ASSEMBLY, OPERATION

1. Disconnect the safety power supply 

circuit, the overcurrent circuit breaker 

or the isolating switch connected to the 

corresponding water circuit.

2. Check voltage-free condition on the 

supply cables with proper instru-

ment.

3. Install LEM-04 in the switchboard on 

TH 35 (DIN) rail.

4. Connect the wires to the terminals in 

accordance with the wiring diagram.

5. Switch on the power supply.

Current  flowing  throught  the  device 

causes that generated pulses are propor-

tional to amount of drawn electric energy 

(2000 pulses per kWh). A flashing LED in-

dicates current consumption and the fact 

that the device is measuring. The value 

can be read from segment LCD. The 

digits after the decimal point indicate the 

hundredths of 0.01 kWh (10 Wh).

NOTES:

•  When using pulse input (terminals 

20, 21) it is necessary to apply addi-

tional supply voltage within a range 

5 ÷ 27 V DC.

•  It is recommended to use an addi-

tional  resistor  R  (470  Ω  ÷  1  kΩ)  to 

limit the value of current.

•  Changing the power supply polarity 

may damage the indicator’s pulse 

output.

•  If there is no connection then the 

metering device should not be con-

nected to pulse output of the supply 

system.

CONNECTION

INTERNAL DIAGRAM

LEM-04 device used as an additional electricity meter in a house inhabited by two 

families

WARRANTY CARD

Manufacturer provides a 24-month warranty

Seller’s stamp and signature, date of sale

1. ZAMEL Sp. z o.o. shall offer a 24-month warranty on the products sold.

2. The warranty provided by ZAMEL Sp. z o.o. shall not cover:

a) mechanical damage caused during transport, loading/unloading or in other circumstances,

b) damage caused by incorrect installation or operation of products manufactured by ZAMEL Sp. z o.o.,

c) damage resulting from any changes made by the BUYER or third parties in the products sold or equipment necessary for the 

proper operation of the products sold,

d) damage resulting from force majeure or other fortuitous events for which ZAMEL Sp. z o.o. is not liable.

3. Any warranty claims shall be made by the BUYER at the point of sale or to ZAMEL z o.o. in writing after defects have been identi-

fied.

4. ZAMEL Sp. z o.o. undertakes to handle complaints in accordance with the applicable provisions of Polish law.

5. The choice of the form of complain resolution, e.g. replacement of a product with a product free from defects, repair, or reimburse-

ment of money, shall lie with ZAMEL Sp. z o.o.

6. The warranty does not exclude, limit, or suspend BUYER’s rights under the statutory warranty for defects in the item sold.

MEASURED 

CIRCUIT

ADDITIONAL 

COUNTING 

DEVICE

R

(470 Ω ÷ 1 kΩ)

5 ÷ 27 V DC

PRIMARY 

METER

ELECTRICAL 

INSTALLATION 

GROUND

FLOOR

ELECTRICAL 

INSTALLATION 

FLOOR

L

OUT

L

IN

4

20
21

1

6

3

N

Отзывы: