The instruction received immediately after the Load Event-Triggered Instruction (#30) command will be
the event-triggered instruction associated with the specified key event. Note that this next instruction will
not be executed by the T-JOY, but will be stored for execution whenever the corresponding key event is
detected. This instruction will also pass un-hindered to any units that may be downstream (away from the
computer) from the T-JOY. For this reason, we recommended disconnecting downstream units from the
joystick before loading or returning event-triggered instructions.
The following table shows the data value necessary
to select a particular key event with which to
associate the next instruction.
Key
Event 1
Event 2
Event 3
Event 4
1
11 12 13 14
2
21 22 23 24
3
31 32 33 34
4
41 42 43 44
5
51 52 53 54
The following table shows the default event-triggered instructions associated with each key event:
Key
Event
Key Event
Default Instruction
(Unit, Command, Data)
Description
1
1
11
(255, 255, 0)
-
1
2
12
(0, 23, 0)
Stop all units
1
3
13
(0, 1, 0)
Home all units
1
4
14
(255, 255, 0)
-
2
1
21
(1, 55, 0)
Echo the number 0
2
2
22
(1, 55, 1)
Echo the number 1
2
3
23
(1, 55, 2)
Echo the number 2
2
4
24
(1, 55, 3)
Echo the number 3
3
1
31
(255, 255, 0)
-
3
2
32
(0, 18, 0)
Go to stored position 0
3
3
33
(0, 16, 0)
Store current position 0
3
4
34
(255, 255, 0)
-
Page 17 of 32