5. Adjustment 

5.1 

Setting Point Switch

 

SPTM-5V series can be calibrated in 2 or 5 points setting.       

a)  2 Point Setting: 

By setting minimum and maximum points <0% and 100% of valve stroke>, in-b 

b)  5 Point Setting 

By setting 5 points <0%, 25%, 50%, 75%, and 100%> the outputs can be set accordingly.   

 

5.2 

Adjustment - Calibration

 

a)  Input 4mA signal to the positioner to move the valve stroke to the 4mA position.     

b)  After the valve reaches at the 4mA position, press “4mA button for 3-4 seconds.  The 

lamp will be lighted, and this indicates that 4mA output 

feedback position has been calibrated.     

c)  Please repeat above step for 8mA, 12mA, 16mA, and 

20mA for 5 point setting.  For 2 point setting, repeat 

above step for 20mA only.     

 

5.3 

Adjustment – Potentiometer 

Potentiometer is designed to output 12mA signal when the feedback lever is at 50% position.   

In case of dislocation of the potentiometer, please follow below procedure to re-set the 

potentiometer.   

 Power must be turned off before adjusting potentiometer.   

 Please be cautious when adjusting potentiometer.   

 Please make sure that there is no remaining circuit on the PCB.   

 Please do not use excessive force when disconnecting potentiometer from the PCB.   

 

1.  Locate the potentiometer under the PCB.    Disconnect from the PCB.    Please do not use 

excessive force.   

2.  Unfasten lock screw which locks the potentiometer gear and take out potentiometer body 

from the lag-gear.   

3.  Fix the feedback lever at 50% position and measure resistance level by connecting two 

probes out of three inlets.     

4.  Rotate pinion gear until resistance vale is about 5K

.  

5.  After setting the resistance value, rotate stopper to the normal position an fasten the lock 

screw. 

6.  Reconnect potentiometer to the PCB and reinstall PCB onto SPTM-5V body.     

Содержание SPTM-5V Series

Страница 1: ...Smart Position Transmitter PRODUCT MANUAL SPTM 5V SERIES VERSION 1 01...

Страница 2: ...tions 4 2 3 Label Description 4 2 4 Product Number 5 2 5 Product Specification 5 2 6 Parts and Assembly 6 2 7 Dimension SPTM 5VL 7 2 8 Dimension SPTM 5VR 7 3 Installation 8 3 1 Safety 8 3 2 SPTM 5VL I...

Страница 3: ...ponsible for any damages caused by user s negligence Manufacturer will not be responsible for any damages or accidents as a result of any alteration or modification of the product and its parts If any...

Страница 4: ...uilt micro processor which transmits DC 4 20mA signal according to changes in valve or damper position 2 2 Main Features and Functions Designed to be Ex ia IIC T6 explosion proof grades Economical pri...

Страница 5: ...Signal 4 20mA DC Load Resistance Max 600 28V DC Supply Voltage 9 28V DC Noise Range 50mV p p Conduit Entry PF 1 2 G 1 2 Enclosure IP 67 Explosion Proof Ex ia IIC T6 KCs Ambient Temp Operating 40 C 85...

Страница 6: ...6 SPTM 5V series 2 6 Parts and Assembly...

Страница 7: ...7 SPTM 5V series 2 7 Dimension SPTM 5VL 2 8 Dimension SPTM 5VR...

Страница 8: ...f the valve stroke Feedback lever connection with the pin of the actuator clamp should be installed in such a way that the valve stroke length coincides with the corresponding figure of mm marked on t...

Страница 9: ...he connection pin at the number on the feedback lever which corresponds to the desired valve stroke To adjust mover the bracket or the connection pin or both 9 After installing the SPTM 5v operate the...

Страница 10: ...ing type rug to protect against vibration or any other external impact Please use twisted cable with conductor section are 1 25mm2 and that is suitable for 600V complying to the conductor table of NEC...

Страница 11: ...to output 12mA signal when the feedback lever is at 50 position In case of dislocation of the potentiometer please follow below procedure to re set the potentiometer Power must be turned off before ad...

Страница 12: ...talled improperly please refer to the positioner s manual and re install the positioner C Set the positioner s zero and span Inaccurate zero and span setting can lower the accuracy and linearity D Che...

Страница 13: ...eries Manufacturer Young Tech Co Ltd 3022 Hagun ri Yangchon myeon Kimpo si Kyeonggi do 415 843 South Korea Tel 82 31 986 8545 Fax 82 31 986 2683 Email ytc ytc co kr Copyright Young Tech Co Ltd All Rig...

Отзывы: