5167531-YIM-J-1019
Johnson Controls Ducted Systems
29
Reheat coil data
Face area (sq. ft)
6.66
6.66
10
10
10
Rows
2
2
2
2
2
Fins per inch
13
13
13
13
13
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Condenser fan data
Quantity of fans
2
2
2
2
4
Fan diameter (inches)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Quantity of motors
2
2
2
2
4
Motor HP each
1/3
1/3
1/3
3/4
1/3
No. of speeds
1
1
1
1
1
RPM
850
850
850
1110
850
Total CFM
6800
6800
6800
9500
14000
Belt drive evap. fan data
Quantity
1
1
1
1
1
Fan size (inches)
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Type
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
56
56
56
184T
Filters
Quantity - size
4 - (24 x 16 x 2)
6,7
4 - (24 x 16 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 16 x 4)
8
4 - (24 x 16 x 4)
8
4 - (24 x 20 x 4)
8
4 - (24 x 20 x 4)
8
4 - (24 x 20 x 4)
8
1. Cooling only unit or cooling unit with electric heat
2. Cooling unit with gas heat
3. Does not meet DOE 2018 minimum efficiency requirements
4. First stage 60% of second stage
5. ZR090, ZR102, ZR120, ZR150, have crankcase heaters standard.
6. 2 in. throwaway, standard, MERV (Minimum Efficiency Reporting Value) 3.
7. 2 in. pleated, optional, MERV 8.
8. 4 in. pleated, optional, MERV 13.
Table 11: ZR078-150 physical data (continued)
Component
Models
ZR078
ZR090
ZR102
ZR120
ZR150
Nominal tonnage
6.5
7.5
8.5
10
12.5