ELECTRICITY METER LEM-04
DIGITAL - SINGLE-PHASE
USER’S MANUAL
ZAMEL
Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamel.com
, e-mail: [email protected]
lem-04_inst_ext_gb | 10.02.21
FEATURES
TECHNICAL DATA
DESCRIPTION
APPEARANCE
LEM-04
Power supply terminals: line L: 1 (L
IN
), 3 (L
OUT
); line N: 4, 6
Reference voltage: 230 V AC
Voltage tolerance: -15 ÷ +10 %
Rated frequency: 50 / 60 Hz
Base / maximum current: 5 A / 45 A
Minimum current: 0,4% of base current (25 mA)
Meter own consumption: 10 VA / 2 W
Accuracy of measurement (IEC61036): class B
Display: counter 5+2 digits
Indication for pulse counting: red LED
Pulse output SO+ SO-: type OC: 20(+), 21(-)
Connection voltage SO+ SO-: 5 ÷ 27 V DC
SO+ SO- connection current: < 27 mA
SO+ SO- constant: 2000 pulses per kWh
Pulse time SO+ SO-: 90 ms
Number of connection terminals: 6
Cross-section of connection cables: 0,2 ÷ 6 mm
2
Operating temperature: -10 ÷ +50
o
C
Enclosure mounting: TH 35 rail (according to EN 60715)
Enclosure IP rating: IP51 (PN-EN 60529)
Overvoltage category: II
Contamination degree: 2
Dimensions: single-module enclosure
Weight: 0,100 kg
Compliance with standards: PN-EN 62094-1; PN-EN 61000-4-2,3,4,5,6,11
● Optical indication for pulse counting,
● LCD display,
● additional pulse output,
● sealable terminal covers,
● single-module housing,
● Installation on TH 35 rail.
LEM-04 device is a single-phase
electricity meter, which can be used as
a electricity sub-meter for single-phase
AC circuit. Measurement of electricity
consumption is signalled by LED and its
value is indicated on LCD. The meter is
also equipped with pulse output allowing
connecting an additional counting device.
To protect the device against the illegal
power consumption LEM-04 is protected
with plastic enclosures on the terminals,
which can be sealed.
The device should be con-
nected to a one-phase network
in accordance with legally bind-
ing standards. The connection
method is described in this
manual. Any activities related
to installation, connection, and adjustment
should be performed by qualified electricians
who have read this user’s manual and famil-
iarised themselves with device functions. Re-
moving the enclosure voids the warranty and
poses a risk of electric shock. Before instal-
lation, make sure that there is no voltage on
connection cables. To install the device, use
a cross-head screwdriver with a diameter of
3.5 mm. The proper operation of the device
is affected by how the device is transported,
stored, and used. It is not advisable to install
the device in the following cases: lack of any
components, damage to or deformation of
the device. If the device operates improperly,
please contact the manufacturer.
NOTE
Do not dispose of this device together
with other waste! To avoid harmful effects
on the environment and human health,
the worn-out device should be stored
in designated areas. Electrical waste
from households may be handed over
to the waste collector established for
this purpose free of change and in any
amount, as well as to the store when
purchasing new equipment.
Terminal covers
Input L
IN
(1)
Output L
OUT
(3)
Indication for pulse counting
LCD display
Pulse (20), - (21)
Output N (6)
Input N (4)