background image

5725848-XIM-A-0319

Johnson Controls Ducted Systems

49

Unexpected flame presence

If a flame is present without a call for heat (flash code 8), then 
the ICB will continue operation of the draft motor and the UCB 
will call for indoor operation when either of the temperature limit 
opens. If the unit is correctly wired and there is not a call for 
heat, then check for control voltage to the gas valve. If control 
voltage exists at the gas valve, then replace the ICB. If voltage 
is not present at the gas valve, then replace the gas valve.

Gas valve stuck off or on

If the pilot and/or the main valves are sensed to be off more 
than 1 second when commanded to be on, the control will shut 
off all outputs and enter a hard lockout (flash code 9). Likewise, 
if the pilot and/or the main valves are sensed to be on more 
than 1 second when commanded to be off, the control will shut 
off all outputs and enter a hard lockout (flash code 9). The 
control will not respond to thermostat demands during a hard 
lockout. The only way to recover from a hard lockout is to 
remove and reapply 24VAC power to the control.

Flame sense circuit failure

If the control detects an internal hardware failure in the flame 
sense circuit, it shuts off all outputs and enters a hard lockout 
(flash code 10). The control will not respond to thermostat 
demands during a hard lockout.  The only way to recover from a 
hard lockout is to remove and reapply 24VAC power to the 
control. If problem persist after removal and reapplication of 
24VAC power, the board may need to be replaced.

Symptomatic troubleshooting

On calls for heating, the draft motor operates and the furnace 
lights but the supply air blower motor does not energize after a 
short delay (the room thermostat fan switch is in “AUTO” 
position).

1.

Place the thermostat fan switch in the “ON” position. If the 
supply air blower motor energizes, go to Step 10.

2.

If the supply air blower motor does not energize when the 
fan switch is set to “ON,” check that line voltage is being 
supplied to the contacts of the M2 contactor, and that the 
contactor is pulled in. Check for loose wiring between the 
contactor and the supply air blower motor.

3.

If M2 is pulled in and voltage is supplied at M2, lightly touch 
the supply air blower motor housing. If it is hot, the motor 
may be off on inherent protection. Cancel any thermostat 
calls and set the fan switch to “AUTO”, wait for the internal 
overload to reset. Test again when cool.

4.

If M2 is not pulled in, check for 24 volts at the M2 coil. If 24 
volts is present at M2 but M2 is not pulled in, replace the 
contactor.

5.

Failing the above, if there is line voltage supplied at M2, M2 
is pulled in, and the supply air blower motor still does not 
operate, replace the motor.

6.

If 24 volts is not present at M2, check that 24 volts is 
present at the supply air blower motor terminal on the UCB. 

If 24 volts is present at the UCB terminal, check for loose 
wiring between the UCB and M2.

7.

If 24 volts is not present at the UCB supply air blower motor 
terminal, check for 24 volts from the room thermostat. If 24 
volts is not present from the room thermostat, check for the 
following:

• Proper operation of the room thermostat (contact 

between R and G with the fan switch in the “ON” 
position and in the “AUTO” position during operation 
calls).

• Proper wiring between the room thermostat and the 

UCB. 

• Loose wiring from the room thermostat to the UCB.

8.

If 24 volts is present at the room thermostat but not at the 
UCB, check for proper wiring between the thermostat and 
the UCB, i.e. that the thermostat G terminal is connected to 
the G terminal of the UCB, and for loose wiring.

9.

If the thermostat and UCB are properly wired, replace the 
UCB.

10. If the blower motor runs with the fan switch in the “ON” 

position but does not run shortly after the furnace has 
ignited when the fan switch is in the “AUTO” position, 
check the room thermostat for contact between R and G 
during “W1” calls.

On calls for heating, the supply air blower operates but the draft 
motor does not (the room thermostat fan switch is in the 
“AUTO” position).

1.

The draft motor has inherent protection. If the motor shell is 
hot to the touch, wait for the internal overload to reset.

2.

If the motor shell is cold with the room thermostat calling 
for heat, check if 24 volts is present at the room thermostat 
but not at the UCB, check for proper wiring between the 
thermostat and the UCB, i.e. that the thermostat “W1” 
terminal is connected to the “W1” terminal of the UCB, and 
for loose wiring.

3.

The draft motor is a 230 volt draft motor on all models 
regardless of unit supply voltage. If the ICB is flashing a 
code other than the heartbeat, then troubleshoot the device 
indicated by the fault code. If not, then remove power to the 
unit for more than 20 seconds. If upon restoring the power 
to the unit the draft motor does not start with a call for heat, 
then verify that terminal “L1” of the ICB has a minimum of 
120 volts to ground on 230 and 460 volt models or a 
minimum of 18 volts to ground on 575 volt models. If 
terminal “L1” does not have the minimum voltage, then 
check the wiring between the unit control box and the ICB 
on all models and on 460 volt models, the transformer in 
the gas heat compartment and its wiring. If terminal “L1” 
does have the minimum voltage, then check for the 
minimum voltage on terminal “IND” of the ICB on single 
stage models and terminal “IND HIGH” of the ICB on two 
stage models. If voltage is not present at the terminal, then 
verify wiring between the control box and the ICB. If all 
wiring is intact, then ICB is at fault. If voltage is present at 
the terminal on 230 and 460 volt models, then the draft 

Содержание ZF076

Страница 1: ...Burner air shutter adjustment 43 Checking gas input 43 Adjustment of temperature rise 44 Troubleshooting 45 Cooling troubleshooting guide 45 Gas heat troubleshooting guide 46 Flash code troubleshooti...

Страница 2: ...od 30 18 Unit dimensions rear view 31 19 Disconnect blower access location 31 20 Belt adjustment 36 21 Pressure drop across coil 37 22 Gas valve piping 40 23 Proper flame adjustment 43 24 Typical valv...

Страница 3: ...parts and electrical components installation and servicing of air conditioning equipment can be hazardous Only qualified trained ser vice personnel should install repair maintain or service this equi...

Страница 4: ...es refrigerant containers and recovery systems must be designed to handle R 410A If you are unsure consult the equipment manufacturer Failure to use R 410A compatible servicing equipment may result in...

Страница 5: ...mbustible material 4 For use with natural gas convertible to LP with kit This product must be installed in strict compliance with the enclosed installation instructions and any applicable local state...

Страница 6: ...d Filters Merv 8 4 Coil Guard CG STD Filter 5 2 Pleated Filter CG A Std Cabinet B HDF HingedFLTR Tooless DR E SSD SST Drain Pan F SSD HFD A No Economizer C Economizer w o Barometric RLF F Econ BAS Rdy...

Страница 7: ...al Code CSA C22 1 2 Installation Codes CSA B149 1 3 Local plumbing and waste water codes and 4 Other applicable local codes Refer to unit application data found in this document After installation gas...

Страница 8: ...air in accordance with section 5 3 of Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 Latest Edition in U S A or Sections 7 2 7 3 or 7 4 of Gas Installation Codes CSA B149...

Страница 9: ...f the evaporator coil and must be kept clean or replaced with same size and type Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown Minimum filter a...

Страница 10: ...2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 1 4 3 1 2 4 Second stage ot required on single stage he g units Jumper is required if there is n...

Страница 11: ...tolerances which must be maintained at the compressor terminals during starting and running OCC C RC G Y2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THER...

Страница 12: ...led heaters are wired for single point power supply Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper...

Страница 13: ...3 50 M3 S 0 47 0 57 0 57 0 61 CFM 1100 1200 1200 1300 4 380 415 3 50 M3 S 0 61 0 61 0 61 0 61 CFM 1300 1300 1300 1300 5 380 415 3 50 M3 S 0 75 0 75 0 75 0 75 0 75 CFM 1600 1600 1600 1600 1600 6 3 380...

Страница 14: ...uitable for the purpose NEVER USE A FLAME 6 The furnace and its individual manual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at te...

Страница 15: ...od slips in under the top of the access panel opening when installing Refer to Vent and Combustion Air Hood Figure 7 The vent hood is installed by inserting the top flange of the hood into the slotted...

Страница 16: ...EDs at the center left of the RRS Economizer Controller indicate POWER green Lit whenever 24 volts AC power is present to the RRS Economizer Controller C and R pins FAULT red Lit then flashes during t...

Страница 17: ...t available Free cooling operation When the control determines that the outside air is suitable the first stage of cooling will always be free cooling Thermostat In free cooling with a thermostat inpu...

Страница 18: ...No inputs are present for non modulating power exhaust Outputs a 2 10 VDC from ECON on Economizer Expansion module b 24 vac from EX FAN to energize exhaust fan on Economizer Expansion module Operation...

Страница 19: ...istor MAT parameter reports input status F C 3 65 VDC reading MAT to COM with open circuit Read only use in current control revision IN1 MAT LEDs at left on upper edge of economizer board POWER POWER...

Страница 20: ...power exhaust actuator and economizer actuator Connects through circuit trace to 24V IN pin HOT ECON 2 10 VDC output for the Economizer actuator Econ parameter reports output status 0 100 Used to posi...

Страница 21: ...negative for the indoor air quality sensor Connects through circuit trace to 24V IN pin COM R 24V 24 VAC hot supplied for the outdoor air quality sensor Connects through circuit trace to 24V IN pin HO...

Страница 22: ...pad layout Keypad The four navigation buttons illustrated in Fig 8 are used to scroll through the menus and menu items select menu items and to change parameter and configuration settings Using the ke...

Страница 23: ...E Economizer Module accessory instruction P N 1150208 UAI A 0514 included in this instruction packet for additional menu information Economizer setup and configuration Before being placed into service...

Страница 24: ...ry the economizer sets the economizing mode to YES economizing is available When conditions are above the selected boundary the conditions are not good to economize and the mode is set to NO Fig 9 sho...

Страница 25: ...LEFT FRONT Table 8 ZF036 076 metric Size Tons Model Weight kg Center of Gravity mm 4 point Load Location kg 6 point Load Location kg Shipping Operating X Y A B C D A B C D E F 036 3 0 ZF036 228 225 10...

Страница 26: ...F 15 45 25 70 25 55 25 55 Gas Limit Setting F Direct Drive 240 210 Gas Limit Setting F Belt Drive 210 210 Gas piping connecting in 1 2 1 2 1 2 1 2 DIMENSIONS inches Length 82 1 4 82 1 4 82 1 4 82 1 4...

Страница 27: ...VAP FAN DATA Quantity 1 1 Fan Size Inch 12 x 10 12 x 11 Type Centrifugal Centrifugal Motor Sheave 1VL44 IVM50 Blower Sheave AK54 AK56 Belt A35 A36 Motor HP each 1 1 2 1 1 2 RPM 1450 1450 Frame size 56...

Страница 28: ...3 25 2EH04512046 12 2 2 18 5 29 4 30 415 3 50 7 8 51 5 12 1 1 3 4 24 NONE 15 3 20 2EH04510746 5 1 1 7 1 15 3 20 2EH04511046 7 5 1 10 4 19 2 20 2EH04511546 10 2 2 14 2 23 9 25 2EH04512046 14 6 2 20 3 3...

Страница 29: ...as heat front view 829 325 8 1140 447 8 64 21 2 213 83 8 292 111 2 445 171 2 445 171 2 181 77 8 171 63 4 206 81 8 137 53 8 2089 821 4 165 61 2 178 7 111 43 8 165 61 2 819 321 4 819 32 1 4 mm inch 829...

Страница 30: ...omizer rain hood Figure 17 Unit with fixed outdoor air motorized damper rain hood DETAIL A 699 271 2 699 271 2 41 15 8 260 101 4 1140 447 8 502 193 4 mm inch DETAIL B 454 177 8 184 71 4 699 271 2 485...

Страница 31: ...th Belt Drive Option Control Box Access A B Wiring Entry See Detail B Mounting Bracket for Disconnect Switch Field Supplied Field Supplied Disconnect Switch Location Blower Motor Access Filter Access...

Страница 32: ...25 LOW 0 67 645 0 63 620 0 58 595 0 53 575 CFM UNIT TONNAGE MOTOR SPEED AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS 31 HI 1699 825...

Страница 33: ...25 1101 980 1130 1045 1158 1075 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Страница 34: ...75 1118 1150 1148 1250 1176 1360 CFM UNIT TONNAGE AIR FLOW CFM AVAILABLE EXTERNAL STATIC PRESSURE IWG 0 20 0 30 0 40 0 50 0 60 0 70 0 80 RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM...

Страница 35: ...id bases and are inherently protected These motors can be selected to operate into their service factor because they are located in the moving air upstream of any heating device Table 20 Static resist...

Страница 36: ...4 Knowing the pressure drop across a dry coil the actual volumetric flow rate through the unit can be determined from the curve in Pressure Drop vs Supply Air flow rate Figure 21 After readings have b...

Страница 37: ...the fan off delay for cooling To be available a compressor must not be locked out due to a high or low pressure switch or freezestat trip Simplicity Lite Control or Evaporator Low Limit sensor detecti...

Страница 38: ...ser fan If the call for cooling is still present at the conclusion of the ASCD the UCB will re energize the halted compressor Should a freezestat open three times within two hours of operation the UCB...

Страница 39: ...and on any compressor reset or lock out Flash codes or error messages The UCB will initiate flash a code on the Simplicity Lite Control see Table 26 or sent error message to the LCD Smart Equipment Co...

Страница 40: ...peration of the draft motor The UCB continues the operation of the indoor blower for a configurable amount of time after the call for heat is satisfied Two stage furnace only If a W1 only call for hea...

Страница 41: ...of the main gas valve will shut off the flow of gas to both the pilot and main gas valves Centrifugal switch The centrifugal switch is mounted on the end of the draft motor and it is an integral part...

Страница 42: ...installed Operating instructions Lighting the pilot and main burners 1 Turn off electric power to unit 2 Turn room thermostat to lowest setting 3 Turn gas valve knob to on position 4 Turn on electric...

Страница 43: ...unction properly Burner instructions To check or change burners pilot or orifices CLOSE MAIN MANUAL SHUT OFF VALVE AND SHUT OFF ALL ELECTRIC POWER TO THE UNIT 1 Remove the screws holding either end of...

Страница 44: ...e readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat Increase the blower Volumetric Flow Rate to decrease t...

Страница 45: ...terminal is connected to the G terminal of the UCB and for loose wiring 10 If the thermostat and UCB are properly wired replace the UCB On a call for cooling the supply air blower motor is operating b...

Страница 46: ...1 ECON terminal 13 For units with economizers If 24 volts is present at the Y1 OUT terminal check for 24 volts at the Y1 ECON terminal If 24 volts is not present check for loose wiring from the Y1 OUT...

Страница 47: ...e ICB LED If it now flashes the heartbeat then the fault was a bad connection between the harness connector and the ICB connector or a broken wire exists in the harness With the harness connected to t...

Страница 48: ...manual reset type If either one opens then the ICB removes power to the gas valve and the UCB energizes the indoor blower until the primary limit automatically resets or the auxiliary limit is manuall...

Страница 49: ...e the motor 6 If 24 volts is not present at M2 check that 24 volts is present at the supply air blower motor terminal on the UCB If 24 volts is present at the UCB terminal check for loose wiring betwe...

Страница 50: ...es for obstruction and alignment Removal procedure is described in BURNER INSTRUCTIONS on page 43 Clean or replace burner orifices and burners as needed Unit flash codes Various flash codes are utiliz...

Страница 51: ...Operation 1 Flash Not Applicable 2 Flashes Control waiting ASCD1 1 These flash codes do not represent alarms 3 Flashes HPS1 Compressor Lock out 5 Flashes LPS1 Compressor Lock out 7 Flashes FS1 Compres...

Страница 52: ...the UCB microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in serie...

Страница 53: ...t indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1 1...

Страница 54: ...reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on right edge of UCB RAH Return Air Humidity input from 0 10 VDC 0 100 RH sensor Input required for rehe...

Страница 55: ...ut for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operation G input or schedule demand C1 24 VAC hot output for compressor 1 If demand is present and permis...

Страница 56: ...er of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the J8...

Страница 57: ...indicates the UCB is supplying power to the communication sub board 1 When wiring unit and other devices using the SA Bus and FC Bus see Table 29 Table 28 Smart Equipment UCB details continued Descri...

Страница 58: ...5848 XIM A 0319 58 Johnson Controls Ducted Systems Typical wiring diagrams Simplicity Lite control board Figure 28 Typical ZF036 048 with Simplicity Lite control with without electric heat wiring diag...

Страница 59: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 59 Figure 29 Typical ZF036 048 with Simplicity Lite control with gas heat wiring diagram...

Страница 60: ...5725848 XIM A 0319 60 Johnson Controls Ducted Systems Figure 30 Typical ZF060 076 with Simplicity Lite control with without electric heat wiring diagram...

Страница 61: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 61 Figure 31 Typical ZF060 076 with Simplicity Lite control with gas heat wiring diagram...

Страница 62: ...5725848 XIM A 0319 62 Johnson Controls Ducted Systems Smart Equipment Figure 32 Typical ZF036 048 with Smart Equipment control with without electric heat wiring diagram...

Страница 63: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 63 Figure 33 Typical ZF036 048 with Smart Equipment control with gas heat wiring diagram...

Страница 64: ...5725848 XIM A 0319 64 Johnson Controls Ducted Systems Figure 34 Typical ZF060 076 with Smart Equipment control with without electric heat wiring diagram...

Страница 65: ...5725848 XIM A 0319 Johnson Controls Ducted Systems 65 Figure 35 Typical ZF060 076 with Smart Equipment control with gas heat wiring diagram...

Страница 66: ...LDO VWDUW XS 7KLV FRQILGHQFH LV VXSSRUWHG E WKH GD GHDOHU SURWHFWLRQ FRYHUDJH SRUWLRQ RI RXU VWDQGDUG ZDUUDQW SROLF ZKLFK VWDWHV WKDW RKQVRQ RQWUROV XFWHG 6 VWHPV ZLOO FRYHU SDUWV DQG ODERU RQ QHZ HTX...

Страница 67: ...LQ WKH IXOO RSHQ SRVLWLRQ DQG WKH IUHTXHQF GULYH LV RSHUDWLQJ DW R QRW SURFHHG ZLWK WKH HTXLSPHQW VWDUW XS ZLWKRXW WKH GHVLJQ 0 LQIRUPDWLRQ HVLJQ 6XSSO LU 0 BBBBBBBBBBBBBBBBBBBBBBBBBB HVLJQ 5HWXUQ LU...

Страница 68: ...RPSOHWH LU 0RYLQJ QVSHFWLRQ RPSOHWHG 6HH 1RWHV OLJQPHQW RI GULYH FRPSRQHQWV HOW WHQVLRQ DGMXVWHG SURSHUO ORZHU SXOOH V WLJKW RQ VKDIW EHDULQJ VHW VFUHZV WLJKW ZKHHO WLJKW WR VKDIW 3UHVVXUH VZLWFK RU W...

Страница 69: ...JH UHTXLUHG WR REWDLQ WKH FRUUHFW DLUIORZ DV LW QHFHVVDU WR LQFUHDVH RI GHFUHDVH WKH DLUIORZ WR PHHW WKH GHVLJQ FRQGLWLRQV I WKH PRWRU SXOOH VL H ZDV FKDQJHG PHDVXUH WKH RXWVLGH GLDPHWHUV RI WKH PRWRU...

Страница 70: ...BB 5 5HWXUQ LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 0L HG LU 7HPSHUDWXUH BBBBBBBBBBBBBBBB GE BBBBBBBBBBBBBBBB ZE BBBBBBBBBBBBBBBB 5 6XSSO LU 7HPSHUDWXUH BBBBBBBBBBBBB...

Страница 71: ...BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB...

Отзывы: