9
EN
Never work when voltage is present on the luminaire.
WARNING – RISK OF ELECTRICAL SHOCK!
WARNING – DO NOT OPEN UNDER TENSION!
INSTALATION INSTRUCTION
ACQUEx LED-T8 luminaires are designed to provide lighting in a specific area and must
be installed by suitably trained and qualified, authorized personnel only and in accordance
with the requirements of current standards, specifically EN 60079-14.
Before installation, ensure that information specified on the luminaire marking label, in
particular the equipment protection level, ingress protection, gas and dust group,
ambient temperature and temperature class are suitable for the intended application.
The ACQUEx LED-T8 luminaires maximum ambient temperature (Ta), indicated in this
manual or/and in the UE-declaration of conformity must not be exceeded.
ACQUEx LED-T8 luminaires must be installed away from draughty areas to avoid
accumulation of electrostatic charges.
ACQUEX LED-T8 luminaires might be fix to the ceiling or the wall surface using
compatible accessories. It is the installer's responsibility to check if the selected
support and fixing system is compatible with the application. Further information is at
the end of the manual.
ELECTRICAL CONNECTION
Electrical connection to the ACQUEx LED-T8 luminaire is to be made at the push wire
terminal block inside the enclosure on push-in terminal block following instructions
included in the luminaire. Connection must be made by single core or multiwire cooper
cable terminated by ferule of 2.5mm
2
cross section.
Important Information Regarding Control gear (ECG)
Interference to the neutral conductor in a three-phase system may result in surge-
related damage in the lighting installation. Only open neutral conductor-disconnect
terminal when disconnected from power supply and close prior to switching back on.
Use mains cables for control inputs of dimmable ECG (DALI, etc.).
In case of the versions ET or ET+LV, once connected to an active source of power
supply, the luminaire will light up automatically.
In case of the versions ETDD or ETDD+LV, once connected to an active source power
supply, the regulation of the luminous flux is controlled by means of the protocol of
communication DALI.
WARNING – For ETDD version ambient temperature shall be check
according to max input wattage of the luminaire as indicated in the
Maximum Ambient Temperature table at the end of this document!
Содержание ACQUEx LED-T8