Report OFF:
[Command Class Switch Binary, Switch Binary Report, Value
=0(0x00)]
Report ON:
[Command Class Switch Binary, Switch Binary Report, Value =
255(0xFF)]
1-2 BASIC_SET / SWITCH_BINARY_SET
Since PAN30 has two relay, all the loads attached to relay1 and relay2 will
turn on or off upon receipt of the following commands from a Z-Wave
Controller.
[Command Class Basic, Basic Set, Value = 1~99, 255(0xFF)]
: the load
attached to relay1 and relay2 turns on.
[Command Class Basic, Basic Set, Value = 0(0x00)]
: the load attached to
relay1 and relay2 turns off.
[Command Class Switch Binary, Switch Binary Set, Value = 1~99,
255(0xFF)]
: the load attached to relay1 and relay2 turns on.
[Command Class Switch Binary, Switch Binary Set, Value = 0(0x00)]
: the
load attached to relay1 and relay2 turns off.
1. Z-Wave’s Groups (Association Command Class Version 2)
The Switch can be set to send reports to the associated Z-Wave devices. It
supports groups which every group has five nodes support. Group1 is called
Lifeline which support SWITCH_BINARY_REPORT
、
METER_REPORT
、
NOTIFICATION_REPORT
、
INDICATOR_REPORT and
DEVICE_RESET_LOCALLY_NOTIFICATION.
For group 1, the Switch will report (1) ON/OFF status of Relay1 and Relay2 (2)
Instant Power Consumption (Watt) of Relay1 and Relay2 (3) Accumulated
Power Consumption (KWh) of Relay1 and Relay2 to Z-Wave Controller.
2-1 Auto report to Grouping 1 ~ 5(Maximum Node 5)
2-1-1 On/Off Event Report
When “on” or “off” state of relay1 or relay2 has been changed, it will send
Binary Switch Report to the nodes of Group1. The report value will be on
when relay1 or relay2 is on, it will be off when both relay1 and relay2 are off.
Binary Switch Report
ON:
[Command Class Switch Binary, Switch Binary Report, Value
=255(0xFF)]
OFF:
[Command Class Switch Binary, Switch Binary Report, Value =0(0x00)]
2-1-2 Instant Power Consumption vary over 5% report
When the power consumption of load vary over 5%, it will send Meter report
to the nodes of Group
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter Type =
0x01
,
Precision = 1
,
Scale = 0x02
,
Size = 4
,
Meter Value(W) ]