S071-02

Wiring graph for instruments with dimension A1, B1,E1 and F1:

Wiring graph for D dimension(72X72mm)instruments: 

  

Wiring graph for D1/D2 dimension(48X48mm)instruments:

Note: 
1. After the connection of thermocouple with compensation wire and the cover of 

plastic panel, it cannot change with common wire. Pay attention to the correct 
connection of wire and lead. 

2.As CE requires, please use product that can stand over 2300V when controller is 

connected with extra Solid state relay. 

AHYS

Hysteresis

Avoid wrong frequent alarm caused by 

wrong value setting

0~200

2

AOP Alarm Output

assignment

AoP is to defi ne the place of HIAL,LoAL,

HdAL alarms like :

AOP = 

    0           4           0           3   

            LdAL   HdAL    LoAL   HIAL ;

Value 0~4."0" means never alarm,"1" 

and "2" represents the alarm outputs 

from AL1 and AL2 respectively. "3" 

and "4" represents the alarm outputs 

from AU1 and AU2 respectively. 

E.g. AOP=403 means HIAL alarm from 

AU1, HdAL from AU2.LoAL no alarm

0~444

Depends

on 

module

added

CtrL

Control mode

onoF:On-off control, used in normal 

case.

APld: high precision control PID mode.
nPld: 

Standard PID algorithm with anti-

integral-saturation function..

onoF/

APld

APld

Act

Dierect/

reverse 

acting 

function

rE:Reverse acting.Increase in measured 

variable causes a decrease in the 

output,such as heating control.

dr:Direct acting.Increase in measured 

variable causes an increase in the 

output,such as refrigerating control.

rEbA:Reverse acting with low limit 

alarm and deviation low alarm 

blocking at the beginning of power 

on.

drbA:Direct acting with high limit alarm 

and deviation high alarm blocking at 

the beginning of power on.

rE

Dr

rEbA

drbA

rE

P

Proportional

band

Proportional band in PID with unit

/F. 

Notes: normally use At to confi rm P, I, 

D and Ctl .But can set known correct 

value.

1~999

30

I

Time of 

Integral

Time of integral in PID.No integral 

effect when I=0 unit is 1 second

0~9999

Sec

100

d

Time of 

Derivative

Time of derivative in PID.No derivative 

effect when d=0

0~

999 .9

Sec

50.0

Ctl Control period

Small  value  can  improve  control 

accuracy. 

For SSR output, generally 0.5 to 3.0 

seconds.

For  Relay  output,  generally  15~40 

seconds, because small value will cause 

the frequent On-Off of mechanical 

switch and shorten its service life.  CtI 

is recommended to be 1/4 ~ 1/10 of 

derivative time. When control under 

on-off control,Ctl use as restart delay 

time affer off,for protect compressor 

application.

0.5~

120 Sec

2.0/20

CHYS

Control 

Hysteresis

CHY is used for on-off control, if PV 

> SV, output turns off; PV<SV-CHYS, 

output turns on.

0~200

2

InP

Input 

specifi cation

InP

Input 

spec

InP

Input 

spec

0

K

1

S

2

R

3

Spare

4

E

5

J

6

Spare

7

N

8-20

Spare

21

Pt100

0~21

0

dPt

Resolution

"0" means 1

or 1F, 

"0.0" means 0.1

/F

0/0.0

0.0

Scb

Input Shift

Scb  is  used  to  make  input  shift  to 

compensate the error produced by sensor 

or input signal. 

PV_after_compensation= PV_before_

compen Scb.

Note:normally set it as 0

-200 ~ 

+400

0

FILt

PV input fi lter

The value of FILt will determine the 

ability of fi ltering noise.  

If great interference exists, then you 

can increase parameter "FILt" gradually 

to make momentary fluctuation of 

measured value less than 2 to 5.  

W h e n   t h e   i n s t r u m e n t   i s   b e i n g 

metrological verified, "FILt" s can be 

set to 0 or 1 to shorten the response 

time.

0~40

1

Fru

Power 

frequency and 

display unit

50Cmeans 50Hz,display unit is 

℃。

50F,means 50Hz,display unit is 

℉。

60Cmeans 60Hz,display unit is 

℃。

60Fmeans 60Hz, display unit is 

℉。

50C

OPH Output highest 

limit

Mininmum value of SV

-999~

+3000

0

SPH

Upper limit of 

SV

Maximum value that SV

40

VII. Installation and wiring 

Wiring graph for instruments with dimension A, B

, E and F: 

    

www.yudian.com   

                       

Yudian Copyright 1991-2015

Note:The graph suits for 
upright instruments with 
dimension A

C or E

     
F o r   i n s t r u m e n t s   w i t h 
dimension B or F size,just 
clockwise rotate the graph 
90 degree.

Note:The graph suits for 
upright instruments with 
dimension A1 

C1or E1

   
For instruments with 
dimension B1 or F1 
size,just clockwise rotate 
the graph 90 degree.

!

POWER

ALM

AL1
AL2