Electrical Connections and Wiring
Reference the panel control document in Appendix A for field wiring requirements.
CAUTION: All wiring should be performed by a licensed professional in accordance with local
electrical codes.
Power Supply:
Voltage:
Single Phase 115/230VAC 50/60Hz
Current:
0.55A/0.35A (115/230V)
Required Wire Size:
16AWG (1mm
2
)
Wire Terminal Torque:
4.4 lb-in (5 kgf-cm)
Wiring Overview:
Max RS-485 cable length between N-300 or N-400 and YZ Connect Box = 3960ft (1200m)
N-300 Modbus Settings
YZ connect uses the default Modbus settings:
Modbus RTU
Address = 1
Baud = 9600
Parity = None
N-400 Modbus Settings
YZ connect uses the default Modbus settings:
Modbus RTU
Address = 1
Baud = 19200
Parity = Even
Stop bits = 1