www.yz-connect.com
Page 13 of 25
GPS
Shows the location of the odorizer. Select Map or Satellite and Zoom etc. to adjust the view. GPS can
be turned off in the Hardware Parameters tab.
Hardware Parameters
An external Analog 4-20mA sensor can be connected as shown below and viewed in the “Snapshot”
screen at the bottom of “General Data” under the 4-20mA Customer Sensor heading. This could be
used to monitor a flow signal, odorant sensor etc. depending on the use case.
Setup:
1.
Add a hole for a NEMA 4X or IP67 rated cable gland in the YZ Connect box on the same side as
the Antenna cable glands (see below)
2.
Run the signal wire to the YZ connect box thru the new cable gland, connect to AIN1 and GND
3.
Setup the signal parameters in the Hardware Parameters tab
4.
Enter the “Sensor Minimum” and click save
5.
Enter the “Sensor Span” and click save
6.
To configure, enter the min value and span, click save and then click
.
Add hole for Analog input cable gland