ELECTRICITY METER LEM-04

DIGITAL - SINGLE-PHASE

 

USER’S MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

lem-04_inst_ext_gb | 10.02.21

FEATURES

TECHNICAL DATA

DESCRIPTION

APPEARANCE

LEM-04

Power supply terminals: line L: 1 (L

IN

), 3 (L

OUT

); line N: 4, 6

Reference voltage: 230 V AC

Voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60 Hz

Base / maximum current: 5 A / 45 A

Minimum current: 0,4% of base current (25 mA)

Meter own consumption: 10 VA / 2 W

Accuracy of measurement (IEC61036): class B

Display: counter 5+2 digits

Indication for pulse counting: red LED

Pulse output SO+ SO-: type OC: 20(+), 21(-)

Connection voltage SO+ SO-: 5 ÷ 27 V DC

SO+ SO- connection current: < 27 mA

SO+ SO- constant: 2000 pulses per kWh

Pulse time SO+ SO-: 90 ms

Number of connection terminals: 6

Cross-section of connection cables: 0,2 ÷ 6 mm

2

Operating temperature: -10 ÷ +50 

o

C

Enclosure mounting: TH 35 rail (according to EN 60715)

Enclosure IP rating: IP51 (PN-EN 60529)

Overvoltage category: II

Contamination degree: 2

Dimensions: single-module enclosure

Weight: 0,100 kg

Compliance with standards: PN-EN 62094-1; PN-EN 61000-4-2,3,4,5,6,11

●  Optical indication for pulse counting,

●  LCD display,

●  additional pulse output,

●  sealable terminal covers,

●  single-module housing,

●  Installation on TH 35 rail.

LEM-04 device is a single-phase 

electricity meter, which can be used as 

a electricity sub-meter for single-phase 

AC circuit. Measurement of electricity 

consumption is signalled by LED and its 

value is indicated on LCD. The meter is 

also equipped with pulse output allowing 

connecting an additional counting device. 

To protect the device against the illegal 

power consumption LEM-04 is protected 

with plastic enclosures on the terminals, 

which can be sealed.

The device should be con-

nected to a one-phase network 

in accordance with legally bind-

ing standards. The connection 

method is described in this 

manual. Any activities related 

to installation, connection, and adjustment 

should be performed by qualified electricians 

who have read this user’s manual and famil-

iarised themselves with device functions. Re-

moving the enclosure voids the warranty and 

poses a risk of electric shock. Before instal-

lation, make sure that there is no voltage on 

connection cables. To install the device, use 

a cross-head screwdriver with a diameter of 

3.5 mm. The proper operation of the device 

is affected by how the device is transported, 

stored, and used.  It is not advisable to install 

the device in the following cases: lack of any 

components, damage to or deformation of 

the device. If the device operates improperly, 

please contact the manufacturer.

NOTE

Do not dispose of this device together 

with other waste! To avoid harmful effects 

on the environment and human health, 

the worn-out device should be stored 

in designated areas. Electrical waste 

from households may be handed over 

to the waste collector established for 

this purpose free of change and in any 

amount, as well as to the store when 

purchasing new equipment.