Yoshitake GD-24 Скачать руководство пользователя страница 4

-3- 

EPDT-209

 

 3.2  Construction  
 

No.

Name of parts 

1 Body 
2 Spring 

Chamber 

3 Cap 
4 Valve 
5 Valve 

Seat 

6 Disc 
7 Suspension 

Metal 

8 Diaphragm 

Shell 

9 Diaphragm 

10

Spring Plate 

11

Adjusting Screw 

12

Lock Nut 

13

Washer 

14

Set Screw 

15

Spring Lock Washer 

16

Nut 

17

Adjusting Spring 

18

O-ring 

19

Bolt 

20

Sealed Nut 

21

Spring 

22

Plug 

27

Label 

28

Spring Washer 

 

 
 

 

4. Operation   

(Refer to the parts number in “3.2 Construction”) 

Turning the adjusting screw(11) to compress the adjusting spring(17) and the load of adjusting 

spring is introduced to the diaphragm(9) and suspension metal(7) to open the valve(4). Then, 
the fluids begin to flow from the inlet side through the upper side of the valve. The reduced 

pressure is led to the diaphragm to be balanced with the adjusting spring load, and control the 

valve travel to maintain the reduced pressure.   

 

 

Содержание GD-24

Страница 1: ...lease carefully store this manual in a handy place The following safety symbols are used in this manual Warning Caution Contents 1 Features 1 2 Specifications 1 3 Dimensions and Construction 3 1 Dimen...

Страница 2: ...rusty water problems 3 A stainless steel valve seat reduces wear and increases durability 4 A sealed construction prevents external leakage even if the diaphragm should break 5 The valve can be mount...

Страница 3: ...3 1 Dimensions Weight GD 24 24B mm Nominal size d L H H1 Weight kg 15A Rc 1 2 80 193 41 5 1 8 20A Rc 3 4 90 210 45 2 4 25A Rc 1 100 230 50 3 3 32A Rc 1 1 4 120 265 60 4 7 40A Rc 1 1 2 150 315 62 8 2 5...

Страница 4: ...ing 22 Plug 27 Label 28 Spring Washer 4 Operation Refer to the parts number in 3 2 Construction Turning the adjusting screw 11 to compress the adjusting spring 17 and the load of adjusting spring is i...

Страница 5: ...he pipe is ideal Cv Value Nominal size 15A 20A 25A 32A 40A 50A Cv value 1 5 1 9 3 4 7 10 Calculation formula for Cv value P G V Cv 365 0 P1 Inlet pressure MPa A V Rated flow rate m3 h P2 Reduced press...

Страница 6: ...5 EPDT 209 5 2 Flow Rate Characteristics Chart 5 3 Pressure Characteristics Chart...

Страница 7: ...lenoid valve secure at least 3 m from the valve Failure to do so may result in malfunction or drastically shortened service life 7 When pressure reducing in two stages secure at least 3 m between the...

Страница 8: ...nt parts Be sure to follow the following steps to complete proper adjustment Refer to the parts number in 3 2 Construction 1 Close the stop valves at both sides of the pressure reducing valve and thor...

Страница 9: ...and after pressure reducing valve and remove all foreign matter and scales via the by pass line before operation Failure to do so may cause the malfunction of pressure reducing valve Consumable parts...

Страница 10: ...oxes are consumable parts Nut Spring Lock Washer Diaphragm Shell Diaphragm Suspension Metal Pressure Gauge Body Valve Seat Set Screw Washer Disc Valve O ring Spring Cap Adjusting Screw Sealed Nut Bolt...

Отзывы: