date; after choosing the mode 

 you go to another 

window;

 Choose time for winter/ summer one with cursors 

 where   is 

winter time and   is summer time, if change of marker has hap-

pened the system will change the current time by adding or sub-

tracting 1 hour, con

fi

 rm the operation with OK;

 After choosing the system moves to winter/ summer time shift win-

dow. 

It is possible to exit every sub- menu window in any moment 
without saving settings by pressing the button   or  .

 MANUAL OP MODE TOGGLE  -  if the main window is open 

and the device is in the automatic op mode  , pressing the 
key    will force the unit to toggle  into the manual op 
mode with active non-freeze temperature  ; succes-
sive pressing the key   will force the manual op mode 
changeover as follows: 

 non-freeze temperature;
 comfort temperature;
 econo temperature;
 output temperature.

If the unit is in one of the mentioned manual op modes 

, pressing the key   will force return  to the automatic 

mode  .