background image

524581-YIM-I-0512

Johnson Controls Unitary Products

65

Cooling Troubleshooting Guide

NOTE: 

For units with optional VFD without manual bypass, the 
M3 contactor has been replaced with an "ice cube" 
relay (designated 'VFDR') located in the control box. 
The relay is energized by "FAN" output from the UCB. 
Normally-open relay contacts provide a run-permit 
signal to the VFD.

On calls for cooling, if the compressors are operating but the 
supply air blower motor does not energize after a short delay 
(the room thermostat fan switch is in the “AUTO” position):

1.

Turn the thermostat fan switch to the ON position. If the 
supply air blower motor does not energize, go to Step 3.

2.

If the blower motor runs with the fan switch in the ON 
position but will not run after the first compressor has 
energized when the fan switch is in the AUTO position, 
check the room thermostat for contact between R and G in 
the AUTO position during calls for cooling.

3.

If the supply air blower motor does not energize when the 
fan switch is set to ON, check that line voltage is being 
supplied to the contacts of the M3, contactor, and that the 
contactor is pulled in. Check for loose wiring between the 
contactor and the supply air blower motor.

4.

If M3 is pulled in and voltage is supplied to M3, lightly touch 
the supply air blower motor housing. If it is hot, the motor 
may be off on internal protection. Cancel any thermostat 
calls and set the fan switch to AUTO. Wait for the internal 
overload to reset. Test again when cool.

5.

If M3 is not pulled in, check for 24 volts at the M3 coil. If 24 
volts are present at M3 but M3 is not pulled in, replace the 
contactor.

6.

Failing the above, if there is line voltage supplied at M3, M3 
is pulled in, and the supply air blower motor still does not 
operate, replace the motor.

7.

If 24 volts is not present at M3, check that 24 volts is 
present at the UCB supply air blower motor terminal, 
“FAN”. If 24 volts is present at the FAN, check for loose 
wiring between the UCB and M3.

8.

If 24 volts is not present at the “FAN” terminal, check for 24 
volts from the room thermostat. If 24 volts are not present 
from the room thermostat, check for the following:

a. Proper operation of the room thermostat (contact 

between R and G with the fan switch in the ON position 
and in the AUTO position during operation calls).

b. Proper wiring between the room thermostat and the 

UCB, and

c. Loose wiring from the room thermostat to the UCB

9.

If 24 volts is present at the room thermostat but not at the 
UCB, check for proper wiring between the thermostat and 
the UCB, i.e. that the thermostat G terminal is connected to 
the G terminal of the UCB, and for loose wiring.

10. If the thermostat and UCB are properly wired, replace the 

UCB.

On calls for cooling, the supply air blower motor is operating but 
compressor #1 is not (the room thermostat fan switch is in the 
“AUTO” position):

1.

If installed, check the position of the economizer blades. If 
the blades are open, the economizer is providing free 
cooling and the compressors will not immediately operate. 
If both stages of cooling are requested simultaneously and 
the economizer provides free cooling, following a short 
delay compressor #1 will be energized unless it is locked 
out. If compressor #1 is locked out, compressor #2 is 
energized. Compressor #2 is always energized in place of 
compressor #1 when compressor #1 is requested but 
locked out.

2.

If no economizer is installed or the economizer is not 
opening to provide free cooling and compressor #1 does 
not energize on a call for cooling, check for line voltage at 
the compressor contactor, M1, and that the contactor is 
pulled in. Check for loose wiring between the contactor and 
the compressor.

3.

If M1 is pulled in and voltage is supplied at M1, lightly touch 
the compressor housing. If it is hot, the compressor may be 
off on inherent protection. Cancel any calls for cooling and 
wait for the internal overload to reset. Test again when 
cool.

4.

If M1 is not pulled in, check for 24 volts at the M1 coil. If 24 
volts are present and M1 is not pulled in, replace the 
contactor.

5.

Failing the above, if voltage is supplied at M1, M1 is pulled 
in, and the compressor still does not operate, replace the 
compressor.

6.

If 24 volts is not present at M1, check for 24 volts at the 
UCB terminal, C1. If 24 volts is present, check for loose 
wiring between C1 and the compressor contactor.

7.

If 24 volts is not present at the C1 terminal, check for 24 
volts from the room thermostat at the UCB Y1 terminal. If 
24 volts is not present from the room thermostat, check for 
the following:

a. 24 volts at the thermostat Y1 terminal

b. Proper wiring between the room thermostat and the 

UCB, i.e. Y1 to Y1, Y2 to Y2, and

c. Loose wiring from the room thermostat to the UCB

8.

If 24 volts is present at the UCB Y1 terminal, the 
compressor may be out due to an open high-pressure 
switch, low-pressure switch, or freezestat. Check for 24 
volts at the HPS1, LPS1, and FS1 terminals of the UCB. If 
a switch has opened, there should be a voltage potential 
between the UCB terminals, e.g. if LPS1 has opened, there 
will be a 24-volt potential between the LPS1 terminals.

9.

If 24 volts is present at the UCB Y1 terminal and none of 
the protection switches have opened, the UCB may have 
locked out the compressor for repeat trips. The UCB 
should be flashing an alarm code. If not, press and release 
the ALARMS button on the UCB. The UCB will flash the 
last five alarms on the LED. If the compressor is locked 

Содержание ZJ078

Страница 1: ...ower Exhaust Specifications 46 20 Motor Sheave Datum Diameters 48 21 Additional Static Resistance 49 22 Electric Heat Limit Setting 53 23 Electric Heat Anticipator Setpoints 54 24 Gas Heat Limit Control Settings 55 25 Gas Heat Anticipator Setpoints 56 26 Gas Rate Cubic Feet Per Hour 58 27 Gas Heat Stages 58 28 Unit Control Board Flash Codes 60 29 Heat Delay 62 30 Ignition Control Flash Codes 62 31...

Страница 2: ...precautions and codes including ANSI Z223 1 or CSA B149 1 latest edition Improper installation may create a condition where the operation of the product could cause personal injury or property damage Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for assistance or for additional information consult a qualified contractor ...

Страница 3: ...ation on combustible material and may be installed directly on combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials 4 For use with natural gas convertible to LP with kit This product must be installed in strict compliance with the enclosed installation instructions and any applicable local state and national codes including but not limited to bu...

Страница 4: ...ctor S A 4 Smoke Detector R A 5 Pwr d Conv Outlet Options AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor Coil Guard AF Phase Monitor Dirty Filter Switch AG Coil Guard Dirty Filter Switch AH Phase Monitor Coil Guard Dirty Filter Switch Additional Options RC Coil Guard Shipping Bag American Flag TA Technicoat Condenser Coil TJ Technicoat Evaporator Coil TS Technicoat ...

Страница 5: ...he ground 3 Remove the condenser coil external protective covering prior to operation 4 Remove the toolless doorknobs and instruction packet prior to installation Figure 2 Condenser Covering Figure 3 Compressor Section 5 If a factory option convenience outlet is installed the weatherproof outlet cover must be field installed The cover shall be located behind the filter access panel To install the ...

Страница 6: ...lications computer rooms switchgear etc please reference applications bulletin AE 011 07 or call the applications department for Unitary Products 1 877 UPG SERV for guidance Additional accessories may be needed for stable operation at temperatures below 30 F Roof curbs in eight and fourteen inch heights Roof curbs for transitioning from York Sunline footprint to the ZJ Series footprints are also a...

Страница 7: ...ise care when moving the unit Do not remove any packaging until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimension across the unit MUST be used across the top of the unit Table 1 ZJ078 150 Unit Limitations Size Tons Model Unit Voltage Unit Limitations App...

Страница 8: ...ted The condenser coils should be protected from rigging cable damage with plywood or other suitable material D A C B LEFT FRONT D A C B E F LEFT FRONT X Y LEFT FRONT Table 2 Weights and Dimensions Size Tons Model Weight lbs Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F 078 6 5 ZJ 1035 1030 39 25 245 191 260 333 170 144 122 167 195...

Страница 9: ...t1 1 Weight given is for the maximum heater size available 54KW 49 49 Gas Heat2 2 Weight given is for the maximum number of tube heat exchangers available 8 tube 110 110 Variable Frequency Drive3 3 Weight includes mounting hardware controls and manual bypass option 30 30 LEFT A 59 00 C D E F 4 19 27 31 89 00 21 19 11 38 15 38 59 00 15 38 29 69 15 25 FRONT SEE DETAIL B FOR DRAIN LOCATION SEE DETAIL...

Страница 10: ...Unitary Products Figure 9 ZJ150 Physical Dimensions 15 23 29 03 14 85 29 03 14 85 15 23 28 86 29 66 44 09 Ø 24 58 TYP 4 PL FRONT See detail B for drain location See detail A for gas inlet C D E F B 4 3 16 27 5 16 89 21 3 16 11 3 8 A LEFT 59 ...

Страница 11: ... 30 3 16 24 3 16 17 3 16 6 3 16 42 CABINET Ø 3 126 Ø 2 000 3 184 4 727 7 705 14 594 Gas Pipe Inlet Gas Exhaust Vent 50 3 4 CABINET Ø 3 126 Ø 2 000 3 184 4 737 7 715 17 541 Gas Pipe Inlet Gas Exhaust Vent 5 3 8 3 4 FPT Table 5 ZJ078 150 Unit Clearances Direction Distance in Direction Distance in Top1 1 Units must be installed outdoors Over hanging structure or shrubs should not obscure condenser ai...

Страница 12: ...t Bottom Duct Openings Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27 1 2 24 21 18 89 Ø 2 469 3X Ø 0 875 Bottom power control and convenience outlet wiring entry ...

Страница 13: ...Electrical Entry Figure 12 ZJ078 120 Unit Side Duct Openings Disconnect Swith Cover Power Entry Ø 2 1 2 Control Entry Ø 7 8 Power Entry Ø 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7 8 FRONT Dot Plugs 5 5 32 31 11 16 2 31 32 18 1 4 Return Air Supply Air A B C D ...

Страница 14: ... Left Duct Opening Dot Plugs 2 7 8 5 5 32 D C 31 5 8 18 1 4 B A Table 6 Side Duct Dimensions Unit Model Number Dimension in A B C D ZJ078 28 1 4 18 1 16 28 1 4 18 1 4 ZJ090 28 1 4 18 1 16 28 1 4 18 1 4 ZJ102 28 1 4 18 1 16 28 1 4 18 1 4 ZJ120 28 1 4 18 1 16 28 1 4 18 1 4 ZJ150 28 1 4 18 1 16 28 1 4 18 1 4 4 5 16 30 3 8 ...

Страница 15: ...e The supply and return air duct connections at the unit should be made with flexible joints to minimize noise The supply and return air duct systems should be designed for the CFM and static pressure requirements of the job They should NOT be sized to match the dimensions of the duct connections on the unit Refer to Figure 10 for bottom air duct openings Refer to Figures 12 13 and Table 6 for sid...

Страница 16: ...With Panel Figure 19 Discharge Panel In Place Condensate Drain The side condensate drain is reversible and maybe re oriented to the rear of the cabinet to facilitate condensate piping A condensate drain connection is available through the base pan for piping inside the roof curb Trap the connection per Figure 20 The trap and drain lines should be protected from freezing Plumbing must conform to lo...

Страница 17: ...replaced replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire A disconnect must be utilized for these units Factory installed disconnects are available If installing a disconnect field supplied or York International supplied accessory refer to Figure 4 for the recommended mounting location NOTE Since not all local codes allow the mounting...

Страница 18: ...nto the unit through the side of the unit or the basepan inside the curb Figure 21 Field Wiring Disconnect Cooling Unit With Without Electric Heat and All Units With VFD Option Figure 22 Field Wiring Disconnect Cooling Unit With Gas Heat Without VFD Option THREE PHASE POWER SUPPLY FACTORY OR FIELD SUPPLIED DISCONNECT GROUND LUG TERMINAL BLOCK TB1 L1 T1 L2 T2 T3 L3 THREE PHASE POWER SUPPLY FACTORY ...

Страница 19: ...Wiring 24 Volt Thermostat Table 7 Control Wire Sizes Wire Size Maximum Length1 1 From the unit to the thermostat and back to the unit 18 AWG 150 Feet 208 230 3 60 and 380 415 3 50 units control transformers are factory wired for 230v and 415v power supply respectively Change tap on transformer for 208 3 60 or 380 3 50 operation See unit wiring diagram W2 RC RH Y1 Y2 W1 G C X1 X3 X4 A1 A2 T T W2 Y1...

Страница 20: ...39 8 45 3 50 50 E09 6 8 1 18 9 39 8 45 3 50 50 E18 13 5 2 37 5 54 3 61 2 60 70 E24 18 2 50 0 70 76 8 70 80 E36 25 5 2 70 8 96 102 9 100 110 230 11 9 88 18 5 3 5 6 0 5 5 0 0 None 39 8 45 3 50 50 E09 9 1 21 7 39 8 45 3 50 50 E18 18 2 43 3 61 6 68 5 70 70 E24 24 2 57 7 79 7 86 5 80 90 E36 34 2 81 8 109 7 116 6 110 125 460 5 2 44 8 1 1 6 3 0 2 2 0 0 None 17 9 20 1 20 25 E09 9 1 10 8 17 9 20 1 20 25 E1...

Страница 21: ...6 73 1 90 90 E24 18 2 50 0 74 5 81 3 90 90 E36 25 5 2 70 8 100 5 107 4 110 110 E54 40 6 2 112 7 152 9 159 7 175 175 230 23 1 160 36 1 5 9 6 5 5 0 0 None 67 6 73 1 90 90 E18 18 2 43 3 67 6 73 1 90 90 E24 24 2 57 7 84 2 91 90 100 E36 34 2 81 8 114 2 121 1 125 125 E54 54 2 129 9 141 9 148 8 175 175 460 12 2 87 19 0 8 4 8 2 2 0 0 None 35 5 37 7 45 45 E18 18 2 21 7 35 5 37 7 45 45 E24 24 2 28 9 42 1 44...

Страница 22: ... 60 E09 6 8 1 18 9 43 4 48 9 50 60 E18 13 5 2 37 5 58 8 65 7 60 70 E24 18 2 50 0 74 5 81 3 80 90 E36 25 5 2 70 8 100 5 107 4 110 110 230 11 9 88 18 5 3 5 9 6 5 5 0 0 None 43 4 48 9 50 60 E09 9 1 21 7 43 4 48 9 50 60 E18 18 2 43 3 66 1 73 70 80 E24 24 2 57 7 84 2 91 90 100 E36 34 2 81 8 114 2 121 1 125 125 460 5 2 44 8 1 1 6 4 8 2 2 0 0 None 19 7 21 9 20 25 E09 9 1 10 8 19 7 22 3 20 25 E18 18 2 21 ...

Страница 23: ... 7 90 100 E24 18 2 50 0 81 5 88 3 90 100 E36 25 5 2 70 8 107 5 114 4 110 125 E54 40 6 2 112 7 159 9 166 7 175 175 230 23 1 160 36 1 5 15 2 5 5 0 0 None 73 2 78 7 90 100 E18 18 2 43 3 73 2 80 90 100 E24 24 2 57 7 91 2 98 100 100 E36 34 2 81 8 121 2 128 1 125 150 E54 54 2 129 9 148 9 155 8 175 175 460 12 2 87 19 0 8 7 6 2 2 0 0 None 38 3 40 5 50 50 E18 18 2 21 7 38 3 40 5 50 50 E24 24 2 28 9 45 6 48...

Страница 24: ...E09 6 8 1 18 9 49 8 55 3 60 60 E18 13 5 2 37 5 66 8 73 7 70 80 E24 18 2 50 0 82 5 89 3 90 90 E36 25 5 2 70 8 108 5 115 4 110 125 230 11 9 88 18 5 3 5 6 0 5 5 10 0 None 49 8 55 3 60 60 E09 9 1 21 7 49 8 55 3 60 60 E18 18 2 43 3 74 1 81 80 90 E24 24 2 57 7 92 2 99 100 100 E36 34 2 81 8 122 2 129 1 125 150 460 5 2 44 8 1 1 6 3 0 2 2 5 0 None 22 9 25 1 25 30 E09 9 0 1 10 8 23 5 26 3 25 30 E18 18 2 21 ...

Страница 25: ...77 6 83 1 100 100 E24 18 2 50 0 87 93 8 100 100 E36 25 5 2 70 8 113 119 9 125 125 E54 40 6 2 112 7 165 4 172 2 175 175 230 23 1 160 36 1 5 9 6 5 5 10 0 None 77 6 83 1 100 100 E18 18 2 43 3 78 6 85 5 100 100 E24 24 2 57 7 96 7 103 5 100 110 E36 34 2 81 8 126 7 133 6 150 150 E54 54 2 129 9 154 4 161 3 175 175 460 12 2 87 19 0 8 4 8 2 2 5 0 None 40 5 42 7 50 50 E18 18 2 21 7 40 5 42 7 50 50 E24 24 2 ...

Страница 26: ... 70 E09 6 8 1 18 9 53 4 58 9 60 70 E18 13 5 2 37 5 71 3 78 2 80 80 E24 18 2 50 0 87 93 8 90 100 E36 25 5 2 70 8 113 119 9 125 125 230 11 9 88 18 5 3 5 9 6 5 5 10 0 None 53 4 58 9 60 70 E09 9 1 21 7 53 4 58 9 60 70 E18 18 2 43 3 78 6 85 5 80 90 E24 24 2 57 7 96 7 103 5 100 110 E36 34 2 81 8 126 7 133 6 150 150 460 5 2 44 8 1 1 6 4 8 2 2 5 0 None 24 7 26 9 25 30 E09 9 1 10 8 25 8 28 5 30 30 E18 18 2...

Страница 27: ...8 7 100 110 E24 18 2 50 0 94 100 8 100 110 E36 25 5 2 70 8 120 126 9 125 150 E54 40 6 2 112 7 172 4 179 2 175 200 230 23 1 160 36 1 5 15 2 5 5 10 0 None 83 2 88 7 100 110 E18 18 2 43 3 85 6 92 5 100 110 E24 24 2 57 7 103 7 110 5 110 125 E36 34 2 81 8 133 7 140 6 150 150 E54 54 2 129 9 161 4 168 3 175 175 460 12 2 87 19 0 8 7 6 2 2 5 0 None 43 3 45 5 50 50 E18 18 2 21 7 43 3 45 6 50 50 E24 24 2 28 ...

Страница 28: ... 80 80 80 No burners 4 6 4 6 4 6 6 8 6 8 No stages 23 23 23 23 23 23 23 23 23 23 Temperature Rise Range ºF 20 50 35 65 15 45 30 60 10 40 25 55 20 50 35 65 10 40 25 55 Gas Limit Setting ºF 165 165 165 165 215 195 195 160 195 160 Gas piping connection in 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 DIMENSIONS inches Length 89 89 89 89 119 1 2 Width 59 59 59 59 59 Height 50 3 4 50 3 4 50 3 4 50 3 4 50 3 4...

Страница 29: ...1VM50 1VP56 Blower Sheave AK74 AK74 AK69 AK69 AK89 AK74 AK84 AK74 AK74 BK77 Belt A53 A54 A53 A54 A56 A54 A56 A54 A54 BX55 Motor HP each 1 1 2 2 1 1 2 3 2 3 2 3 3 5 RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 Frame size 56 56 56 56 56 56 56 56 56 184T FILTERS Quantity Size 4 24 x 20 x 2 4 5 4 24 x 20 x 2 4 5 4 24 x 20 x 2 4 5 4 24 x 20 x 2 4 5 4 24 x 20 x 2 4 5 4 24 x 20 x 4 6 4 24 x 20 x...

Страница 30: ... minimum CFM limitations and to Table 8 for electrical data Table 10 Electric Heat Minimum Supply Air Size Tons Model Voltage Minimum Supply Air CFM Heater kW 9 18 24 36 54 078 6 5 ZJ 208 230 3 60 1950 1950 1950 1950 460 3 60 1950 1950 1950 1950 600 3 60 1950 1950 1950 1950 090 7 5 ZJ 208 230 3 60 2250 2250 2250 2250 460 3 60 2250 2250 2250 2250 600 3 60 2250 2250 2250 2250 102 8 5 ZJ 208 230 3 60...

Страница 31: ...er to the Pipe Sizing Table 11 The heating value of the gas may differ with locality The value should be checked with the local gas utility Figure 25 Side Entry Gas Piping Figure 26 Bottom Entry Gas Piping NOTE Maximum capacity of pipe in cubic feet of gas per hour based upon a pressure drop of 0 3 inch W C and 0 6 specific gravity gas NOTE There may be a local gas utility requirement specifying a...

Страница 32: ... safety standards of the National Fire Protection Association Table 12 Gas Heat Minimum Supply Air Size Tons Model Heat Size Supply Air CFM Cooling Heating Min Max Min Max 078 6 5 ZJ 10 1950 3250 1950 3250 15 1950 3250 1950 3250 090 7 5 ZJ 10 2250 3750 2250 3750 15 2250 3750 2250 3750 102 8 5 ZJ 10 2550 4250 2550 4250 15 2550 4250 2550 4250 120 10 ZJ 15 3000 5000 3000 5000 20 3000 5000 3000 5000 1...

Страница 33: ...rding to NFPA 72 requirements and cleaned at least once a year For specific troubleshooting and maintenance procedures please refer to the smoke detector s installation instructions which accompanies the unit Motorized Outdoor Damper The Motorized Outdoor Damper can be a factory installed option or a field installed accessory If factory installed refer to the instructions included with the outdoor...

Страница 34: ... ductwork and to the atmosphere Connect the tubing from the HIGH pressure tap of the transducer to a static pressure tap field supplied in the supply duct located at a point where constant pressure is expected To prevent an unstable signal due to air turbulence there should be no obstructions turns or VAV terminal boxes up or down stream of the sensing tube location for at least a distance of 6 10...

Страница 35: ... connections run permit signal speed reference signal fault signal All required drive parameters are pre programmed at the factory except in the case of 208 volt applications in which the parameter that defines motor nameplate voltage must be changed to a value of 208 00 and the parameter that defines motor rated current must be changed to the appropriate value appearing on the motor s nameplate R...

Страница 36: ...lsewhere either within the building on a perpendicular wall which is not subjected to excessive temperature vibration humidity dust corrosive gas explosive gas etc or within an appropriate enclosure rated for outside installation to safeguard against moisture dust and excessive heat The power leads to the drive L1 L2 L3 and from the motor T1 T2 T3 have been temporarily spliced together with wire n...

Страница 37: ...t With no power exhaust option adjust the Exhaust Air Adjustment Screw fully clockwise This will allow 2nd stage cooling to operate With power exhaust option each building pressurization requirement will be different The point at which the power exhaust comes on is determined by the economizer damper position Percent Open The Exhaust Air Adjustment Screw should be set at the Percent Open of the ec...

Страница 38: ...ischarge pressures or producing a high noise level the scroll is misphased 40 4 70 21 50 10 55 13 60 16 65 18 35 2 45 7 75 24 80 27 35 2 40 4 45 7 50 10 55 13 60 16 65 18 70 21 75 24 80 27 85 29 85 29 90 32 90 32 105 41 110 43 100 38 95 35 95 35 100 38 105 41 110 43 APPROXIMATE DRY BULB TEMPERATURE 0 F 0 C D D C C B B A A CONTROL CURVE CONTROL POINT APPROX 0 F 0 C AT 50 RH A D C B 63 17 73 23 70 2...

Страница 39: ... will be generated and less power will be required than a similar application at sea level Air density correction factors are shown in Table 14 and Figure 31 Scroll compressors require proper rotation to operate correctly Units are properly phased at the factory Do not change the internal wiring to make the blower condenser fans or compressor rotate correctly Table 13 Supply Air Limitations Unit S...

Страница 40: ...given is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80 Enter the blower table at 6000 sCFM and static pressure of 1 8 The rpm listed will be the same rpm needed at 5 000 ft Suppose that the corresponding BHP listed in the table is 3 2 This value must be corrected for elevation BHP at 5 000 ft ...

Страница 41: ...5 1 95 BHP exceeds the maximum continuous BHP rating of the 1 5 HP motor The 2 HP motor is required 6 1268 RPM is within the range of the 2 HP drives 7 Using the 2 HP motor and drive 5 turns open will achieve 1268 RPM Airflow Performance Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP RPM BHP ...

Страница 42: ...400 631 0 16 682 0 41 736 0 66 793 0 90 852 1 14 911 1 36 970 1 58 1028 1 78 1084 1 97 1136 2 13 2600 642 0 27 692 0 52 747 0 76 804 1 01 862 1 24 922 1 47 981 1 69 1039 1 89 1094 2 07 1146 2 24 2800 652 0 39 703 0 64 757 0 88 814 1 13 873 1 36 932 1 59 992 1 81 1049 2 01 1105 2 19 1157 2 36 3000 663 0 53 714 0 77 768 1 02 825 1 26 884 1 50 943 1 73 1003 1 94 1060 2 14 1116 2 33 1168 2 49 3200 675...

Страница 43: ...IWG1 1 Blower performance includes gas heat exchangers and 2 filters See STATIC RESISTANCE table for additional applications 2 See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP 3 kW BHP x 0 932 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Stand...

Страница 44: ...1 1012 1 61 1065 1 81 1113 2 02 1153 2 24 2400 689 0 42 743 0 69 800 0 93 859 1 16 919 1 37 978 1 57 1035 1 77 1088 1 97 1135 2 18 1176 2 40 2600 712 0 60 766 0 87 823 1 11 882 1 34 942 1 55 1002 1 75 1058 1 95 1111 2 15 1159 2 36 1199 2 58 2800 736 0 80 790 1 06 847 1 31 906 1 53 967 1 74 1026 1 94 1082 2 14 1135 2 34 1183 2 55 1223 2 78 3000 761 1 00 815 1 27 872 1 52 931 1 74 991 1 95 1051 2 15...

Страница 45: ...RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard 3 HP Drive Hi Static 5 HP Drive 3200 797 1 32 851 1 46 903 1 60 953 1 74 1001 1 86 1048 1 99 1093 2 11 1138 2 23 1181 2 35 1224 2 48 3400 828 1 52 882 1 67 934 1 81 983 1 94 1032 2 07 1078 2 19 1124 2 32 1168 2 44 1212 2 56 1254 2 68 3600 861 1 75 915 1 90 967 2 04 1017 2 17 1065 2 30 1112 2 42 1157 2 54 1201 2 6...

Страница 46: ... screws after 10 12 hrs run time is recommended Table 18 Indoor Blower Specifications Size Tons Model Motor Motor Sheave Blower Sheave Belt HP RPM Eff SF Frame Datum Dia in Bore in Model Datum Dia in Bore in Model 078 6 5 ZJ 1 1 2 1725 0 8 1 15 56 2 6 3 6 7 8 1VL40 7 0 1 AK74 A53 2 1725 0 8 1 15 56 3 6 4 6 7 8 1VM50 7 0 1 AK74 A54 090 7 5 ZJ 1 1 2 1725 0 8 1 15 56 2 6 3 6 7 8 1VL40 6 5 1 AK69 A53 ...

Страница 47: ...open 5 Select the correct blower performance table for the unit from Tables 15 and 16 Tables are presented for side and downflow configuration 6 Determine the unit Measured CFM from the Blower Performance Table External Static Pressure and the number of turns the variable motor sheave is open 7 To adjust Measured CFM to Required CFM see SUPPLY AIR DRIVE ADJUSTMENT 8 After reading has been obtained...

Страница 48: ...stallation for any installation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure and BHP BHP and AMP draw of the blower motor will increase by the cube of the blower speed Static pressure will increase by the square of the blower speed Only qualified personnel should make blower sp...

Страница 49: ...stance in the respective Blower Performance Tables Economizer2 3 2 Deduct these values from the available external static pressure shown in the respective Blower Performance Tables 3 The pressure drop through the economizer is greater for 100 outdoor air than for 100 return air If the resistance of the return air duct is less than 0 25 IWG the unit will deliver less CFM during full economizer oper...

Страница 50: ...plicity Freenet USB Adapter S1 03101967000 5 Freenet service cable S1 02538682000 No Outdoor Air Options When the thermostat calls for the first stage of cooling the low voltage control circuit from R to Y1 and G is completed The UCB energizes the economizer if installed and free cooling is available or the first available compressor and the condenser fans For first stage cooling compressor 1 is e...

Страница 51: ... Outside Air Temperature sensor and will allow free cooling when the outdoor temperature is less than both the First Stage SAT Control set point plus 5 F and the Economizer OAT Enable set point Single Enthalpy optional A field installed Outdoor Air Humidity sensor is connected to the control When the measured outdoor enthalpy is below the Outside Air Enthalpy set point and the outdoor temperature ...

Страница 52: ...he UCB will de energize the associated compressor initiate the ASCD and if the other compressor is idle stop the condenser fans If the call for cooling is still present at the conclusion of the ASCD the UCB will re energize the halted compressor Should a freezestat open three times within two hours of operation the UCB will lock out the associated compressor and flash a code Table 28 If the other ...

Страница 53: ...peration status i e the limit is monitored at all times If the temperature limit opens three times within one hour it will lock on the indoor blower motor and a flash code is initiated See Table 28 Safety Controls The UCB monitors the temperature limit switch of electric heat units The control circuit includes the following safety controls Limit Switch Ls This control is located inside the heater ...

Страница 54: ...n After this 60 seconds the ICB will then use the call for the second stage of heat to control second stage operation of the GV When W1 is satisfied both valves are closed Second Stage Of Heating When the ICB receives a call for the second stage of heating W2 the ICB conducts a complete first stage ignition sequence If this sequence is satisfied the second main valve of the GV is opened When W2 is...

Страница 55: ...t Switch LS This control is located inside the gas heat compartment and is set to open at the temperature indicated in the Gas Heat Limit Control Settings Table 24 It resets automatically The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs thus shutting down the heater and energizing the blower Auxiliary Limit Switch ALS This control is located i...

Страница 56: ... room thermostat fan switch to off 9 Turn unit electrical power off Operating Instructions 1 Turn unit electrical power on NOTE Prior to each cooling season the crankcase heaters must be energized at least 10 hours before the system is put into operation 2 Set the room thermostat setting to lower than the room temperature 3 First stage compressors will energize after the built in time delay five m...

Страница 57: ...number of seconds it takes for one revolution of the dial calculate the cubic feet of gas consumed per hour See example below 5 If necessary adjust the high pressure regulator as discussed in the section Manifold Gas Pressure Adjustment Be sure not to over fire the furnace on Second stage If in doubt it is better to leave the Second stage of the furnace slightly under fired Repeat Steps 1 5 To det...

Страница 58: ...r the manifold pressure 3 Remove plastic cap covering HI and LO pressure adjustment screws 4 Turn on power to the unit 5 Set thermostat to call for second stage heat and start furnace 6 If necessary using a screwdriver turn the second stage adjustment screw adjacent to the HI marking on the valve clockwise to increase manifold pressure or counterclockwise to decrease manifold pressure Be sure not ...

Страница 59: ...step 4 4 Remove the heat shield on top of the manifold supports Burners are now accessible for inspection and or replacement NOTE Reverse the above procedure to replace the assemblies Make sure that burners are level and seat at the rear of the gas orifice Figure 34 Typical Flame Figure 35 Typical Gas Valve Charging The Unit All ZJ units use Thermal Expansion Devices Charge the unit to nameplate c...

Страница 60: ...cases it may be necessary to zero the ASCD for the compressors in order to perform troubleshooting To reset all ASCDs for one cycle press and release the UCB TEST RESET button once Flash codes that do and do not represent alarms are listed in Table 28 Table 28 Unit Control Board Flash Codes Flash Code Description Green LED 16 Red LED 8 Red LED 4 Red LED 2 Red LED 1 On Steady This is a Control Fail...

Страница 61: ...ameters for the currently displayed mode Option Byte or Heat Delay Heat Delay Setup Enter the Option Setup mode by pushing the OPTION SETUP STORE button and holding it for at least 2 seconds The green status LED Option Byte will be turned on and the red status LED Heat Delay is turned off Press the COMM SETUP SELECT button to toggle into the Heat Delay Setup the green LED will turn off and the red...

Страница 62: ...X Limit 5 Flame Present With Gas Off First Stage Gas Valve Energized With W1 Off Second Stage Gas Valve Energized With First Stage Gas Valve Off Gas Valve 6 Ignition Lockout Gas Flow Gas Pressure Gas Valve Flame Sensor STEADY OFF No Power Or Control Failure 24VAC or Control Table 31 VAV Control Board Flash Codes Flash Codes Description On Steady This is a Control Failure 1 Flash Not Applicable 2 F...

Страница 63: ...First Stage Call for 2nd Stage Cooling Yes Yes Loss of Call for Heating Loss of Call for Cooling Heat Off Cool Off Yes Yes No Call for ID Blower Fan off 10 secs Energize ID Blower Motor Yes Yes No Programming Program Unit Control Board Trip Failure No No Lossof Call for ID Blower Turn off ID Blower Motor Fan on 30 secs Yes No Yes No No Yes Yes No Power to Unit Initialize ASCD Call for heat Voltage...

Страница 64: ...524581 YIM I 0512 64 Johnson Controls Unitary Products Figure 39 Trip Failure Flow Chart ...

Страница 65: ... the UCB and for loose wiring 10 If the thermostat and UCB are properly wired replace the UCB On calls for cooling the supply air blower motor is operating but compressor 1 is not the room thermostat fan switch is in the AUTO position 1 If installed check the position of the economizer blades If the blades are open the economizer is providing free cooling and the compressors will not immediately o...

Страница 66: ...he C1 terminal wire and jumper it to the Y1 terminal DO NOT jump the Y1 to C1 terminals If the compressor engages the UCB has faulted 16 If none of the above correct the error replace the UCB On calls for the second stage of cooling the supply air blower motor and compressor 1 are operating but compressor 2 is not the room thermostat fan switch is in the AUTO position 1 If installed check the posi...

Страница 67: ...volts is not present at the C1 terminal check for 24 volts from the room thermostat at the UCB Y1 terminal If 24 volts are not present at the UCB Y1 terminal the UCB may have faulted Check for 24 volts at the Y1 ECON terminal If 24 volts is not present at Y1 ECON the UCB has faulted The UCB should de energize all compressors on a loss of call for the first stage of cooling i e a loss if 24 volts a...

Страница 68: ... operate replace the motor 6 If 24 volts is not present at M3 check that 24 volts is present at the supply air blower motor terminal on the UCB If 24 volts is present at the UCB terminal check for loose wiring between the UCB and M3 a If 24 volts is not present at the UCB supply air blower motor terminal check for 24 volts from the room thermostat If 24 volts is not present from the room thermosta...

Страница 69: ...temperature limit open wait for limit reset 5 If all are intact replace the ICB The draft motor runs and the spark ignitor sparks at the burner but the burner does not ignite and a gas odor is not detected at the draft motor outlet 1 Check to ensure gas is being supplied to the unit Confirm that the gas pressure to the unit is within the proper limits as described in the POST START CHECKLIST 2 Che...

Отзывы: